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r- --� + 77 FAN SCHEDULE FAN No. MANUFACTURER AND MODEL No. RPM HP CFM 8" SP. ELECT SERVICE V /O /HZ DIMENTIONS W x L x H (IN.) WEIGHT LB 3. REMARKS TYP. TOILET RM. EXHAUST FAN 3 & 4 NUTONE QT 110 500 1/4 100 0 1/8" 115/1/60 9 x 9 x 4 6 W/• GRILLE 4 "0 DUCT ROOF CAP 208/230 3 60 60/60 10.50 12.00 550 POUNDS 47• 81" 35" 910 CFM REPLACEMENT OF EXISTING UNIT R RETURN AIR TITUS PAS HVAC LEGEND El SUPPLY AIR DIFFUSER ® SUPPLY AIR DIFFUSER O T THERMOSTAT 18" D SUPPLY AIR DUCT CROSS SECTION VOLUME DAMPER, AT TAKE OFF FLEXIBLE ROUND DUCT XX E.F. FAN O SMOKE DETECTOR RIGID FIBERGLASS DUCT SPIN COLLAR WITH VOLUME DAMPER AND LOCKING QUADRANT AIR CONDITION EQUIPMENT SCHEDULLE USE MARK MANUFACTURER MODEL TONS CFM ELECTRICAL V PH HZ BREAKER EER SEER WEIGHT DIMENLONS H O/A AIR DISTRIBUTION 140 REHEEM RLMA -AO60 5.0 1900 208/230 3 60 60/60 10.50 12.00 550 POUNDS 47• 81" 35" 910 CFM REPLACEMENT OF EXISTING UNIT R RETURN AIR TITUS PAS INSULATED FLEXIBLE DUCT GLASS 1 1/2- WITH POLYETHYLENE JACKET AND STEEL WIRE REINFORCING DIFFUSER OFFICE AND RESTROOMS TAKE - OFF DETAIL NTS 3/8" LAG BOLT AT 24" O.C. PR BU NAII ECH AN I CAL PLAN SCALE: 1/4" = 1' -0" OUTSIDE AIR CALCULATIONS PER ASHRAE 62 -89 1.) CUSTOMER AREA MAX.: 40 CUST. 3 EMPLOYEES 0/A CFM REQUIRED 20 CFM / PERSON CFM = 43 X 20 = 860 2.) KITCHEN AREA = 169 S.F. 0 /A. AIR REQUIRED 15 CFM /PER 20 PERSONS/ 1000S.F. CFM = 20 X 169/1000 X 15 = 50 TOTAL CFM . REQUIRED = 910 CFM PROVIDED 910 A/C UNIT (ROOF TOP) INSTALLATION DETAIL NO SCALE NIT 7) MIN. AIR DISTRIBUTION SCHEDULE SYMBOL USE CFM TYPE DESCRIPTION NECK PANEL MAT'L DESIGN, MFGR. & MODEL CFM A DISTRIBUTION 230 CEIL DIFFUSER PERFORATED 8" 0 24 X 24 TITUS PAS g DISTRIBUTION 140 CE DIFFM- PERFORATED LAY -IN 6" 0 24 X 24 MS PAS C DISTRIBUTION 50 CEIL DIFFUSER 4" Z 12 X6 TITUS PAS R RETURN AIR TITUS PAS CONDENSING UNITS BOLT THRU W/1" X1.5 "LG.BOLTS, NUTS & WA.— TO STAND WINDS OF OVER 120 MPH WEATHER HOOD PIPE INSULATION - PITCH PAN BUILT -UP ROOF COOLER CONDENSING UNIT INSTALLATION DETAIL SCHEME NO SCALE STRUCTURAL SUPPORT 4'X4 -XI' STEEL BEAM OF ANGLE r W J Q W U 5 cr w V) X W HVAC DESIGN REQUIRES YES NO DUCT SMOKE DETECTOR FIRE DAMPER (S) SMOKE DAMPER (S) FIRE RATED ENCLOUSURE FIRE RATED ROOF FLOOR CEILING ASSEMBLY FIRE STOPPING SMOKE CONTROL ALUMINUN PIPE A/C BASE BY R.M. ENTERPRISES DADE CO. PROD.APP. #96- 1206.01 FLASH AND SEAL TO ROOF (BY ROOF CONTRACTOR) BOLT THRU CONC. W /3 /8 "X6'LG. BOLTS, NUTS 8 WASHERS 8 STEEL PLATE I" THICK TO STAND WINDS OVER 120 MPH � 4 N.T.S. >t ;4i� , s 4. PROJECT No Q p O r o Nz I F- CC N W G N = FILE: solerest 0 OO LL. I— Z Q ZQ Q ~ �Wj