05-1471-027RTU -1
ROOF
IAA ,flnnr
NE
N
E
(TYPICAL)
1 ST FLOOR
FIRE ALARM RISER DIAGRAM (FACPm2,3,4,5)
NOT TO SCALE
1) ALL WIRING SHALL BE RUN IN CONDUIT (EMT) PER MANUFACTURER'S REQUIREMENTS.
2) gRIISERq�DIIAy�G�RAGM gDNE�PICTS GENERAL SYSTEM LAYOUT ONLY
3) EQVPMENT INUPPUERE(HFM& OC%S SHALL BE THE RESPONSIBILITY
4) PROVIDE DUCT SMOKE DETECTORS AS REQUIRED BY NFPA AND FINAL
DUCT INSTALLATION COORDINATE WITH MECH. CONTRACTOR.
5) PROVIDE A TEST SWITCH AT CEILING FOR EACH DUCT SMOKE DETECTOR.
OVERHEAD
2ND
1 st Floor
TO FIRE ALARM
CONTROL PANEL
ROOF
2nd floor
NOTIFIER #500
WITH ADJUSTABLE RELAYS
OL PROVIDE MINIMUM OF 24 AMPS
OF 24V DC POWER.
120V SUPPLY
(SEE FLOOR PLAN) 1st floor
FIRE ALARM RISER DIAGRAM (FACP=I)
NOT TO SCALE
NOTES:
1) ALL WIRING SHALL BE RUN IN CONDUIT (EMT) PER MANUFACTURER'S REQUIREMENTS.
2) RISER DIAGRAM DEPICTS GENERAL SYSTEM LAYOUT ONLY
3) EQUIPMENT INUPPUEREAND 1 %&1CTOR SHALL BE THE RESPONSIBILITY
ELECTRICAL POWER RISER DIAGRAM
SCALE: NONE
NOTES (POWER RISER DIAGRAM ONL
11_ .VS "1 r1Lt..: r'IC�r� Uf f(UUGI i
WIRING
CHECK NAi1 EPLATEDA7 OF A/C
EQUIPMENT, HOT WATER HEATERS
AND OTHER EpUIP1 ENT TO OBTAIN
CORRECT iVIRE SIZES AND
OVERCURRENT PROTECTION
•DE DATE SERVICE CAPACTi '-- .
MUST BE PROVIDE,
SUBJECT TO ELECTRIC'
Ai
INSPECTION
1O NEW PAD MOUNTED TRANSFORMER (SECONDARY: 208Y/120, 3 PHASE, 4 WIRE, 60 HERTZ).
4O
GROUNDING ELECTRODE CONDUCTOR: PROVIDE 3/0 CU. PROVIDE TWO NEW 5/8" X
10'
COORDINATE WITH UTILITY COMPANY (CONTACT MS. BLANCA NODAR
0" LONG COPPER CLAD GROUND RODS WITH EXOTHERMIC WELDS; PROVIDE NEW 3/0 CU
(1- 305 - 387 -6647) AND PAY FOR ALL SERVICE CHARGES AND ACCESSORIES (SUCH
TO BURIED METALLIC WATER PIPE WITH 10' OF PIPE (MINIMUM) IN THE GROUND
AS METER HOUSING, CONDUITS, CONCRETE PAD AND CONNECTION, AS REQUIRED). PROVIDE
(COORDINATE LOCATION WITH EXISTING FIELD CONDITIONS) AND PROVIDE APPROVED CLAMP AND
BOLLARD TRANSFORMER PROTECTION (COORDINATE WITH PE REQUIREMENTS).
HANDHOLE ACCESS COVER; PROVIDE CONNECTION TO EXISTING FOOTING GROUND AT OLD
GROUNDING ELECTRODE CONDUCTOR.
SHORT CIRCUIT ANALYSIS:
O
NEW CT CABINET (HOT SEQUENCING METERING)
A AVAILABLE SHORT CIRCUIT CURRENT ON SECONDARY BUSHINGS OF THE NEW
42K AIC COMPONENT
TRANSFORMER: 55,000A SYM.
B MDP -1: CALCULATED AVAILABLE FAULT CURRENT LESS THAN 42K AIC.
O6
FEEDER 3 SETS, EACH; 3 #500 MCM THWN/THNN CU. 1 #500MCM THWN/THNN CU. N, 1#3/0
THWN/THNN CU G. 1 4"C.
SELECT ALL EQUIPMENT 42K AMP SYM WITHSTAND.
O7
1000A MLO MAIN DISTRIBUTION PANEL 42K AIC (SEE SCHEDULE).
RECONFIRM AVAILABLE SHORT CIRCUIT CURRENTS FOR ACTUAL TRANSFORMER BEING
INSTALLED WITH UTILITY COMPANY PRIOR TO ORDERING EQUIPMENT OR COMMENCING WORK.
O8
SURGE SUPPRESSOR; LIEBERT SERIES #LM125120YANSE —WNA (SEE SPECIFICATIONS)
VOLTAGE DROP: FEEDERS LESS THAN 2%, BRANCH CIRCUITS LESS THAN 3%.
O9
FEEDER; 3 #1/0 THWN/THNN CU. 1 #1/0 THWN/THNN CU. N, 1 #6 THWN/THNN CU G,
2 "C.
MDP LOAD ANALYSIS (NEC 220 SERVICE ENTRANCE CONDUCTOR SIZING):
1�
SINGLE POINT GROUNDING ELECTRODE CONDUCTOR: PROVIDE 3/0 CU. AND ONE NEW
5/8" X 10' ROD
IOAD
11
FEEDER; 3 #4/0 THWN/THNN CU. 1 #4/0 THWN/THNN CU. N, 1 #4 THWN/THNN CU G.
2- 1/2 "C.
167.3
FANS 19.3
C OLJNG N/A
12
FEEDER RTU #1; 3 #3/0 THWN/THNN CU. 1 #3/0 THWN/THNN CU. N, 1 #6 THWN/THNN
CU G, 2- 1/2 "C.
HEATING 126.0
LARGERST MOTOR 26.9
_33T
13
FEEDER; 3 #4/0 THWN/THNN CU. 1#4/0 THWN/THNN CU. N, 1#4 THWN/THNN CU G.
2-1/2"C.
14
FEEDER; 3 #1 THWN/THNN CU. 1#1 THWN/THNN CU. N, 1#6 THWN/THNN CU G, 2 "C.
O 1200A SERVICE LATERAL• 4 SETS, EACH: 4# 500MCM THWN/THHN CU, 4 "C. REMOVE
EXISTING SERVICE LATERAL (CONDUIT AND CONDUCTORS). PROVIDE NEW SERVICE LATERAL
15
FEEDER; 3 #3/0 THWN/THNN CU. 1#3/0 THWN/THNN CU. N, 1#6 THWN/THNN CU G,
2 -1 /2 "C.
AS SHOWN.
3O METER ASSEMBLY: 1" METERING CONDUIT WITH PULLWIRE (METERING CONDUCTORS FROM
16
FEEDER RTU #2; 3 #3/0 THWN/THNN CU. 1#3/0 THWN/THNN CU. N, 1#6 THWN/THNN
CU G. 2-1/2"C.
C/T'S TO METER BY UTILITY COMPANY). METERING SOCKET, FURNISHED BY THE UTILITY
COMPANY, INSTALLED BY ELECTRICAL INSTALLER. LOCATE METER ON EXTERIOR OF THE
17
FEEDER RTU #3; 3 #3/0 THWN/THNN CU. 1 #3/0 THWN/THNN CU. N, 1 #6 THWN/THNN
CU G, 2- 1/2 "C.
BUILDING AS DIRECTED BY UTILITY COMPANY COORDINATE EMS CONNECTION TO METER.
ROPERTY LINE
S. W. 41 T H
ANY PLANT DEVIATION (CHANGE, MUST COMPLY WITU .
STREET MUST Dc r�, � N�
lld �'�;01�ED CE1=0I�E P. A. #
PISPIECTION REQUEST F. Q. C, #
w
NEW PAD MOUNTED TRANSFORMER
TO ALL UTILITY CO. REQUIREMENTS.
Q
��
El
EXISTING
2 STORY BUILDING
1 SITE PLAN
E0.3 SCALE: NTS
NOTES:
1. SEE SYMBOLS, SCHEDULES, NOTES AND DETAILS.
2. COORDINATE PAD MOUNTED TRANSFORMER LOCATION WITH UTILITY.
"SUBJECT TO
L ELD INSPECTION ,,
cn SUBJECT TO FL"PI "A
BUILDING E pLUS
LOCAL 'I "MEN I S
BY:
Notes:
Revisions:
8/15/05 PLAN REVISION
8/22/05 PLAN REVISION
9/23/05 PLAN REVISION
Seal:
,'`II,1111111111'lll,,l�/',//'
.•..,,•
• 4
11111$11111111111� 0'0 .
Consultants:
Im
ARCHITECTURAL ENGINEERING INCORPORATED
3442 EAST LAKE ROAD, PALM HARBOR, FL 34683
CONSULTING ENGINEERS (727) 784 -1472
CERTIFICATE OF AUTHORIZATION: FL 3886
W. RONALD MCILVEEN FL PE 30270
• 4r
1�♦ '�` ■
ELEMENTS
ARCHITECTS -INTERIOR DESIGNERS
Tampa Office
The Edgewater Building
600 SOL'tii = Magnolia Avenue _
Suite 15& -1- -
Tamp7, Florida -3S606 - ^ - - - -
Phon^_�813) 25•� -0555
Fay 81:> 251 -0567
Miami Office
4240 Southwest , 3rd StreeT
Miami, Florida 3-3134 _ _ _, - _
Phone (305) 441 --7617
Fax (305) 774,1123
Nicholas Puglis� Arch;tect License #AF12460
ELEMENTS Stct_' License--#A/1.000234-1
WACHOVIA
WEST GABLES BRANCH
5880 BIRD ROAD
MIAMI, FLORIDA
Drawing No. /Date 5/2/05
E0.3
04- 028/05143
Drawing Title /Scale /Drawn by E\/D
ELECTRICAL RISER
SCALE: