05-1471-022ROOFTOP AIR CONDITIONING UNIT SCHEDULE
DAMPER
RTU RTU
RTU
UNIT NO. 1 2
3
LOCATION
ROOF
ROOF
INLET SIZE ON
ROOF
SERVICE
1ST FLOOR
2ND FLOOR N/W
12
2ND FLOOR N/E
TOTAL COOLING -MIN (MBH)
214
187
12
187
SENSIBLE COOLING -MIN (MBH)
167
127
12
127
COIL EAT - COOLING (DB/WB)
78.98166.57
80.25168.14
NOTE 2
80.25168.14
COIL LAT- COOLING (OB/WB)
55154.29
55/54
NOTE 2
55/54
COOLING - OPERATING STEPS
2
2
6004200
2
TOTAL AIR (CFM)
7,275
5,090
3764 -0
5,040
OUTSIDE AIR (CFM)
1500
1500
NOTE 3
1,480
ESP (IN WG)
1
0.85
STEPS
0.85
FILTER SP -INIT /FINAL (IN WG)
0.3
0.3
NOTE 3
0.3
ELECT. HEAT
EXISTING
EXISTING
0.6
42 KW
RPM
898
898
0.6
898
BHP - MAX
3.98
2.34
NOTE 3
2.34
MOTOR (HP)
NOTE 3
NOTE 3
NOTE 3
NOTE 3
ELECT (FLA/MCA/MOCP)
EXISTING
EXISTING
NOTE 3
136/166/175
ELECT (V /P /HZ)
208/3/60
208/3/60
NOTE 3
208/3/60
EER- MIN
10.8
10.8
40
10.8
WEIGHT (LBS)
EXISTING
EXISTING
MANUFACTURER
2000
MANUFACTURER
CARRIER
CARRIER
ENVIRO-TEC
CARRIER
MODEL NO.
50HJ020
50HJ016
FINISH
50HJ017
REMARKS
2, EXISTING
2, EXISTING
SDR
1
REMARK NUMBERS:
REMARKS
1. NEW PACKAGED ROOFTOP AIR CONDITIONING UNIT WITH: 14" HIGH FULL
1 -5
PERIMETER INSULATED ROOF CURB, CONTROLS AND ROOM
1 -5
THERMOSTAT TO START UNIT, HUMIDISTAT
1 -5
INTEGRAL ELECTRICL HEATER WITH 2 STEPS AND INTEGRAL CB AND
1 -5
CONTROLS, TIE DOWN KIT, 1 INCH FILTERS, EXHAUST FAN INTERLOCK,
RTU-2
SINGLE POINT POWER CONNECTION, NON -FUSED DISCONNECT,
RTU-2
LOW AMBIENT CONTROL TO 0 DEGREES AMBIENT, OUTSIDE AIR HOOD
RTU-2
HEAD PRESSURE CONTROL, MOTORIZED OA DAMPER. PROVIDE
1
FIELD INSTALLED NEOPRENE ISOLATION BETWEEN UNITAND
VAV2 -1
FACTORY CURB AND SECURE UNIT TO CURB.
AV2 -3
2. CONTRACTOR TO PROVIDE THE FOLLOWING FOR RTU -1 AND RTU -2:
VAV2 5
A. REWIRE UNIT TRANSFORMER INCLUDING ALL TAPPING CONNECTIONS.
All
8
B. REPLACE EXITSING HEATER WITH KW TO MATCH EXISTING. COORDINATE VOLTAGE.
C. REPLACE ALL REFRIGERANT.
DAMPER
D. REPLACE ALL AUTOMATIC TEMPERATURE CONTROLS IN UNIT.
DAMPER
E. MANUFACTURER TO RECERTIFY COMPLETE UNIT FOR FINAL INSTALLATION.
INVARIABLE VOLUME BOX SCHEDULE
RTU-1
UNIT NO. VAV1 -1
GENERAL MECHANICAL (HVAC) NOTES:
M -1 REGULATORY REQUIREMENTS: PROVIDE ALL WORK TO MEET OR EXCEED MINIMUM
REGULATORY REQUIREMENTS INCLUDING:
FLORIDA BUILDING CODE - 2001, 2ND EDITION WITH 2003 REVISIONS
FLORIDA FIRE PREVENTION CODE: 2002 EDITION (WITH AMENDMENTS)
NFPA 1 - 2000 EDITION
ADVISE THE ARCHITECT OF ANY CHANGES IN THE CONTRACT DOCUMENTS THAT MAY
BE REQUIRED IN ORDER TO MEET CODE, PRIOR TO WORK (ORDERING, ROUGHING OR
INSTALLING).
M -2 COORDINATION: COORDINATE WITH OTHER WORK (INCLUDING ELECTRICAL AND
ARCHITECTURAL) FOR AVAILABLE SPACE, SEQUENCE OF INSTALLATION, AND
INSTALLATION REQUIREMENTS. PRIOR TO COMMENCING CONSTRUCTION. ADVISE THE
ARCHITECT OF ANY CHANGES IN THE CONTRACT DOCUMENTS THAT MAY BE REQUIRED
FOR THE WORK TO BE PERFORMED.
M -3 EXISTING FIELD CONDITIONS: THE CONTRACT DOCUMENTS INDICATE THE DESIGN
INTENT USING AVAILABLE INFORMATION. THE CONTRACTOR IS TO ADVISE THE
ARCHITECT IF EXISTING CONDITIONS DIFFER FROM THOSE SHOWN. ALSO ADVISE THE
ARCHITECT IF CODE OR SAFETY CONFLICTS EXIST. THE CONTRACTOR IS REQUIRED
TO INSPECT THE SITE (PRIOR TO BID) TO BECOME FAMILIAR WITH CONDITIONS AND
INSTALLATION DETAILS THAT WILL AFFECT HIS WORK. CHANGES IN THE CONTRACT
SUM AND CONTRACT TIME WILL NOT BE ALLOWED FOR FAILURE TO INVESTIGATE FIELD
CONDITIONS. ALL WORK IS NEW, UNLESS NOTED OTHERWISE
M -4 BASIS OF DESIGN: THE MECHANICAL CONTRACT DOCUMENTS HAVE BEEN PREPARED
USING THE FOLLOWING DATA IN THE CALCULATIONS (SIMPLIFIED FOR PRESENTATION
HERE):
INDOOR OUTDOOR
SUMMER 75 DB /50X RH 90 DB /79 WB
WINTER 72 DB 50 DB
ADVISE THE ARCHITECT IF MODIFICATIONS TO THE BUILDING CONSTRUCTION ARE
MADE (TO DETERMINE EFFECT ON MECHANICAL DESIGN AND EFFECT ON BUILDING
ENERGY EFFICIENCY CALCULATIONS).
M -5 DEVICE LOCATIONS: REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF
AIR OUTLETS, AIR INLETS. AND OTHER CEILING ITEMS (TO AVOID CONFLICTS). LOCATE
ALL PIPING AND DUCTWORK IN FINISHED ROOMS OR SPACES WITHIN CONCEALED
LOCATIONS (FURRED CHASES OR SUSPENDED CEILINGS, AS AVAILABLE). DO NOT
LOCATE PIPING OR DUCTWORK ABOVE ELECTRICAL SWITCHBOARDS OR PANELBOARDS.
M -6 SIZES: WHEN A PIPE OR A DUCT SIZE IS NOT INDICATED. SIZE THAT PIPE OR DUCT
USING THE LARGER ADJACENT UPSTREAM SIZE, UNLESS A SMALLER SIZE IS APPROVED
BY THE ARCHITECT. PROVIDE 3/4 INCH MINIMUM PIPE SIZE, UNLESS SPECIFICALLY
NOTED OTHERWISE. FOR SIZES NOT INDICATED ON PLANS. REFER TO EQUIPMENT
DETAILS, FLOW DIAGRAMS, RISER DIAGRAMS, AND OTHER LOCATIONS IN THE CONTRACT
DOCUMENTS (DRAWINGS AND SPECIFICATIONS) FOR INFORMATION.
M -7 PRIOR TO ROUGHING, VERIFY ADEQUATE CLEARANCES FOR DUCTWORK, OTHER WORK.
ELECTRICAL, AND LIGHTING
M -8 OUTSIDE AIR DEMAND QUANTITIES ARE CALCULATED BASED ON THE FOLLOWING:
A RTU -1: PEOPLE x 20 = 1500 CFM
B RTU -2: PEOPLE x 20 = 1500 CFM
C RTU -3: PEOPLE x 20 - 1480 CFM
R LM RTU•1 RTU-1 RTU-1 RTU-1 RTU-1 RT1U•1 I
VAV1 -2 VAV1 -3 VAV1 -4 VAV1 -5 VAV1 -6 VAV1 -7 VAVII-8
TYPE
DAMPER
DAMPER
DAMPER
DAMPER
DAMPER
DAMPER
DAMPER
DAMPER
INLET SIZE ON
12
12
12
12
12
12
8
16
INLET BRANCH DUCT SIZE (IN)
12
12
12
12
12
12
8
16
MIN COOL AIRFLOW ( CFM)
NOTE 2
NOTE 2
NOTE 2
NOTE 2
NOTE 2
NOTE 2
NOTE 2
NOTE 2
MAX COOL AIRFLOW RANGE(CFM)
863- 1725
575-1150
6004200
550 - 1100
488- 975
463 -925
225450
3764 -0
ELECTRIC HEATER (KWj
NOTE 3
NOTE 3
NOTE 3
NOTE 3
NOTE 3
NOTE 3
NOTE 3
NOTE 3
STEPS
NOTE 3
NOTE 3
NOTE 3
NOTE 3
NOTE 3
NOTE 3
NOTE= 3
NOTE 3
TOTAL SP LOSS (IN WG)
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.5
ELECT (FLA/ MCA /MOCP)
NOTE 3
NOTE 3
NOTE 3
NOTE 3
NOTE 3
NOTE 3
NOTE 3
NOTE 3
ELECT (V/PH/HZ)
NOTE 3
NOTE 3
NOTE 3
NOTE 3
NOTE 3
NOTE 3
NOTE 3
NOTE 3
WEIGHT
40
40
40
40
40
40
40
220
MANUFACTURER
ENVIRO-
ENVIRO-TEC
ENVIRO-TEC
ENVIRO-TEC
ENVIRO-TEC
ENVIRO-TEC
ENVIRO-TEC
ENVIRO-TEC
MODEL NO.
FINISH
WHITE
SDR
SOR
SOR
SDR
SDR
SDR
REMARKS
1 -5
1 -5
1 -5
1 -5
1 -5
1 -5
1 -5
1 -5
350RL
RTU-2
RTU•2
RTU-2
RTU-2
RTU-2
1
UNIT NO.
VAV2 -1
VAV2 -2
AV2 -3
VAV24
VAV2 5
All
7
All
8
'TYPE
DAMPER
DAMPER
&LMPER
DAMPER
DAMPER
CEILING
INLETS12E (1N)
5
12
14
10
16
T -BAR
INLET BRANCH DUCT SIZE ON)
5
12
14
10
16
PERF.
MIN COOL AIRFLOW (CFM)
NOTE 2
NOTE 2
NOTE 2
NOTE 2
NOTE 2
MOD 32X32
MOD 18X18
MAX COOL AIRFLOW RANGE(A
125. 250
988 -1975
1050 -2100
525 - 1140
2562-0
NONE
ELECTRIC HEATER (KVlfj
NOTE 3
NOTE 3
NOTE 3
NOTE 3
NOTE 3
WHITE
'STEPS
NOTE 3
NOTE 3
NOTE 3
NOTE 3
NOTE 3
TITUS
TOTAL SP LOSS (IN WG)
0.6
0.6
0.6
0.6
0.6
350RL
350RL
ELECT (FLA/MCA/MOCP)
NOTE 3
NOTE 3
NOTE 3
NOTE 3
NOTE 3
REMARKS
1
ELECT (V/PHrH7a
NOTE 3
NOTE 3
NOTE 3
NOTE 3
NOTE 3
1
REMARK NUMBERS:
1. REFER TO DRAWING FOR NECT SIZES. ALUMINUM AIR DEVICE.
2. FOUR WAY BLOW UNLESS OTHERWISE INDICATED ON DRAWING.
3. PROVIDE FLEXIBLE DUCT CONNECTION SIZED AT NECK SIZE OF A0.
WEIGHT
40
40
40
50
220
MANUFACTURER
TEC
ENVIRO-TEC
ENVIRO-TEC ENVIRO-TEC
MODEL NO.
SDR
SDR
SDR
SDR
SDR
REMARKS
1 -5
1 -5
1 -5
1 -5
1 -5
RTU-3
R1U•3
RTU-3
RTU-3
RTU-3
RTU-3
UNIT NO.
VAV3 -1
VAV3 -2
VAV3 -3
VAV3 -4
VAV3 -5
VAV3 -6
TYPE
DAMPER
DAMPER
DAMPER
DAMPER
DAMPER
DAMPER
INLET SIZE ON)
12
10
10
10
14
14
INLET BRANCH DUCT SIZE (IN)
12
10
10
10
14
14
MIN COOL AIRFLOW (CM
NOTE 2
NOTE 2
NOTE 2
NOTE 2
NOTE 2
NOTE 2
MAX COOL AIRFLOW RANGE(CFM)
750 - 1500
645 -1290
650 -1300
475 -950
1260
1260
ELECTRIC HEATER (KW)
NOTE 3
NOTE 3
NOTE 3
NOTE 3
NOTE 3
NOTE 3
,STEPS
NOTE 3
NOTE 3
NOTE 3
NOTE 3
NOTE 3
NOTE 3
TOTAL SP LOSS (IN WG)
0.6
0.6
0.6
0.6
0.6
0.6
ELECT (FLA/MCA/MOCP)
NOTE 3
NOTE 3
NOTE 3
NOTE 3
NOTE 3
NOTE 3
ELECT (V/PHFIZ)
NOTE 3
NOTE 3
NOTE 3
NOTE 3
NOTE 3
NOTE 3
WEIGHT
40
50
50
50
200
200
I MANUFACTURER
ENVIRO-TEC
ENVIRO-TEC
ENVIRO-TEC
ENVIRO-TEC ENVIRO•TEC ENVIRO -TEC
MODEL NO.
SDR
SDR
SDR
SOR
SOR
I
REMARKS
1 -5
1 -5
1 -5
1 -5
1 -5
!1!-5::]
REMARKS NUMBERS:
11. UNIT NO: VV4-X INDICATES INLET SIZE "4" WTH CONTROLLING SENSOR IN ROOM "X'. PROVIDE 36 INCHES OF RIGID
STRAIGHT BRANCH DUCT INLET TO BOXAND CONCAL REDUCER AT BOX
;2. AIRFLOW: MAXIMUM AIR FLOW RANGE CFM INDICATES MAXIMUM AIRFLOW AMOUNT FOR BOX BOX IS SIZED BASED ON THIS QUANTITY.
MINIMUM SETTINGS ARE 33% OF MAXIMUM AMOUNTS, UNLESS SPECIFICALLY NOTED OTHERWISE.
13. TOTAL SP LOSS: PRESSURE LOSS INCLUDES ENTIRE ASSEMBLY AT MAXIMUM OPERATING AIRFLOW (DAMPER, CASING, SOUND
ATTENUA70R IF PROVIDED, AND HEATER IF PROVIDED)
MECHANICAL (HVAC) SPECIFICATIONS:
M 1 SCOPE OF WORK:
A MODIFY EXISTING SYSTEMS AND PROVIDE NEW, AS INDICATED.
B MAINTAIN OPERATIONAL EXISTING SYSTEMS THAT ARE NOT PART OF THIS WORK.
C PROVIDE TESTING, ADJUSTING AND BALANCING OF EACH REVISED SYSTEM.
M 2 PROVIDE ALL NECESSARY FEES AND PERMITS. REVIEW OPERATION OF EACH SYSTEM WITH
OWNERS REPRESENTATIVE PROVIDE ONE YEAR WARRANTY ON ENTIRE SYSTEM. PROVIDE
RECORD DRAWING (CONTRACTOR FURNISHED REPRODUCIBLE) SUBMITTALS: SUBMIT
PRODUCT DATA FOR EACH NEW MECHANICAL DEVICE AND TEST AND BALANCE REPORT.
M 3 WORK IN EXISTING BUILDINGS:
A DO NOT USE POWDER DRIVEN FASTENERS OF ANY TYPE.
B SALVAGE: RETURN ALL EXISTING NON- REUSED DEVICES TO THE OWNER AS SALVAGE.
REMOVE THESE DEVICES AS TRASH, IF SPECIFICALLY AND INDIVIDUALLY ADVISED BY
OWNER. AS PART OF BASIC WORK.
C CONTINUITY: MAINTAIN HVAC SERVICE TO OTHER AREAS REMAINING IN OPERATION
DURING CONSTRUCTION. ADVISE THE OWNER OF ANY INTENDED INTERRUPTION IN
SERVICE AT LEAST 24 HOURS BEFORE INTERRUPTION.
D EXISTING ITEMS: EXISTING ITEMS WITHOUT WORK ARE SHOWN FOR CLARITY ONLY.
NOTE THAT ADDITIONAL EXISTING ITEMS WITHOUT WORK MAY ALSO BE PRESENT.
M 4 ACCESS DOORS: PROVIDE 18 INCH X 18 INCH (MINIMUM) PAINTED, ALUMINUM ACCESS
DOOR (WITH FULL HINGE AND KEY) FOR ACCESS TO VALVES, EQUIPMENT, AND
ACCESSORIES IN PLASTER, DRYWALL, OR INACCESSIBLE CEILINGS OR IN WALLS. PROVIDE
INSULATED ACCESS DOORS (DO NOT SUBSTITUTE PANELS) IN DUCTWORK FOR ACCESS TO
DAMPERS AND OTHER OPERATING DEVICES (INCLUDING UPSTREAM OF ELECTRIC
RESISTANCE DUCT HEATERS AND AT DUCT MOUNTED SMOKE DETECTORS). GROUP
DEVICES AT ON LOCATION, AS AVAILABLE.
M 5 PAINTING: IN ADDITION TO SPECIFIED PAINTING, PROVIDE EACH OUTDOOR REM WITH TWO\
COATS OF WEATHERPROOF PAINT (SUITABLE FOR MATERIAL BEING PAINTED) WITH FINAL
COLOR TO BE SELECTED BY ARCHITECT DURING SUBMITTALS (DO NOT PAINT CONDENSER
COILS
M 6 INSULATION:
A DUCTWRAP INSULATION: SUPPLY AIR, OUTSIDE AIR, AND MIXED AIR DUCTS: 2 INCH
THICK FOIL FACED OWENS CORNING FIBERGLASS TYPE 150 (OR AS APPROVED), R =6
(MINIMUM) INSTALLED.
B INSTALLATION: PROVIDE INSULATION AT LOCATIONS WHERE INSULATION IS INTERRUPTED
(SUCH AS AT FLEXIBLE CONNECTIONS), TO PREVENT CONDENSATION.
C CONDENSATE PIPING: 1" THICK ARMAFLEX INSULATION. COAT OUTDOOR INSULATION
FOR SUNLIGHT PROTECTION.
M 7 ROOFTOP AIR HANDLING UNIT (RTU 1, 2, AND 3):
A PACKAGED ROOFTOP AIR HANDLING UNIT, VERTICAL DISCHARGE AIR MOVEMENT, UL
LISTED, COPPER COIL WITH ALUMINUM FINS, DIRECT DRIVE FORWARD CURVED
VARIABLE SPEED MOTOR AND CONTROLS PACKAGE, R -22, CHECK VALVES, LOW
AMBIENT COOLING SYSTEM INTEGRAL WITH CONDENSING UNIT (THERMAL EXPANSION
VALVE, AND EVAPORATOR DEFROST CONTROL, AIR FILTER, FACTORY INSTALLED
INTERNAL ELECTRIC HEATER WITH PACKAGED CONTROLS (SUITABLE FOR
SIMULTANEOUS HEAT / COOL OPERATION). SINGLE POINT ELECTRICAL CONNECTION,
LOW VOLTAGE (24 VAC) TRANSFORMER. ACCEPTABLE MANUFACTURERS: TRANE AND
CARRIER.
B EXHAUST FANS: ROOF MOUNTED EXHAUST FAN: GALVANIZED STEEL, DIRECT
DRIVE (WITH MOTOR SPEED CONTROLLER FOR BALANCING - COORDINATE WIRING WITH
ELECTRICAL WORK), ACCESS DOOR, PLUG -IN MOTOR ASSEMBLY, NEOPRENE ISOLATION
SUPPORTS, BACKDRAFT DAMPER, ROOF CURB. ACCEPTABLE MANUFACTURERS:
GREENHECK, COOK, AND PENN.
M -8 AIR DISTRIBUTION:
A DUCTWORK:
1 RTU DUCTWORK (SUPPLY AIR, RETURN AIR, MIXED AIR. OUTSIDE AIR): GALVANIZED
STEEL. SMACNA 2 INCH PRESSURE CLASS, SMACNA A SEAL CLASS
2 EF DUCTWORK: GALVANIZED STEEL, SMACNA 1/2 INCH PRESSURE CLASS,
SMACNA A SEAL CLASS.
3 TEST (BY FEEL OR TEMPERATURE CHANGE) EACH DUCTWORK SYSTEM FOR LEAKS
BEFORE INSULATING. RESEAL. AS REQUIRED.
4 DUCT DIMENSIONS INDICATE AIR FLOW SIZES.
5 AT CONTRACTORS OPTION, EQUAL AREA DUCTWORK HAVING A MAXIMUM 4 TO 1
ASPECT RATIO MAY BE SUBSTITUTED FOR DUCT DIMENSIONS SHOWN.
6 FLEXIBLE DUCTWORK (USED TO CONNECT TO SUPPLY AIR OUTLETS: THERMAFLEX
TYPE M -KE (OR AS APPROVED).
7 BRANCH DUCT CONNECTIONS (POSITIVE AND NEGATIVE PRESSURE): ON
RECTANGULAR DUCTS. PROVIDE VOLUME EXTRACTORS OR 45 DEGREE ENTRIES; ON
CIRCULAR DUCTS, PROVIDE CONICAL TAPS (WITH DAMPERS). PROVIDE THESE
CONNECTIONS ON EACH BRANCH DUCT CONNECTION FOR EACH SYSTEM; DO NOT
SUBSTITUTE CONNECTIONS.
8 ELBOWS (POSITIVE AND NEGATIVE PRESSURE): PROVIDE LONG RADIUS (FULL)
ELBOWS OR TURNING VANES FOR ALL ELBOWS; DO NOT SUBSTITUTE SQUARE
ELBOWS.
9 INSTALL DUCTWORK AND ACCESSORIES IN ACCORDANCE WITH SMACNA HVAC
DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE (1985 EDITION).
B AIR OUTLETS AND AIR INLETS:
1 STYLE, AS NOTED. PROVIDE OFF -WHITE FINISH TO MATCH EXISTING. ACCEPTABLE
MANUFACTURERS: METALAIRE, TITUS. PRICE
M 9 CONTROLS
A RTU 1, 2 AND 3:
1 THERMOSTAT: DIGITAL, PROGRAMMABLE, WALL- MOUNTED WITH AUTOMATIC HEATING
COOLING CHANGEOVER CONTROLS.
2 EF -1: EXHAUST FAN OPERATES WITH RTU -3.
3 EF -2: EXHAUST FAN OPERATES WITH RTU -1.
4 EF -3: EXHAUST FAN OPERATES WITH RTU -1.
5 EF -4: EXHAUST FAN OPERATES WITH RTU -2.
6 EF-5: EXHAUST FAN OPERATES WITH RTU -2.
7 EF -6: EXHAUST FAN OPERATES WITH RTU -1.
M 10 TESTING, ADJUSTING AND BALANCING:
A GENERAL: PERFORM TESTING, ADJUSTING, AND BALANCING OF EACH NEW AND
EXISTING:
1 RTU
2 EF
3 ELECTRIC HEATER
4 MANUAL BALANCING DAMPER
5 AIR OUTLET
6 AIR INLET
B PERFORM TESTING USING AABC TOTAL SYSTEM BALANCE PROCEDURES. USE DATA
FOUND ON AABC FORMS IN THE SUBMITTALS.
MECHANICAL LEGEND
SYMBOL DESCRIPTION
�- D CONDENSATE DRAIN PIPING
® POSRIVE PRESSURE DUCTWORK (SUPPLY AIR, RELIEF AIR)
NEGATIVE PRESSURE DUCTWORK (RETURN AIR, EXHAUST AIR,
OUTSIDE AIR INTAKE)
NEW DUCT OR DEVICES
FLEXIBLE DUCTWORK
-► �-� AIR FLOW: POSITIVE PRESSURE; NEGATIVE PRESSURE
BRANCH DUCT CONNECTION: WITH 45 DEGREE ENTRY
CEIUNG
BRANCH DUCT CONNECTION: WITH CONICAL CONNECTION AND DAMPER
OT THERMOSTAT
O HUMIDISTAT
AIR OUTLET TYPE (AO -1); CONNECTION SIZE; AND MAXIMUM CFM
INDICATED. BRANCH DUCT SIZE MATCHES CONNECTION SIZE,
UNLESS NOTED OTHERWISE THROW: 4 WAY, UNLESS NOTED
OTHERWISE.
AIR INLET TYPE (AI -1); CONNECTION SIZE; AND MAXIMUM CFM
INDICATED. BRANCH DUCT SIZE MATCHES CONNECTION SIZE,
UNLESS NOTED OTHERWISE.
- U-►- 3/4" DOOR UNDERCUT- COORDINATE WITH ARCHITECTURAL WORK.
AIR HANDLING UNIT TYPE
AO AIR OUTLET REGISTER / FLEXIBLE DUCTWORK SIZE / CFM
L/ CFM
/A'\ AIR INLET REGISTER / CFM
1 300 CFM
eEXHAUST FAN TYPE
1
ODRAWING NOTE: REFER TO NOTES ON EACH DRAWING
ABBREVIATION DESCRIPTION ABBREVIATION DESCRIPTION
BTU BRITISH THERMAL UNIT
LAT LEAVING AIR TEMPERATURE
CFM CUBIC FEET PER MINUTE
LLB LEAVING DRY BULB
DB DRY BULB
LWB LEAVING WET BULB
ESP EXTERNAL STATIC PRESSURE
MBH THOUSAND BTU PER HOUR
TYP TYPICAL
RA RETURN AIR
WB WET BULB
RH RELATIVE HUMIDITY
SP STATIC PRESSURE
SA SUPPLY AIR
AIR DEVICE
SYMBOL
SCHEDULE (AO AND
AO AO
1 2
AI)
AO
3
AO
4
ROOF
MOUNTING
CEILING
IN -LINE
CEILING
CEILING
CEIUNG
RTU 1
FRAME
T -BAR
RTU 1
T -BAR
T -SLOT
T -SLOT
1250
FACE
LOUVER
250
LOUVER
LOUVER
LOUVER
0.375
STYLE
MOD 24X24
0.5
MOD 12X12
MOD 48X6
MOD 60X6
9.1
DAMPER
OBD
7.6
OBD
OBD
OBD
1140
FINISH
WHITE
1550
WHITE
WHITE
WHITE
-
MANUFACTURER
TITUS
-
TITUS
TITUS
TITUS
1 20
MODEL NO.
TMS -AA
1 20
TMS -AA
ML -39 -NT
ML -39 -NT
-
REMARKS
1,2.3
-
1,2,3
1.3
1.3
120 1 60
SYMBOL
All
1
All
2
AI
3
Al
4
23
MOUNTING
CEIUNG
23
CEILING
CEILING
CEILING
GREENHECK
FRAME
T -BAR
GREENHECK
T -BAR
T -BAR
T -BAR
G -085 -D
FACE
PERF.
G -065 -G
PERF.
PERF.
PERF.
1
STYLE
MOD 12X6
1
MOD 14X6
MOD 10X6
MOD 24X24
DAMPER
NONE
NONE
NONE
NONE
FINISH
WHITE
WHITE
WHITE
WHITE
MANUFACTURER
TITUS
TITUS
TITUS
TAUS
MODEL NO.
350RL
350RL
350RL
350RL
REMARKS
1
1
1
1
SYMBOL
Al
5
AI
6
All
7
All
8
All
9
MOUNTING
CEIUNG
CEILING
CEILING
CEILING
CEILING
FRAME
T- BAR
T -BAR
T -BAR
T -BAR
T -BAR
FACE
PERF.
PERF.
PERF.
PERF.
PERF.
STYLE
MOD 28X28
MOD 32X32
MOD 18X18
MOD 14X14
MOD 16X16
DAMPER
NONE
NONE
NONE
NONE
NONE
FINISH
WHITE
WHITE
WHITE
WHITE
WHITE
MANUFACTURER
TITUS
TITUS
TITUS
TITUS
TITUS
MODEL N0.
350RL
350RL
350RL
350RL
350RL
REMARKS
1
1
1
1
1
REMARK NUMBERS:
1. REFER TO DRAWING FOR NECT SIZES. ALUMINUM AIR DEVICE.
2. FOUR WAY BLOW UNLESS OTHERWISE INDICATED ON DRAWING.
3. PROVIDE FLEXIBLE DUCT CONNECTION SIZED AT NECK SIZE OF A0.
MECHANICAL - LEGEND, NOTES, SCHEDULES
SCALE: NONE
EXHAUST FAN SCHEDULE
EF EF EF EF EF EF
UNIT NO. 1 2 3 4 5 6
LOCATION
ROOF
ROOF
ROOF
ROOF
ROOF
IN -LINE
SERVICE
RTU 3
RTU 1
RTU 1
RTU 2
RTU 2
RTU 1
TOTAL AIR CFM
1500
300
1250
900
150
250
ESP IN WG
0.25
0.5
0.375
0.25
0.25
0.5
SOUND - MAX (SONES)
7.4
7.6
9.1
7.1
3.2
7.6
RPM
860
1550
1140
1140
1300
1550
BHP - MAX
-
-
-
-
-
-
MOTOR HP OR WATTS
1/8
1 20
1 20
1 6
1 60
1 20
ELECT FLA MCA MOCP
-
-
-
-
-
-
ELECT V PH HZ
1120/11/60
1120/1/60
120 1 60
1120/1/60
120/1760
1120/11/60
WEIGHT (LBS)
72
23
51
40
23
23
MANUFACTURER
GREENHECK
GREENHECK
GREENHECK
f GREENHECK
GREENHECK
GREENHECK
MODEL NO.
G -160 -C
G -085 -D
G -141 -B
G -101 -B
G -065 -G
G -085 -D
REMARKS
1
1
1
1
1
1
REMARK NUMBERS:
1. ROOF MOUNTED FAN WITH CURB, DIRECT DRIVE, BACKDRAFT DAMPER, PLUG -IN MOTOR SERVES AS DISCONNECT, ADJ ABLE MOTOR SPEED 3
CONTROLLER (FOR T&B). FAN OPERATES WITH RTU.
Notes:
Revisions:
8/15/05 PLAN REVISION
8/22/05 PLAN REVISION
9/23/05 PLAN REVISION
?: pia,, •,
1
consultants: I
ARCHITECTURAL ENGINEERING INCOR
3442 EAST LAKE RW, PALM HARBOR.
CONSULTING ENGINEERS (727)
CERTIFICATE OF AUTHORIZATION:
W. RONALD MCILVEEN FL
L 34485
14 -1472
FL 3888
30270
-,
10
E L E M E N T S
� ` 1
1
ARCHITECTS - INTERIOR DESIGNERS
T m p a Off i s
The Edgewater Buildin
600 South Magnolia Avenu
Suite 150
Tampa, Florida 33606
Phone (813) 251 -0565
Fax (813) 251 -0567
Micmi_.,_Offic
4240 Southv/est 3rd -Sire t
Miami, Florida 331-:4 ------
Phone (305) 441 =7517_ _
Fax - /305' 774 =1123 -
Nicholas Puglisi Architect License ,# 12460
ELEMENTS State - License #AA0_00 34i
WA CH 0___ V A
WEST GABLES BRANCH
5880 61�I7 t;0At7
MIAMI, I'L RIDA
Drawing No. /Date 512105
M 0.1
04 -028/ 05193
Drawing Title /Scale /Drawn by W
MECHANICAL SCHEDULE I'
AND NOTES
5C&l: NONE