05-1212-002ELECTRICAL NOTES:
1. ALL POOL ELECTRICAL WORK SHALL BE ACCOMPLISHED IN COMPLIANCE
WITH FLORIDA BUILDING CODE.
2. ALL ELECTRICAL GROUNDING AND BONDING SHALL CONFORM
WITH THE FLORIDA BUILDING CODE.
3. NO OVERHEAD WIRING SHALL BE LOCATED WITHIN 10' -0"
OF POOL'S WATER EDGE.
4. SHOULD THE ELECTRICAL RISER DIAGRAM NOT ACCURATELY
DEPICT REQUIRED WORK, A REVISED DRAWING SHALL BE SUB-
MITTED AND APPROVED SHAOWING EXPECTED AS BUILT CONFIGURATION
WITH ADDITONAL SERVICE AND LOAD CALCULATIONS, IF NECESSARY.
5. ALL ELECTRICAL EQUIPMENT NOT SUITABLE FOR EXPOSURE TO THE
ELEMENTS SHALL BE ENCLOSED IN A WEATHERPROOF CONTAINER. ALL PUMPS,
HEATERS, PIPING AND RELATED POOL EQUIPMENT SHOWN ON THESE PLANS ARE
SATISFACTORY FOR EXPOSURE TO THE ELEMENTS.
NOTE: PROVIDE #4 BARE COPPER BOND WIRE FROM LIGHT TO POOL STEEL. WHERE
A CONCRETE DECK IS NOT PROVIDED, PROVIDE A #4 BARE COPPER BOND
WIRE FROM THE POOL STEEL TO THE EQUIPMENT TO THE PANEL.
WHERE A CONCRETE SLAB IS PROVIDED, THE BOND WIRE SHALL BE CONNECTED
FROM THE POOL STEEL TO THE REINFORCING MESH CONTINUOUS TO THE #5 REINFORC-
ING BAR IN THE PERIMETER SLAB FOOTING. A BOND WIRE SHALL THEN BE CONNECTED
FROM THE PERIMETER STEEL TO THE EQUIPMENT TO THE ELECTRICAL PANEL.
N PANEL "A"
BRK
WIRE
DESCRIPTION
WATTS
70
30
EXIST. POOL PANEL
5,000
WIRE
CIR
BRK
CIR
--
--
SPACE
--
--
--
SPACE 7
--
200 AMP WIRE: 3 - f 3/0 THWN. CU.
SEE LOAD SUMMARY IN 1 -1/ CONDUIT.
256 S. F. 0 3 VA = 768 VA
ONE 20 A, GFI /WP
0 1500 VA EA. (GFI) = 1500 VA
TOTAL = 2268 VA
2268 VA /240 V = 9.45 AMPS
40 A. 120/240 V. 1 PHASE 3 W. SERVICE RATING
NEW
SUB -PANEL
"B"
DISCONNECT SWITCH
WATTS
WATTS
DESCRIPTION
WIRE
WIRE
CIR
BRK
CIR
CIR
BRK
WIRE
DESCRIPTION
*
WATTS
2268
MAIN DISC. SWITCH
20
8
2
40
1 C
2
20
12
GFI CIRCUIT
GENERAL LIGHTING
4500
Q)
rq
3
4
L_
3 C
4
15
14
GENERAL LIGHTING
►�
500
--
SPACE
6
--
--
5
6
--
--
SPACE
--
--
SPACE
1 15
--
1 GENERAL LIGHTING
--
7
8 1
--
--
1. SPACE
--
MTG.: SURFACE MOUNTED
MAIN: 40 AMP
VOLTS 120/240 V.1-, 3W
BUS: 40 AMP
LOAD: SEE LOAD SUMMARY
WIRE: 3 - 8 THWN. CU.
IN 374' CONDUIT.
256 S. F. 0 3 VA = 768 VA
ONE 20 A, GFI /WP
0 1500 VA EA. (GFI) = 1500 VA
TOTAL = 2268 VA
2268 VA /240 V = 9.45 AMPS
40 A. 120/240 V. 1 PHASE 3 W. SERVICE RATING
NEW 200 AMP
METER/ MAIN 1
SNATCH COMBO
200 AMP O.C.P
EXIST GF
CONDUC'1 UK IV KCMANV
NEW 40 AMP SUB -PANEL "B" 0
CABANA W/ MAIN DISC. SVMTCH
3—f8 THWN CU. IN 3/4" CONDUIT
EXISTING 70 AMP SUB PANEL
ELEC. PANEL JANDY AQUALINK
TO REMAIN SYSTEM (PDA)
ELECTRICAL RISER DIAGRAM �
SCALE: N.T.S.
ELECTRICAL NOTES
1. ALL WORK SHALL COMPLY WITH N.E.C., AND ALL OTHER APPLICABLE CODES AND /OR AUTHORITIES
HAVING JURISDICTION OVER THIS PROJECT.
2. THE ELECTRICAL CONTRACTOR SHALL SUPPLY AND INSTALL ALL WIRES, CONDUITS, CONNECTORS,
ETC. TO ACHIEVE A COMPLETE ELECTRICAL SYSTEM. WHERE ELECTRICAL EQUIPMENT, OUTLET, OR
OTHER FEATURES ARE REQUIRED BY CODE, BUT NOT SHOWN ON THE PLANS, THE ELECTRICAL
CONTRACTOR SHALL FURNISH AND INSTALL SAME, AS REQUIRED BY CODE.
3. ALL ELECTRICAL WIRES USED SHALL BE RONEX TYPE.
4. THE ELECTRICAL CONTRACTOR SHALL OBTAIN AND PAY FOR ALL REQUIRED PERMITS, APPROVALS,
AND INSPECTIONS.
5. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING AND PROCURING TEMPORARY
POWER DURING CONSTRUCTION ACCESSIBLE TO ALL TRADES.
6. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE TO CLEARLY LABEL THE CIRCUITS AT THE PANEL
WITH THEIR CORRESPONDING AREA CONTROLLED BY THAT CIRCUIT.
7. THESE PLANS CONSTITUTE A COMPLETE SET OF PLANS, THEREFORE NO SECTION STANDS ON ITS
OWN. THE ELECTRICAL CONTRACTOR SHALL COORDINATE THIS PLAN WITH ALL OTHER PLANS IN SET,
AS WELL HIS ACTUAL WORK WITH ALL OTHER TRADES, TO MINIMIZE CONFLICTS AT THE JOB SITE.
T.O.S. +10.0' NGVD POOL EQUIP.
EXISTING ELEC. METER TO BE
REMOVED AND RELPACED W/ NEW
AMP 200 METER DISC/ COMBO.
REMOVE EXISTING OVERHEAD
LINES AND PROVIDE NEW UNDER
GROUND ELEC. SERVICE AS REQ'D. _
EXISTING
A C
;a1
PAN
ELECTRICAL LEGEND
NEW
SUB
-PANEL "X" (AQUALINK)
DISCONNECT SWITCH
WATTS
DESCRIPTION
O ELECTRIC PANEL
WIRE
BRK
CIR
CIR
BRK
WIRE
DESCRIPTION
CEILING MOUNTED FIXTURE
WATTS
*
GENERAL UGHTING
INTERRUPTER
2 12
20
1
2
60
6
POOL HEATER
RECESSED CEILING FIXTURE
10000
*
GENERAL LIGHTING
FAN W/ LIGHT
Q)
rq
3
4
L_
-Q
*
GENERAL LIGHTING
►�
0
5
6
GENERAL LIGHTING
_
*
GENERAL LIGHTING
44J
7
8
1 15
1 14
1 GENERAL LIGHTING
-0
MTG.: SURFACE MOUNTED
MAIN: 70 AMP
VOLTS 120/240 V.1-, 3W
BUS: 70 AMP WIRE 3 - f 8 THWN.
LOAD: SEE LOAD SUMMARY IN 3/e CONDUIT.
CU.
NEW 200 AMP
METER/ MAIN 1
SNATCH COMBO
200 AMP O.C.P
EXIST GF
CONDUC'1 UK IV KCMANV
NEW 40 AMP SUB -PANEL "B" 0
CABANA W/ MAIN DISC. SVMTCH
3—f8 THWN CU. IN 3/4" CONDUIT
EXISTING 70 AMP SUB PANEL
ELEC. PANEL JANDY AQUALINK
TO REMAIN SYSTEM (PDA)
ELECTRICAL RISER DIAGRAM �
SCALE: N.T.S.
ELECTRICAL NOTES
1. ALL WORK SHALL COMPLY WITH N.E.C., AND ALL OTHER APPLICABLE CODES AND /OR AUTHORITIES
HAVING JURISDICTION OVER THIS PROJECT.
2. THE ELECTRICAL CONTRACTOR SHALL SUPPLY AND INSTALL ALL WIRES, CONDUITS, CONNECTORS,
ETC. TO ACHIEVE A COMPLETE ELECTRICAL SYSTEM. WHERE ELECTRICAL EQUIPMENT, OUTLET, OR
OTHER FEATURES ARE REQUIRED BY CODE, BUT NOT SHOWN ON THE PLANS, THE ELECTRICAL
CONTRACTOR SHALL FURNISH AND INSTALL SAME, AS REQUIRED BY CODE.
3. ALL ELECTRICAL WIRES USED SHALL BE RONEX TYPE.
4. THE ELECTRICAL CONTRACTOR SHALL OBTAIN AND PAY FOR ALL REQUIRED PERMITS, APPROVALS,
AND INSPECTIONS.
5. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING AND PROCURING TEMPORARY
POWER DURING CONSTRUCTION ACCESSIBLE TO ALL TRADES.
6. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE TO CLEARLY LABEL THE CIRCUITS AT THE PANEL
WITH THEIR CORRESPONDING AREA CONTROLLED BY THAT CIRCUIT.
7. THESE PLANS CONSTITUTE A COMPLETE SET OF PLANS, THEREFORE NO SECTION STANDS ON ITS
OWN. THE ELECTRICAL CONTRACTOR SHALL COORDINATE THIS PLAN WITH ALL OTHER PLANS IN SET,
AS WELL HIS ACTUAL WORK WITH ALL OTHER TRADES, TO MINIMIZE CONFLICTS AT THE JOB SITE.
T.O.S. +10.0' NGVD POOL EQUIP.
EXISTING ELEC. METER TO BE
REMOVED AND RELPACED W/ NEW
AMP 200 METER DISC/ COMBO.
REMOVE EXISTING OVERHEAD
LINES AND PROVIDE NEW UNDER
GROUND ELEC. SERVICE AS REQ'D. _
EXISTING
A C
;a1
PAN
ELECTRICAL LEGEND
,
L!
SWITCH
DISCONNECT SWITCH
;3
THREE -WAY SWITCH
O ELECTRIC PANEL
;D
SWITCH W/ DIMMER
[E]3 ELECTRIC METER
A)
DUPLEX RECEPTACLE
WP WEATHER PROOF
0
CEILING MOUNTED FIXTURE
GFI GROUND FAULTED
INTERRUPTER
4
WALL MOUNTED FIXTURE
INK
®
RECESSED CEILING FIXTURE
FLOOD LIGHT
EXHAUST FAN
FAN W/ LIGHT
NOTE:
GENERAL CONTRACTOR TO COORDINATE EQUIPMENT MOUNTING HEIGHT WITH F.F.
ELEV. AND FLOOD ZONE REQUIREMENTS.
PANEL "A"
Al
W���
L
A -36
/I
TO SUB PANEL "X"
JANDY AQUALINK
A SYSTEM (PDA)
A 6
L-
TO SUB PANEL "X"
JANDY AQUALINK
ISYSTEM (PDA)
A -40 1
I
LIGHT
1
PROPOSED POOL
■
GFl - - --� - -
A -36 - - -
GFI
A -34
/ — STORAGE ROOM ,0
A -36 0 A -36
T.O.S. +10.0' NGVD
SUB- 3
PANEL "B"
- -'-a'
A -38 A -38
ROPOSE I
4CUZZI
' A 8 t A -388 --- -38
I
,I
ELECTRICAI
J)UALL: 1/ 4 =1 -U
imm5g
U.S. Structures, Inc.
Structural Engineers
4444 SOUTHWEST 71st AVE, #103
MIAMI, FLORIDA 33155
305.665.4555 FAX 305.665.5522
usstructuresinc.com
CA 8439
,
L!
09 -15 -05
EL "X
record set
LINK
08 -16 -11
A-
A)
-
D
—
L X
INK
)
3
W
I
,I
ELECTRICAI
J)UALL: 1/ 4 =1 -U
imm5g
U.S. Structures, Inc.
Structural Engineers
4444 SOUTHWEST 71st AVE, #103
MIAMI, FLORIDA 33155
305.665.4555 FAX 305.665.5522
usstructuresinc.com
CA 8439
R E
V I S 1 0 N S:
09 -15 -05
09 -26 -05
record set
08 -16 -11
4--)
L_
O
W
Q)
rq
L_
-Q
z
�,
►�
0
W
U
_
44J
0
LO
-0
U—)
00
—
O
(n
LL
00
O
O
4-)
0
0
Q
0
L(-)*
Q—J
0-)
4-J
0
CO
:D
LC)
00
O
0
Lo
Cn
rr)
R E
V I S 1 0 N S:
09 -15 -05
09 -26 -05
record set
08 -16 -11
DRAWN
JAT
CHECKED
JAT
DATE
August 1, 2005
SCALE
As Indicated
JOB NO.
SDP 05.035.2
SHEET
E -1
OF 8 SHEETS