Loading...
05-1212-002ELECTRICAL NOTES: 1. ALL POOL ELECTRICAL WORK SHALL BE ACCOMPLISHED IN COMPLIANCE WITH FLORIDA BUILDING CODE. 2. ALL ELECTRICAL GROUNDING AND BONDING SHALL CONFORM WITH THE FLORIDA BUILDING CODE. 3. NO OVERHEAD WIRING SHALL BE LOCATED WITHIN 10' -0" OF POOL'S WATER EDGE. 4. SHOULD THE ELECTRICAL RISER DIAGRAM NOT ACCURATELY DEPICT REQUIRED WORK, A REVISED DRAWING SHALL BE SUB- MITTED AND APPROVED SHAOWING EXPECTED AS BUILT CONFIGURATION WITH ADDITONAL SERVICE AND LOAD CALCULATIONS, IF NECESSARY. 5. ALL ELECTRICAL EQUIPMENT NOT SUITABLE FOR EXPOSURE TO THE ELEMENTS SHALL BE ENCLOSED IN A WEATHERPROOF CONTAINER. ALL PUMPS, HEATERS, PIPING AND RELATED POOL EQUIPMENT SHOWN ON THESE PLANS ARE SATISFACTORY FOR EXPOSURE TO THE ELEMENTS. NOTE: PROVIDE #4 BARE COPPER BOND WIRE FROM LIGHT TO POOL STEEL. WHERE A CONCRETE DECK IS NOT PROVIDED, PROVIDE A #4 BARE COPPER BOND WIRE FROM THE POOL STEEL TO THE EQUIPMENT TO THE PANEL. WHERE A CONCRETE SLAB IS PROVIDED, THE BOND WIRE SHALL BE CONNECTED FROM THE POOL STEEL TO THE REINFORCING MESH CONTINUOUS TO THE #5 REINFORC- ING BAR IN THE PERIMETER SLAB FOOTING. A BOND WIRE SHALL THEN BE CONNECTED FROM THE PERIMETER STEEL TO THE EQUIPMENT TO THE ELECTRICAL PANEL. N PANEL "A" BRK WIRE DESCRIPTION WATTS 70 30 EXIST. POOL PANEL 5,000 WIRE CIR BRK CIR -- -- SPACE -- -- -- SPACE 7 -- 200 AMP WIRE: 3 - f 3/0 THWN. CU. SEE LOAD SUMMARY IN 1 -1/ CONDUIT. 256 S. F. 0 3 VA = 768 VA ONE 20 A, GFI /WP 0 1500 VA EA. (GFI) = 1500 VA TOTAL = 2268 VA 2268 VA /240 V = 9.45 AMPS 40 A. 120/240 V. 1 PHASE 3 W. SERVICE RATING NEW SUB -PANEL "B" DISCONNECT SWITCH WATTS WATTS DESCRIPTION WIRE WIRE CIR BRK CIR CIR BRK WIRE DESCRIPTION * WATTS 2268 MAIN DISC. SWITCH 20 8 2 40 1 C 2 20 12 GFI CIRCUIT GENERAL LIGHTING 4500 Q) rq 3 4 L_ 3 C 4 15 14 GENERAL LIGHTING ►� 500 -- SPACE 6 -- -- 5 6 -- -- SPACE -- -- SPACE 1 15 -- 1 GENERAL LIGHTING -- 7 8 1 -- -- 1. SPACE -- MTG.: SURFACE MOUNTED MAIN: 40 AMP VOLTS 120/240 V.1-, 3W BUS: 40 AMP LOAD: SEE LOAD SUMMARY WIRE: 3 - 8 THWN. CU. IN 374' CONDUIT. 256 S. F. 0 3 VA = 768 VA ONE 20 A, GFI /WP 0 1500 VA EA. (GFI) = 1500 VA TOTAL = 2268 VA 2268 VA /240 V = 9.45 AMPS 40 A. 120/240 V. 1 PHASE 3 W. SERVICE RATING NEW 200 AMP METER/ MAIN 1 SNATCH COMBO 200 AMP O.C.P EXIST GF CONDUC'1 UK IV KCMANV NEW 40 AMP SUB -PANEL "B" 0 CABANA W/ MAIN DISC. SVMTCH 3—f8 THWN CU. IN 3/4" CONDUIT EXISTING 70 AMP SUB PANEL ELEC. PANEL JANDY AQUALINK TO REMAIN SYSTEM (PDA) ELECTRICAL RISER DIAGRAM � SCALE: N.T.S. ELECTRICAL NOTES 1. ALL WORK SHALL COMPLY WITH N.E.C., AND ALL OTHER APPLICABLE CODES AND /OR AUTHORITIES HAVING JURISDICTION OVER THIS PROJECT. 2. THE ELECTRICAL CONTRACTOR SHALL SUPPLY AND INSTALL ALL WIRES, CONDUITS, CONNECTORS, ETC. TO ACHIEVE A COMPLETE ELECTRICAL SYSTEM. WHERE ELECTRICAL EQUIPMENT, OUTLET, OR OTHER FEATURES ARE REQUIRED BY CODE, BUT NOT SHOWN ON THE PLANS, THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL SAME, AS REQUIRED BY CODE. 3. ALL ELECTRICAL WIRES USED SHALL BE RONEX TYPE. 4. THE ELECTRICAL CONTRACTOR SHALL OBTAIN AND PAY FOR ALL REQUIRED PERMITS, APPROVALS, AND INSPECTIONS. 5. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING AND PROCURING TEMPORARY POWER DURING CONSTRUCTION ACCESSIBLE TO ALL TRADES. 6. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE TO CLEARLY LABEL THE CIRCUITS AT THE PANEL WITH THEIR CORRESPONDING AREA CONTROLLED BY THAT CIRCUIT. 7. THESE PLANS CONSTITUTE A COMPLETE SET OF PLANS, THEREFORE NO SECTION STANDS ON ITS OWN. THE ELECTRICAL CONTRACTOR SHALL COORDINATE THIS PLAN WITH ALL OTHER PLANS IN SET, AS WELL HIS ACTUAL WORK WITH ALL OTHER TRADES, TO MINIMIZE CONFLICTS AT THE JOB SITE. T.O.S. +10.0' NGVD POOL EQUIP. EXISTING ELEC. METER TO BE REMOVED AND RELPACED W/ NEW AMP 200 METER DISC/ COMBO. REMOVE EXISTING OVERHEAD LINES AND PROVIDE NEW UNDER GROUND ELEC. SERVICE AS REQ'D. _ EXISTING A C ;a1 PAN ELECTRICAL LEGEND NEW SUB -PANEL "X" (AQUALINK) DISCONNECT SWITCH WATTS DESCRIPTION O ELECTRIC PANEL WIRE BRK CIR CIR BRK WIRE DESCRIPTION CEILING MOUNTED FIXTURE WATTS * GENERAL UGHTING INTERRUPTER 2 12 20 1 2 60 6 POOL HEATER RECESSED CEILING FIXTURE 10000 * GENERAL LIGHTING FAN W/ LIGHT Q) rq 3 4 L_ -Q * GENERAL LIGHTING ►� 0 5 6 GENERAL LIGHTING _ * GENERAL LIGHTING 44J 7 8 1 15 1 14 1 GENERAL LIGHTING -0 MTG.: SURFACE MOUNTED MAIN: 70 AMP VOLTS 120/240 V.1-, 3W BUS: 70 AMP WIRE 3 - f 8 THWN. LOAD: SEE LOAD SUMMARY IN 3/e CONDUIT. CU. NEW 200 AMP METER/ MAIN 1 SNATCH COMBO 200 AMP O.C.P EXIST GF CONDUC'1 UK IV KCMANV NEW 40 AMP SUB -PANEL "B" 0 CABANA W/ MAIN DISC. SVMTCH 3—f8 THWN CU. IN 3/4" CONDUIT EXISTING 70 AMP SUB PANEL ELEC. PANEL JANDY AQUALINK TO REMAIN SYSTEM (PDA) ELECTRICAL RISER DIAGRAM � SCALE: N.T.S. ELECTRICAL NOTES 1. ALL WORK SHALL COMPLY WITH N.E.C., AND ALL OTHER APPLICABLE CODES AND /OR AUTHORITIES HAVING JURISDICTION OVER THIS PROJECT. 2. THE ELECTRICAL CONTRACTOR SHALL SUPPLY AND INSTALL ALL WIRES, CONDUITS, CONNECTORS, ETC. TO ACHIEVE A COMPLETE ELECTRICAL SYSTEM. WHERE ELECTRICAL EQUIPMENT, OUTLET, OR OTHER FEATURES ARE REQUIRED BY CODE, BUT NOT SHOWN ON THE PLANS, THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL SAME, AS REQUIRED BY CODE. 3. ALL ELECTRICAL WIRES USED SHALL BE RONEX TYPE. 4. THE ELECTRICAL CONTRACTOR SHALL OBTAIN AND PAY FOR ALL REQUIRED PERMITS, APPROVALS, AND INSPECTIONS. 5. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING AND PROCURING TEMPORARY POWER DURING CONSTRUCTION ACCESSIBLE TO ALL TRADES. 6. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE TO CLEARLY LABEL THE CIRCUITS AT THE PANEL WITH THEIR CORRESPONDING AREA CONTROLLED BY THAT CIRCUIT. 7. THESE PLANS CONSTITUTE A COMPLETE SET OF PLANS, THEREFORE NO SECTION STANDS ON ITS OWN. THE ELECTRICAL CONTRACTOR SHALL COORDINATE THIS PLAN WITH ALL OTHER PLANS IN SET, AS WELL HIS ACTUAL WORK WITH ALL OTHER TRADES, TO MINIMIZE CONFLICTS AT THE JOB SITE. T.O.S. +10.0' NGVD POOL EQUIP. EXISTING ELEC. METER TO BE REMOVED AND RELPACED W/ NEW AMP 200 METER DISC/ COMBO. REMOVE EXISTING OVERHEAD LINES AND PROVIDE NEW UNDER GROUND ELEC. SERVICE AS REQ'D. _ EXISTING A C ;a1 PAN ELECTRICAL LEGEND , L! SWITCH DISCONNECT SWITCH ;3 THREE -WAY SWITCH O ELECTRIC PANEL ;D SWITCH W/ DIMMER [E]3 ELECTRIC METER A) DUPLEX RECEPTACLE WP WEATHER PROOF 0 CEILING MOUNTED FIXTURE GFI GROUND FAULTED INTERRUPTER 4 WALL MOUNTED FIXTURE INK ® RECESSED CEILING FIXTURE FLOOD LIGHT EXHAUST FAN FAN W/ LIGHT NOTE: GENERAL CONTRACTOR TO COORDINATE EQUIPMENT MOUNTING HEIGHT WITH F.F. ELEV. AND FLOOD ZONE REQUIREMENTS. PANEL "A" Al W��� L A -36 /I TO SUB PANEL "X" JANDY AQUALINK A SYSTEM (PDA) A 6 L- TO SUB PANEL "X" JANDY AQUALINK ISYSTEM (PDA) A -40 1 I LIGHT 1 PROPOSED POOL ■ GFl - - --� - - A -36 - - - GFI A -34 / — STORAGE ROOM ,0 A -36 0 A -36 T.O.S. +10.0' NGVD SUB- 3 PANEL "B" - -'-a' A -38 A -38 ROPOSE I 4CUZZI ' A 8 t A -388 --- -38 I ,I ELECTRICAI J)UALL: 1/ 4 =1 -U imm5g U.S. Structures, Inc. Structural Engineers 4444 SOUTHWEST 71st AVE, #103 MIAMI, FLORIDA 33155 305.665.4555 FAX 305.665.5522 usstructuresinc.com CA 8439 , L! 09 -15 -05 EL "X record set LINK 08 -16 -11 A- A) - D — L X INK ) 3 W I ,I ELECTRICAI J)UALL: 1/ 4 =1 -U imm5g U.S. Structures, Inc. Structural Engineers 4444 SOUTHWEST 71st AVE, #103 MIAMI, FLORIDA 33155 305.665.4555 FAX 305.665.5522 usstructuresinc.com CA 8439 R E V I S 1 0 N S: 09 -15 -05 09 -26 -05 record set 08 -16 -11 4--) L_ O W Q) rq L_ -Q z �, ►� 0 W U _ 44J 0 LO -0 U—) 00 — O (n LL 00 O O 4-) 0 0 Q 0 L(-)* Q—J 0-) 4-J 0 CO :D LC) 00 O 0 Lo Cn rr) R E V I S 1 0 N S: 09 -15 -05 09 -26 -05 record set 08 -16 -11 DRAWN JAT CHECKED JAT DATE August 1, 2005 SCALE As Indicated JOB NO. SDP 05.035.2 SHEET E -1 OF 8 SHEETS