TURNING V4
FOR SMACNA
STANDARDS.
I.....Ii
TYPICAL 90- DEGREE VANED ELBOW DETAIL.
WOOD JOIST
& DECK.
HANGER WIRE
12 GAUGE (MIN.)
SCREWS FASTENERS.
DUCT
SHEET METAL CHANNEL
SUSPENDED CEILING
(SEE ARCH. DRAWINi
DUCT HANGER DETAIL
N.T.S.
HVAC SYMBOL LEGEND
SYMBOL
DESCRIPTION
®
SUPPLY DUCT
DESIGN MANUFACTURER
RETURN /EXHAUST DUCT
IIIIIIII
FLEXIBLE DUCT
ACCESORIES
ELBOW W/ TURNING VALVES
REF. S &R
REFRIGERANT SUCTION & LIQUID LINES
CEILING DIFFUSER
CEILING EXHAUST FAN
TITUS 250 -AA
EXHAUST REGISTER
OCOOLING
THERMOSTAT
O.B.D.
X: AIR DEVICE TYPE
AX B
OX
# CFM
#
- --
TITUS 4FL
AXB: NECK SIZE
SA
SUPPLY AIR
RA
RETURN AIR
EA
EXHAUST AIR
CU
CONDENSING UNIT 4"'
AFF
ABOVE FINISH FLOOR
CFM
CUBIC FEET PER MINUTE
FCU
FAN COIL UNIT
EF
EXHAUST FAN
CONDENSING
UNIT
6" M IN.
--�
FASTEN C.U. TO CONCRETE -
PAD USING (4) 1/4" CONCRETE
SCREWS WITH 1.5" EMBEDMENT
MINIMUM AS PER MFG. CERTIFIED
DATA. PROVIDE (4) 1/2"
ISOMODE PADS AT EACH SCREW
CONCRETE BASE W/
6X6- 10 /10WWF
6" MIN. '
SEAL ENTRANCE OF REFRIGERANT
LINES INTO P.V.C. PIPE W/
IMPERMEABLE, RESILIENT MATERIAL
NOTE: CONCRETE CREWS SHALL BE RATED
FOR 500 LBS. MIN. PULL -OUT CAPACITY.
UNIT A
DRAIN
NEOPR
METAL
TYPICAI
RETURI
FLOOR
1 1/2" X 26 GA. GALV.
STEEL HANGER STRAP
(5' O.C.)
AIR DUCT (SEE PLAN VIEW)
LOW FRICTION LOSS
BRANCH TAKE -OFF FITTING
METAL ROUND FITTING
QUADRANT OPERATOR TO BE
OUTSIDE INSULATION
PROVIDE INSULATION GUARD
WHERE NECESSARY
SEAL JOINT W/
DUCT SEALER AND 6' MAX.
TAPE
AIR FLOW
INSULATE TOP
OF DIFFUSER.
DIFFUSER W/ OPPOSED
BLADE DAMPER
ADAPTOR ROUND TO SQUARE
IF REQUIRED
SUPPORT FROM
UNDERSIDE OF
STRUCTURE.
AIR FLOW
INSULATED FLEX. DUCT
BAND OF SAME SIZE
AS HANGER STRAP
SEAL JOINT WITH DUCT
SEALER AND TAPE
FLEXIBLE DUCT CONNECTION DETAIL
N.T.S.
POWER & CONTROL
CONNECTIONS
6" MIN.
4" MIN.
CONDENSING UNIT MOUNTING DETAIL
N.T.S.
STRUCTURE OF
FLOOR ABOVE
SUPPLY AIR DUCT
DISCONNECTED SWITCH
FAN SECTION
FAN COIL UNIT TO BE MOUNTED
WITH WALL METAL SHELVES.
REFRIGERANT PIPES
FROM COND. UNIT
COIL SECTION
AUX. FLOAT SWITH.%
FLOAT SWITH SHALL STOP FAN
COIL UNIT IF INDICATED.
FAN COIL UNIT MOUNTING DETAIL
N.T.S. (TYPICAL RESIDENCE UNIT)
NOTE: NO COMBUSTIBLES ALLOWED IN A/C CLOSET.
LIQUID LINE
W/O INSULATION
PVC SCH.40 PIPE SIZED
2" LARGER THAN THE PIPE
AND INSULATION ENCASED.
(4 "0 1A MIN.)
SUCTION LINE W/ 1/2"
ARMAFLEX INSULATION
& VAPOR BARRIER
NOTES, DETAILS, SCHEDULES - HVAC_
SC4LE:NiS.
'BIBhii
COORDINATE WITH PLUMBING
CONTRACTOR FOR WATER
HEATER ELEVATION.
HVAC NOTES
1. GENERAL
A. ALL WORK SHALL BE DONE in accordance with the Florida
Building Code and with all applicable regulations.
B. DRAWINGS: Refer to all drawings for coordination of the HVAC work.
C. ARRANGE AND PAY for all permits licenses, inspections and tests.
Obtain the required certificates and present to owner.
D. GUARANTEE: The completed installation shall be fully guaranteed
against defective materials and /or improper workmanship for a
minimum of one year for material and labor. Compressors shall be
guranteed for a period of five years.
E. As built drawings shall be submitted to owner at the completion
of project.
2. SHOP DRAWINGS: Contractors shall submit for approval, within 30 days
after signing contract, a minimum of five copies of fully descriptive
literature, including but not limited to: fans, air conditioning units, air outlets.
No work shall proceed without approval of these submittals.
3. DESIGN PARAMETERS:
A. Outdoor design temperature (Summer): 917 DB and 797 WB
B. Outdoor design temperature (Winter): 45'F
C. Indoor design temperature (Summer): 787 DB
D. Indoor design temperature (Winter): 727 DB
4. ALL THERMOSTATS SHALL have heating mode maximum setting of 75 F, and
cooling mode minimum setting of 70 F. The thermostat shall be arranged
to prevent the simultaneous operation of heating and cooling.
5. ELECTRICAL CONTROLS AND POWER WIRING: Under electrical contract.
6. EQUIPMENT SPECIFIED BY manufacturer's number shall include all
accessories, controls, etc., listed in the catalog as standard with the
equipment. Optional or additional accessories shall be furnished as
specified.
7. MATERIALS:
A. REFRIGERANT PIPING: Shall be type L soft drawn, copper tubing,
dehydrated for refrigerant use. Sized as shown on drawings or as
per air conditioning equipment manufacturer's recommendations.
B. INSULATION: Refrigerant suction piping shall be insulated with
1/2" thick foamed plastic insulation, fire retardant type.
Insulation shall be installed in piping before assembly. No split
insulation will be acceptable. Seal joints with manufacturer's
approved adhesive and grey tape.
C. DUCTWORK:
a. All supply air ductwork shall be fiberglass ductboard,
fabricated and installed as per latest edition of SMACNA
"Fibrous Glass Duct Manual ". 1 -1/2" thick R -6.0 in
uncond. space. 1" thick R -4.2 in cond. space.
b. All exhaust ductwork shall be galvanized sheet metal
duct not lighter than 26 gage.
c. All duct dimensions are clear inside dimensions.
d. Flexible insulated ductwork with 1 1/2" thick fiberglass
insulation with FRK vapor barrier, class I air duct, U.L.
R -6.0 MIN.
e. Dryer ductwork: 26 ga. min. galvinized steel, having a
smooth interior surface with joints running in the direction
of airflow and without sheet metal screws or other fastners
in the air stream. Maximum length shall not exceed 25 feet.
wall caps shall be provided with backdraft damper.
8. Provide metal round fittings with scoop at all flexible duct connection
to supply duct.
9. TEST AND BALANCE: Contractor shall test and balance all ventilation and
air conditioning systems. Submit four copies of Test and Balance Report
to owner for approval.
10. CONTROLS: Air conditioning units shall be started and stopped thru
individual thermostat. Individual thermostats shall start /stop supply
fans and activate cooling /heating systems as selected.
11. Mechanical plans in general, are diagrammatic in nature, and are to be read
in conjuction with arch. Plumbing, electrical and structural plans and shall
be considered as one set of documents. Duct and piping offsets, bends
and transitions will be required to provide and install a complete functional
system and shall be provided by the contractor at no additional cost to
the owner.
12. Contractor shall verify job conditions prior to ordering, fabrication or
installation of materials or equipment. Notify architect /engineer of any
conflicts before fabrication.
AIR DISTRIBUTION SCHEDULE
UNIT DESIGNATION
UNIT DESIGNATION
FCU -1
FCU -2
DESIGN MANUFACTURER
SIMBOL
USE
TYPE
ACCESORIES
& MODEL Mo.
OSUPPLY
AIR
CEILING DIFFUSER
O.B.D.
TITUS 250 -AA
OB
SUPPLY AIR
WALL REGISTER
O.B.D.
TITUS 272FS
(D
RETURN AIR
WALL / CEILING
- --
TITUS 4FL
DESIGN MANUFACTURER
RHEEM
REGISTER
RHEEM
RHEEM
OL
EXHAUST AIR
WALL LOUVER
ALUMINUM
BIRDSCREEN
RUSKIN 4O
NOTE:
1. ALL AIR DISTRIBUTION DEVICES SHALL BE ALL ALUMINUM CONSTRUCTION.
2. COORDINATE COLOR FINISH WITH ARCHITECT, WHITE BAKED ENAMEL STANDARD.
3. ARROWS INDICATE DIRECTION OF AIR DISTRIBUTION.
4. DADE COUNTY APPROVED.
SPLIT A/C UNIT SCHEDULE
UNIT DESIGNATION
UNIT DESIGNATION
FCU -1
FCU -2
FCU -2A
FCU -3
TOILET
AREA SERVED
UNITS 4
UNITS 1,2,3
UNIT 1
UNITS 5,6,7
LOCATION
LOCATION
A/C CLOSET
A/C CLOSET
A/C CLOSET
A/C CLOSET
CLG. EXHAUSTER
OPERATING WEIGHT
92.0
92.0
109
109.0
4200
DESIGN MANUFACTURER
RHEEM
RHEEM
RHEEM
RHEEM
MODEL NO.
RBHC17J11SFG
RBHC17J11SFH
RBHK21511SFC
RBHC21JIlSFG
FAN TIP SPEED, FPM MAX.
EER, MIN.
12.0
12.0
13.60
12.0
- --
- --
TOTAL AIR, CFM
1000
1200
1200
1400
0.375
MCA /MOCP
38.4/48.0
38.4/48.0
38.4/48.0
38.4/48.0
FAN MOTOR STARTER TYPE
Z
L":Lr
EXT. STATIC PRESS., INCHES OF H2O
0.4
0.4
0.4
0.4
- --
MECH. CONTRACTOR
FAN MOTOR H.P. (NON - OVERLOAD)
1/4
1/4
1/2
1/3
MASONARY OPENING REQUIRED
ELECTRICAL SERVICE AVAILABLE
208/1/60
208/1/60
SCALE:
208/1/60
0.3
0.6
FACE VELOCITY, FPM
--
--
--
--
Z
D
a
DESIGN AIR ACROSS COIL, CFM
1000
1200
1200
1400
o
U
z
TQTAL-CAPACI , BTUH
28,400
34,000
36,200
41,000
Z
GRAND
o
TO LL SENSIBLE BTUH
20,800
24,800
26,400
29,900 /
ALUM /PLASTIC
ALUM /PLASTIC
_CAPACITY,
0:
0
MULTIBLADE BACKDRAFT DAMPER
YES
YES
LZ
ov
EN RING AIR TEMP. OF DB /WB
80/67
80/67
80/67
80/67
SOLID STATE SPEED CONTROL
NO
COIL MODEL NO.
RCHA -36A1
RCHJ -36A2
RCGJ -36A2
RCHA -48A2
NO
NO
FILTER TYPE & THICKNESS
PERM & WASH
PERM & WASH
PERM & WASH
PERM & WASH
FILTER AND FILTER FRAME
NO
NO
NO
QUANTITY AND SIZE
(1)19.75X21
(1)16.25X21
(1)19.75X21
(1)19.75X21
FACE VELOCITY FPM. MAX.
HEAT /REHEAT COIL TYPE
ELECTRICAL
ELECTRICAL
ELECTRICAL
ELECTRICAL
Of
W
ELECTRICAL SERVICE AVAILABLE
208/1/60
208/1/60
208/1/60
208/1/60
=
AUXILIARY ELECTRIC HEAT, KW
7.3
7.3
7.3
7.3
STAGES AND KW /STAGE
1/7.3KW
1/7.3KW
1/7.3KW
1/7.3KW
UNIT DESIGNATION
CU -2
CU -1
CU -2A
CU -3
TYPE OF FAN
PROPELLER
PROPELLER
PROPELLER
PROPELLER
~
Z
NO. OF FANS AND FLA
1 -1.3 FLA
1 -2.0 FLA
1 -2.0 FLA
1 -2.0 FLA
D
o
AMBIENT AIR TEMP., ODB
95'
95'
95'
95'
Z
in
CONDENSING TEMP., '�7 DB
--
--
--
--
o
NO. OF COMPRESSORS
1
1
1
1
Z
0
0
COMPRESSORS RPM MAX.
--
--
--
--
W
CAPACITY REDUCTION
0 -100%
0 -100%
0 -100%
0 -100%
0
MCA /MOCP
19/30
23/35
23/35
27/45
a
ELECTRICAL SERVICE AVAILABLE
208/1/60
208/1/60
208/1/60
208/1/60
OPERATING WEIGHT,LBS.
169
185
185
255
DESIGN MANUFACTURER
RHEEM
RHEEM
RHEEM
RHEEM
MODEL NO.
RAMB030JAZ
RAMS036JAZ
RAMB036JAZ
RAMB042JAZ
REFRIGERANT LINE SUCTION & LIQUID
3/4 " -1/4"
3/4" -5/16"
3/4" -5/16"
1 -1/8" - 5/16"
NOTES: 1. ALL FAN COIL UNITS SHALL BE PROVIDED WITH FACTORY INSTALLED CIRCUIT BREAKER.
2. ALL THERMOSTATS SHALL BE PROGRAMABLE TYPE.
VENTILATION FAN SCHEDULE
UNIT DESIGNATION
EF -1
EF -2
GEF -1
AREA SERVED
TOILET
TOILET
BASEMENT
PARKING
OPERATING WEIGHT, LBS
15
17
275
LOCATION
CEILING
CEILING
CEILING
FAN TYPE
CLG. EXHAUSTER
CLG. EXHAUSTER
IN LINE EXHAUSTER
SMOKE CONTROL
TOTAL AIR, CFM
50
80
4200
DRIVE TYPE
DIRECT
DIRECT
DIRECT
FAN WHEEL TYPE
CENTRIFUGAL
CENTRIFUGAL
CENTRIFUGAL
0�
FAN TIP SPEED, FPM MAX.
- --
---
---
ILL
FAN SPEED, RPM
- --
- --
- --
Z
TOTAL STATIC PRESSURE, IN OF WATER
0.1
0.1
0.375
FAN MOTOR HP. (NON- OVERLOAD)
0.7 AMPS
1.1 AMPS
1.0 AMPS
,
FAN MOTOR STARTER TYPE
WALL SWITCH
WALL SWITCH
MOTOR RATED SWITCH
STARTER FURNISHED BY
- --
- --
MECH. CONTRACTOR
03 -060
ELECTRICAL SERVICE AVAILABLE
120 -1 -60
120 -1 -60
208 -1 -60
MASONARY OPENING REQUIRED
- --
- --
- --
SCALE:
ZONES
0.3
0.6
0.6
DESIGN MANUFACTURER
BROAN
BROAN
COOK
MODEL NUMBER
S50U
S80U
180SQI -B
SERVICE SWITCH
YES (WALL)
YES (WALL)
YES
SMOKE DETECTOR ( U.L. APPROVED)
NO
NO
NO
FIRE DAMPER
- --
- --
- --
w
CONSTRUCTION
ALUM /PLASTIC
ALUM /PLASTIC
GALV. STEEL
0:
0
MULTIBLADE BACKDRAFT DAMPER
YES
YES
YES
(n
w
BIRDSCREEN
NO
NO
NO
U
a
SOLID STATE SPEED CONTROL
NO
NO
YES
THERMOSTAT CONTROL
NO
NO
NO
FACTORY FABRICATED CURB
NO
NO
NO
FILTER AND FILTER FRAME
NO
NO
NO
HVAC DESIGN REQUIRES:
YES
NO
DUCT SMOKE DETECTOR
-
X
FIRE DAMPER(S)
-
X
SMOKE DAMPER(S)
-
X
FIRE RATED ENCLOSURE
-
X
FIRE RATED ROOF /FLOOR
CEILING ASSEMBLY
_
X
FIRE STOPPING
-
X
SMOKE CONTROL
-
X
CJ
oO�fl • o
I�,PJ, Inc.
STATE OF FL CO. NO. (000065130 ) P.E. NO. (� 16395)
4977 S.W. 74th COURT
MIAMI, FL 33155
PHONE: (305) 666 -2131 FAX: (305) 666 -0131
JCHAS & ASSOCIATES, PA
0
43M &W. '11 TH STRIEL7
MWrN, Ratio 33146
TEL- (305) 969 3149
FAX: (305) 4471501
JACFIASTANI T O d M
A R 0 0 1 2 6
1 1
OWNERS:
PALMAS OF SUNSET J.V.
5835 Blue Lagoon Drive, Subs 200
Mlerrrl, Fbrkia 33126
T 786275.8480
F 786275.8474
x
`
'
R AEL P A Jit. (1639
��M
v�
oO�fl • o
I�,PJ, Inc.
STATE OF FL CO. NO. (000065130 ) P.E. NO. (� 16395)
4977 S.W. 74th COURT
MIAMI, FL 33155
PHONE: (305) 666 -2131 FAX: (305) 666 -0131
JCHAS & ASSOCIATES, PA
ARCHITECTURE PLANNING INTERIORS
43M &W. '11 TH STRIEL7
MWrN, Ratio 33146
TEL- (305) 969 3149
FAX: (305) 4471501
JACFIASTANI T O d M
A R 0 0 1 2 6
1 1
OWNERS:
PALMAS OF SUNSET J.V.
5835 Blue Lagoon Drive, Subs 200
Mlerrrl, Fbrkia 33126
T 786275.8480
F 786275.8474
��M
v�
O
T
Z
M
0�
® 11 III
O
�
ILL
nn�
U �
O010
IuL,
.
MO
L�
a
,
A T E:
D12-14-03
REVISIONS:
PROJECT Na
03 -060
DRAWN BY:
n
T. L ILS
CHECKED BY:
RPJ
SCALE:
AS SHOWN
SHEET No.
AC -4