10-723-086
VOLTAeE DROP CALCULATIONS 1. 3% VOLTAGE DROP CALCULATED FOR EVERY BRANCH CIRCUIT SHOWS MAXIMUM DISTANCE ALLOWED FOR THE SPECIFIED WIRE SIZE BASED ON DESIGNED LOAD. 2. ALL CIRCUITS HAVE BEEN VERIFIED ON FLOOR PLANS BASED ON HORIZONTAL STRAIGHT RUNS WITH ADDITIONAL 30 FEET OF VERTICAL RUNS. ACTUAL DISTANCES FOR EVERY CIRCUIT RUN SHALL BE FIELD MEASURED BY THE ELECTRICAL CONTRACTOR. CONTRACTOR SHALL PROVIDE NEXT WIRE SIZE FOR RUNS OVER MAXIMUM DISTANCE SHOWN ON PANEL SCHEDULES. PAVEL SCHIDULES KOTES 1. BOLD DENOTES AREA OF WORK FOR REFERENCE ONLY. 2. UPON DEMOLITION, CONTRACTOR SHALL IDENTIFY AND REUSE CIRCUITS THAT BECOME AVAILABLE, AND PROVIDE ENGINEER WITH COMPLETE AS BUILTS, REFER TO NOTE #31 OF THE ELECTRICAL SPECIFICATIONS. 3. IF AVAILABLE ARE INSUFFICIENT, CONTACT ENGINEER IMMEDIATELY. 4. CONTRACTOR SHALL CLEARLY MARK IN PANEL SCHEDULE ALL CIRCUITS. 5. CONTRACTOR SHALL REMOVE ALL WIRING NOT USED AND NOT IN A RACEWAY GOING INTO CLIENT SPACE. 6. CONTRACTOR SHALL MARK AS SPARE DEMO CIRCUIT NOT BEEN USED BY THE SPACE AND LEAVE THEM IN OFF POSITION. DRMCH CIRCUIT COI^; DUIT SIZE WIRE SIZE CONDUIT SIZE _._. ----------------- 0, --------- 10 1 2" a 14" S____� -_ _ 4 1" 3 1 1/4" - - -- - - - - -- 11g- 1 1 1/2 MW 1 PANEL SCHEDULE LD (EXISTING) Rated Voltage: 1201208V 3PHAW Manufacture: EXISTING Mounting: SURFACE Rated Amps: (Cu bus) 225A SPACES: 42 Location: 2ND FL ELEC ROOM Type: NEMA 1 Main: MLO Project No: 10069.00 A.I.C: EXISTING KVA KVA PANEL SCHEDULE DPB O.C.P. (EXISTING) MAX. DIST.(ft) VOLT DROP RCPT LTG MOT /OTHER PH RCPT Rated Voltage: 120/20$V 3PH,4W VOLT DROP Manufacture: EXISTING 0C.P. Mounting: MAX. SURFACE Show Win rec list FI (note 7) 20/1 Rated Amps: (Cu bus) 900A 3% SPACES: 24 Location: 2ND FL ELEC ROOM Type: 1.00 NEMA 1 217 3% Main: MCB Show Win rec 2nd FI (note 7) 2 3 Project No: 10069.00 2011 A.I.C: 132 EXISTING PANEL'HA' 1 1.00 1.20 B 1.10 1.00 KVA KVA 3% 10 20/1 Show Win rec 2nd FI (note 7) 4 5 CIRCUIT DESIGNATION O.C.P. AWG MAX. VOLT RCPT LTG MOTIOTHER PH I RCPT LTG MOT /OTHER MAX. VOLT AWG O.C.P. CIRCUIT DESIGNATION 6 7 NEW PANEL'UPS' 90/2 4 DIST.(ft) DROP 1.44 0.00 4.00 A 1.10 1.00 29.00 DIST.(ft) DROP 10 20/1 Show Win rec 2nd FI (note 7) 9 1 PANEL'LD' 200/3 SEE RISER B 3% 1.44 7.00 4.00 A 0.00 7.46 2.20 10 11 SEE RISER 20013 PANEL'LC' 2 3 3.06 7.00 2.50 B 0.00 7.26 2.00 4 5 0.00 7.40 0.00 C 0.00 6.26 2.00 C 7 PANEL'LE' 200/3 SEE RISER 12 A 9.00 0.00 3.40 A 3% 10 20/1 Show Win rec 1st FI (note 7) 14 15 SPARE SPACE t 9 6.90 0.00 6.20 B 13 3% 1 1.00 3% 217 3% 10 SPACE 10 11 6.52 0.00 6.20 C 16 17 2nd fl conv receptacles 20/1 12 C 3% SPACE 12 13 SPACE 10 2011 Show Win rec 1st FI (note 7) 13 19 SPARE 20/1 A 19 19 2nd fl conv receptacles 20/1 12 A 3% SPACE 14 15 SPACE 10 20/1 Show Win rec 1st FI (note 7) 20 21 SPARE 20/1 B 20 21 SPARE 20/1 12 B B SPACE 16 17 SPACE 10 20/1 Show Win rec 1st FI (note 7) 22 23 SPARE 20/1 C 22 23 Office receptacles (2nd fl) 2011 12 C 3% SPACE 19 19 SPACE 20/1 FUTURE SHOW WINDOW REC 24 25 SPARE 2011 A 24 25 Office receptacles (2nd fl) 20/1 12 A 3% SPACE 20 21 SPACE 10 20/1 Show Win rec 1st FI (note 7) 26 27 SPARE 20/1 B 26 27 COPIER 20/1 12 B 3.6 SPACE 22 23 SPACE 10 2011 Show Win rec 1st FI (note 7) 2= 29 SPARE 2011 C 29 219 Office receptacles (2nd fl) 2011 12 C 3.6 SPACE 24 217 SUBTOTAL CONNECTED LOAD: 10 2011 25.9 21.4 22.3 SPACE 0.0 21.0 6.2 31 Office receptacles (2nd fl) : SUBTOTAL CONNECTED LOAD 12 A CONNECTED LOAD PHASE A: 33.5 SUBTOTAL CONNECTED LOAD: 217 CONTINUOUS & LARGEST MOTOR @ 25.1.: 10.6 20/1 note 1 verity max. O.C.P.D. with nameplate 33 CONNECTED LOAD PHASE B: 34.9 SPARE 32 33 CONNECTED MOTOR LOADS @ 100 %: 29.5 12 note 2 lockable circuit breaker 1.00 TOTAL COMPUTED LOAD: 400 KVA note 6 tune switch controlled CONNECTED LOAD PHASE C: 29.4 1 10 2011 Show Win rec 1st FI (note 7) CONNECTED LIGHTING LOAD @100 %: 42.4 SPACE note 3 non - concurrent load 34 35 TOTAL CONNECTED LOAD: 96.9 12 C 3.6 1.00 217 note 4 G.F.C.I. t)7x circuit breaker 20/1 Show Win rec 1st FI (note 7) RECEPT. CONNECTED LOAD: 25.•9 SPACE 3011 EXISTING RECEPEPTACLE COMPUTED LOAD: 19.0 Office receptacles (2n4 fl) note 5 Provide a lighting contactor A 3.6 0.72 2.10 A TOTAL COMPUTED LOAD: 99 KVA 38 note 6 Via separate time switch 20/1 EXISTING 39 39 Office receptacles (2nd fl) 2011 12 B 276 AMPS 0.72 note 7 Via lighting relay panel B PANEL SCHEDULE LD (EXISTING) Rated Voltage: 1201208V 3PHAW Manufacture: EXISTING Mounting: SURFACE Rated Amps: (Cu bus) 225A SPACES: 42 Location: 2ND FL ELEC ROOM Type: NEMA 1 Main: MLO Project No: 10069.00 A.I.C: EXISTING KVA KVA • = • • Y r Y • 4 4 � PANEL SCHEDULE DPA (EXISTING) • r Y • Y • V V Y ` CIRCUIT DESIGNATION O.C.P. AWG MAX. DIST.(ft) VOLT DROP RCPT LTG MOT /OTHER PH RCPT LTG MOTIOTHER MAX. DIST.(ft) VOLT DROP AWG 0C.P. CIRCUIT DESIGNATION MAX. 1 Show Win rec list FI (note 7) 20/1 12 132 3% VITACU RA 1.00 1.20 A 1.10 1.00 2.50 217 3% 10 20/1 Show Win rec 2nd FI (note 7) 2 3 Show Win rec list FI (note 7) 2011 12 132 3% PANEL'HA' 1 1.00 1.20 B 1.10 1.00 16.10 217 3% 10 20/1 Show Win rec 2nd FI (note 7) 4 5 SPACE 20/1 12 110 3.6 0.00 21.00 1.20 C 1 1.00 2.50 217 1 3% 10 1 20/1 Show Win rec 2nd FI (note 7) 6 7 NEW PANEL'UPS' 90/2 4 140 2% 1.44 0.00 4.00 A 1.10 1.00 29.00 217 3% 10 20/1 Show Win rec 2nd FI (note 7) 9 9 3,06 0.00 2.50 B 3% 1.00 29.00 217 3% 10 20/1 Show Win rec 2nd FI (note 7) 10 11 SPACE 20/1 2n4l fl Caleidescope quasi recept 10 11 2nd fl conv receptacles 2011 12 C 3% 1.00 540 217 3% 10 20/1 Show Win rec 2nd FI (note 7) 12 13 SPARE 2011 2nd fl Caleidoscope quad recept 12 13 2nd fl conv receptacles 2011 12 A 3% 1.00 B 217 3% 10 20/1 Show Win rec 1st FI (note 7) 14 15 SPARE 20/1 2nd fl Caleidoscope quad recept 14 15 VISUAL OFF RECEPT 20/1 12 13 3% 1 1.00 3% 217 3% 10 1 2011 Show Win rec 1st FI (note 7) 16 17 SPARE 20/1 2nd fl Caleidoscope quad recept 16 17 2nd fl conv receptacles 20/1 12 C 3% 1.00 3.10 217 3% 10 2011 Show Win rec 1st FI (note 7) 13 19 SPARE 20/1 2nd fl Caleidoscope quad recept 19 19 2nd fl conv receptacles 20/1 12 A 3% 1.00 2.70 217 3% 10 20/1 Show Win rec 1st FI (note 7) 20 21 SPARE 20/1 2nd fl Caleidoscope quad recept 20 21 SPARE 20/1 12 B B 1.00 3.20 217 3% 10 20/1 Show Win rec 1st FI (note 7) 22 23 SPARE 20/1 2nd fl Caleidescope quad recept 22 23 Office receptacles (2nd fl) 2011 12 C 3% 2.40 540 A C 20/1 FUTURE SHOW WINDOW REC 24 25 SPARE 2011 SPARE 24 25 Office receptacles (2nd fl) 20/1 12 A 3% 1.00 33 217 3% 10 20/1 Show Win rec 1st FI (note 7) 26 27 SPARE 20/1 SPARE 26 27 COPIER 20/1 12 B 3.6 1.00 36 217 3% 10 2011 Show Win rec 1st FI (note 7) 2= 29 SPARE 2011 SPARE 29 219 Office receptacles (2nd fl) 2011 12 C 3.6 1.00 39 217 1 3% 10 2011 Show Win rec 1st FI (note 7) 30 31 SPACE 20/1 SPARE 30 31 Office receptacles (2nd fl) 2011 12 A 3% 1.00 SUBTOTAL CONNECTED LOAD: 217 3% 10 20/1 Show Win rec 1st FI (note 7) 32 33 SPACE 20/1 SPARE 32 33 Office receptacles (2nd fl) 20/1 12 B 1 1.00 TOTAL COMPUTED LOAD: 400 KVA note 6 tune switch controlled 217 3% 1 10 2011 Show Win rec 1st FI (note 7) 34 35 SPACE 20/1 EXISTING 34 35 Office receptacles (2nd fl) 20/1 12 C 3.6 1.00 217 3`/. 10 20/1 Show Win rec 1st FI (note 7) 36 37 SPACE 3011 EXISTING 36 37 Office receptacles (2n4 fl) 2011 12 A 3.6 0.72 2.10 A SPACE 38 39 SPACE 20/1 EXISTING 39 39 Office receptacles (2nd fl) 2011 12 B 3.6 0.72 B SPACE 40 41 SPACE 50/2 EMSTING 40 41 SPARE 2011 C SPACE 42 C SUBTOTAL CONNECTED LOAD: SPACE 42 32.2 SUBTOTAL CONNECTED LOAD: 0.0 4.5 2.0 6.5 0.0 19.4 0.0 SUBTOTAL CONNECTED LOAD CONNECTED LOAD PHASE A: 12.4 CONTINUOUS & LARGEST MOTOR @ 25 %! 5.4 note 1 verity max. O.C.P.D. with nameplate CONNECTED LOAD PHASE d: 12.6 CONNECTED MOTOR LOADS @ 100 %: 6.5 note 2 lockable circuit breaker CONNECTED LOAD PHASE C: 7.4 CONNECTED LIGHTING LOAD @100.6: 21.4 note 3 non - concurrent load TOTAL CONNECTED LOAD: 32.4 note 4 G.F.C.l. type circuit bleaker RECEPT. CONNECTED LOAD: 4.5 RECEPEPTACLE COMPUTED LOAD: 4.5 note 5 Provide a lighting contactor TOTAL COMPUTED LOAD: 39 KVA note 6 Via separate tune switch 105 AMPS note 7 Via existing lighting contactor PANEL SCHEDULE LE (EXISTING) Rated Voltage: 120 /209V 3PHAW Manufacture: EXISTING Mounting: SURFACE Rated Amps: (Cu bus) 225A SPACES: 42 Location: 2ND FL ELEC ROOM Type: NEMA II Main: MLO Project No: 10069.00 A. C: EXISTING KVA KVA • = • • Y r Y • 4 4 � PANEL SCHEDULE DPA (EXISTING) • r Y • Y • V V Y ` CIRCUIT DESIGNATION O.C.P. AWG MAX. DIST.(ft) VOLT DROP RCPT LTG MOT /OTHER PH RCPT LTG MOTIOTHEIR MAX. DIST.(ft) VOLT DROP AWG O.C.P. CIRCUIT DESIGNATION MAX. 1 1ST FL MOTORIZED DOOR 20/1 12 110 3% VITACU RA 2.50 1.20 A 1.10 2.50 120 3% 12 20/1 2nd fl Caleidescope quad recept 2 3 1ST FL MOTORIZED DOOR 2011 12 110 3.6 PANEL'HA' 1 200/3 1.20 B 1.10 0.00 16.10 120 3% 12 20/1 2nd fl Caleidoscope quad recept 4 5 2ND FL MOTORIZED DOOR 20/1 12 110 3.6 0.00 21.00 1.20 C 1.10 1 2.50 120 3`I. 12 2011 2nd fl Caleidoscope quad recept 6 7 2ND FL MOTORIZED DOOR 20/1 12 110 3% 150/3 1/0 1.20 A 1.10 29.00 120 1 3`/. 12 1 20/1 2nd fl Caleidoscope quad recept 9 9 2nd fl conv receptacles 20/1 12 146 3% 0.90 29.00 B B 1.10 13.00 10 120 3% 12 20/1 2n4l fl Caleidescope quasi recept 10 11 2nd fl conv receptacles 2011 12 146 3% 0.90 540 3% C 0.72 13.00 A 193 3% 12 20/1 2nd fl Caleidoscope quad recept 12 13 2nd fl conv receptacles 2011 12 146 3% 0.90 B A 0.72 16 17 193 3% 12 20/1 2nd fl Caleidoscope quad recept 14 15 VISUAL OFF RECEPT 20/1 12 244 3% 0.54 3% B 0.72 A 193 3.6 12 20/1 2nd fl Caleidoscope quad recept 16 17 2nd fl conv receptacles 20/1 12 244 3% 0.54 3.10 C 0.72 23 193 3% 12 20/1 2nd fl Caleidoscope quad recept 19 19 2nd fl conv receptacles 20/1 12 244 3% 0.54 2.70 A 0.72 2.50 193 3.6 12 20/1 2nd fl Caleidoscope quad recept 20 21 SPARE 20/1 12 7.00 B 3.20 4.00 B 0.72 2.50 193 3% 12 20/1 2nd fl Caleidescope quad recept 22 23 Office receptacles (2nd fl) 2011 12 193 3% 0.72 540 A C 5.90 20/1 SPARE 24 25 Office receptacles (2nd fl) 20/1 12 120 3% 1.10 33 ESCALATOR A 10 345 3% 345 3% 10 20/1 SPARE 26 27 COPIER 20/1 12 132 3.6 5.90 36 1.00 B 350/3 SEE RISER 2.50 1 291 3% 12 20/1 SPARE 29 219 Office receptacles (2nd fl) 2011 12 120 3.6 1.10 39 39 C B 20/1 SPARE 30 31 Office receptacles (2nd fl) 2011 12 120 3% 1.10 SUBTOTAL CONNECTED LOAD: A 0.0 52.2 1 212.7 1 0.0 0.0 20/1 SPARE 32 33 Office receptacles (2nd fl) 20/1 12 120 3% 1.10 TOTAL COMPUTED LOAD: 400 KVA note 6 tune switch controlled 492 AMPS note 7 mechanically held lighting contactor B 1.00 132 3% 12 20/1 EXISTING 34 35 Office receptacles (2nd fl) 20/1 12 193 3.6 0.72 C 2.00 109 3% 10 3011 EXISTING 36 37 Office receptacles (2n4 fl) 2011 12 193 3.6 0.72 2.10 A 1.00 132 3% 12 20/1 EXISTING 39 39 Office receptacles (2nd fl) 2011 12 1113 3.6 0.72 B 3.00 44 3% 12 50/2 EMSTING 40 41 SPARE 2011 SPACE 42 C SUBTOTAL CONNECTED LOAD: 3.00 42 32.2 SUBTOTAL CONNECTED LOAD: 0.0 11.6 0.0 5.9 9.9 010 10.0 : SUBTOTAL CONNECTED LOAD CONNECTED LOAD PHASE A: 11.4 CONTINUOUS 4 LARGEST MOTOR @ 25.6: 0.0 note 1 verily max, O.('.P. D. with nameplate CONNECTED LOAD PHASE B: 13.1 CONNECTED MOTOR LOADS @ 100%: 15.9 note 2 kickable circuit breaker CONNECTED LOAD PHASE C: 12.7 CONNECTED LIGHTING LOAD @100X: 0.0 note 3 non - concurrent load TOTAL CONNECTED LOAD: 37.2 note 4 CiT.C.I. t)pe circuit breaker RECEPT. CONNECTED LOAD: 21.4 RECEPEPTACLE COMPUTED LOAD: 15.7 note 5 Provide a lighting contactor TOTAL COMPUTED LOAD: 32 KVA note 6 Via separate time switch 97 AMPS note 7 Via lighting rclay panel Y V W U Y N �' U • N• 4 V U 4 Y N • • � 1, Y t U Y t`i • iotk •t1�IMNN1ro'�gNlMlif►llttk!� 01�. Y r V yy • = • • Y r Y • 4 4 � PANEL SCHEDULE DPA (EXISTING) • r Y • Y • V V Y ` Rated Voltage: 2771480V 3PHAW Manufacture: EXISTING Moanting:'rr SURFAC-CE Rated Amps: (Cu bus) 1200A SPACES: 42 Location: 2ND FL ELEC ROOM Type: NEMA 1 Main: 1000AMCB Project No: 10069.00 F. C Y••tiaISTING -�� �•••• KVA KVA " "`� �Nv • -- VOLT DROP CIRCUIT DESIGNATION O.C.P. AWG MAX. VOLT RCPT LTG MOTIOTHER PH RCPT LTG MOTIOTHER MAX. VOLT EXISTING LIGHTS 1st floor J (i.C.P.. • • Clio; oft DtSi`GVA`rION 291 3% VITACU RA 2.50 DIST.(ft) DROP 2.50 291 3% 12 20/1 CU DIST.(ft) DROP 1st Floor LIGHTS (note 7) zone 1 20/1 12 251 1 PANEL'HA' 1 200/3 SEE RISERI B 0.00 16.10 9.60 A 12 20/1 CU 4 5 SEE RISER 200/3 PANEL'LA'&'LB' VIA TRANSFORMER 2 3 0.00 21.00 7.10 B 1 1 2.50 4 5 0.00 15.10 4.60 C 7 1st Floor LIGHTS (note 7) zone 2 20/1 6 7 AHU -9 150/3 1/0 250 3% 29.00 A 3% 12 13.00 540 3% 4 70/3 AHU -4 9 9 3% 29.00 B B 13.00 10 11 3% 12 29.00 C 10 11 13.00 12 13 AHU -1 70/3 4 540 3% C 13.00 A 200 3% 11.00 421 3% 6 60/3 AMU -5 14 15 13.00 B A 11.00 16 17 395 3% 13.00 C ROOF LIGHTS (note 7) 14 11.00 19 19 AHU -2 50/3 4 334 3% B 9.00 A 291 7.00 430 3% 9 40/3 AHU -6 20 21 12 226 9.00 B 3.10 7.00 22 23 291 00 C 20/1 EXISTING 7.00 24 25 AHU -3 40/3 E 430 3% 2.70 7.00 A 2.50 4.00 304 3`/. 12 20/3 AHU -7 26 27 2011 12 7.00 B 3.20 4.00 29 30 29 2.50 7.00 C 12 20/1 4.00 31 23 2n4I Floor LIGHTS (bath /locker) 20/1 12 469 3% 540 A C 5.90 32 24 25 5.90 B 12 252 5.90 34 33 ESCALATOR 30/3 10 345 3% 345 3% 10 30/3 ESCALATOR 35 27 EXISTING LIGHTS 2nd floor 5.80 C 469 3% 5.90 36 37 PANEL'PDB' VIA TRANSFORMER 350/3 SEE RISER 2.50 1 291 3% 12 20/1 A 29 29 EXISTING LIGHTS 2nd floor 20/1 12 469 3.6 39 39 C B 40 42 41 30 31 SPACE C SUBTOTAL CONNECTED LOAD: A 0.0 52.2 1 212.7 1 0.0 0.0 122.4 1 32 SUBTOTAL CONNECTED LOAD SPACE CONNECTED LOAD PHASE A: 130.3 CONTINUOUS & LARGEST MOTOR @ 25 %: 13.1 note 1 verify max. O.C.P.I), with nameplate CONNECTED LOAD PHASE d: 132.7 CONNECTED MOTOR LOADS @ 100 %: 335.1 note 2 lockable circuit breaker CONNECTED LOAD PHASE C: 124.3 CONNECTED LIGHTING LOAD @100%: 52.2 note 3 non - concurrent load TOTAL CONNECTED LOAD: 397.3 note 4 G.f.C.I. type circuit breaker RECEPT. CONNECTED LOAD: 0.0 RECEPEPTACLE COMPUTED LOAD: 0.0 note 5 photo cell controlled TOTAL COMPUTED LOAD: 400 KVA note 6 tune switch controlled 492 AMPS note 7 mechanically held lighting contactor PANEL SCHEDULE HA (EXISTING) Rated Voltage: 2771490V 3PHAW Manufacture: EXISTING Mounting: SURFACE Rated Amps: (Cu bus) 400A SPACES: 42 Location: 2ND FL ELEC ROOM Type: NEMA 1 Main: 300A MCB Project No: 10069.00 A.I.0: EXISTING KVA KVA DPd CIRCUIT DESIGNATION O.C.P, AWG MAX. DIST.(ft) VOLT DROP RCPT LTG MOTIOTHER PH RCPT LTG MOTIOTHER MAX. DIST.(ft) VOLT DROP AWG O.C.P. CIRCUIT DESIGNATION WHERE PREPARED BY ME OR UNDER MY SUPERVISION, AND TO THE BEST 1 EXISTING LIGHTS 1st floor 20/1 12 291 3% VITACU RA 2.50 A 2.50 291 3% 12 20/1 CU 2 3 1st Floor LIGHTS (note 7) zone 1 20/1 12 251 3% 2.90 B 2.50 291 3% 12 20/1 CU 4 5 1 1st Floor LIGHTS (note 7) zone 1 20/1 12 1 234 3% 1 3.00 C 1 1 2.50 291 1 3% 12 1 20/1 CU 6 7 1st Floor LIGHTS (note 7) zone 2 20/1 12 234 3% 3.00 A 2.50 291 3% 12 20/1 CU 9 9 EXISTING LIGHTS 1st floor 20/1 12 291 3% 2.50 B 3.50 200 3% 12 2011 LIGHT BOX (note 7) 10 11 SPARE 20/1 C 3.50 200 3% 12 20/1 LIGHT BOX (note 7) 12 13 SPARE 2011 A 3.00 395 3% 10 2011 ROOF LIGHTS (note 7) 14 15 LIGHT BOXUH 20/1 12 291 3% 2.50 B 2.50 291 3% 12 20/1 EXISTING 1C 17 2nd Floor LIGHTS (zone 4) 2011 12 226 3% 3.10 C 2.50 291 3% 12 20/1 EXISTING 19 19 2nd Floor LIGHTS (zone 4) 20/1 12 260 3% 2.70 A 2.50 291 3% 12 20/1 EXISTING 20 21 2nd Floor LIGHTS (zone 5) 2011 12 219 3% 3.20 B 2.50 291 3% 12 20/1 EXISTING 22 23 2n4I Floor LIGHTS (bath /locker) 20/1 12 469 3% 1.50 C SPACE 24 25 2nd Floor LIGHTS (office) (note 7) 20/1 12 252 3% 2.40 A 2.50 291 3% 12 20/1 CU 26 27 EXISTING LIGHTS 2nd floor 2011 12 469 3% 1.50 B 2.50 1 291 3% 12 20/1 CU 29 29 EXISTING LIGHTS 2nd floor 20/1 12 469 3.6 1.50 C SPACE 30 31 SPACE A SPACE 32 33 SPACE B SPACE 34 35 SPACE C SPACE 36 37 NEW SCISSOR LIFT 5HP 1513 12 334 3% 2.10 A SPACE 39 39 2.10 B SPACE 40 41 2.10 C SPACE 42 SUBTOTAL CONNECTED LOAD: 0.0 32.2 1 6.3 0.0 20.0 15.0 : SUBTOTAL CONNECTED LOAD CONNECTED LOAD PHASE A: 25.7 CONTINUOUS 9 LARGEST MOTOR @ 25.6: 13.1 note 1 verll'y max. O.C.P,D, with nameplate CONNECTED LOAD PHASE Q: 29.1 CONNECTED MOTOR LOADS @ 100.6: 21.3 note 2 lockable circuit breaker CONNECTED LOAD PHASE C: 19.7 CONNECTED LIGHTING LOAD @100.6: 52.2 note 3 non - concurrent load TOTAL CONNECTED LOAD: 73.5 note 4 G.F.CI. type circuit breaker RECEPT. CONNECTED LOAD: 0.0 RECEPEPTACLE COMPUTED LOAD: 0.0 note 5 photo cell controlled TOTAL COMPUTED LOAD: E7 KVA note 6 time switch controlled 104 AMPS note 7 Via lighting relay panel PAV211.8' CHART DPd DPA LD HA LE SURE 0 202 DANIA BEACH, FLORIDA 33004 PH: (954) 922 -6551 architect NORBERTO ROSENSTEIN ARCHITECT , INC. RUMCM - MM DE" - nJWM 126 S. FEDERAL HIGHWAY SURE 0 202 DANIA BEACH, FLORIDA 33004 PH: (954) 922 -6551 FAX: (954) 922 -7385 EMAIL- info•rw+er otainarchitectcom WEBS www.rowmteinarchitect.com STATE REG. NO. APtOOI&674 NATL. RECs. NO. &c�I'78 COP1'RICsHT © 2010 N011417ERTO MOSEN81EIN ARCHITECT, INC. ALL RICsFdtfr F SERVEp- tHIb pOCUMEhtT OR PARTS THEREOF, MAY NOT 156 PRODUCED IN ANY FOIE" I kW UT PEFMO610K DESIGNED % / / %if / % %' -' As N As ;DRAWA5:: ECKED EH I HEREBY CERTIFY THAT THESE PLANS WHERE PREPARED BY ME OR UNDER MY SUPERVISION, AND TO THE BEST OF MY KNOWLEDGE, COMPLY WITH ALL APPLICABLE CODES. elton + lenmiz A R Q U I T E C T O S A S O C I A D 0 S RUT :76.575.840 -8 AURELIO GONZALEZ 3330 VITACU RA Q 08/11/10 GEN. REVISION AS R E V I S 1 0 N S