10-723-085ELECTRICAL SPECIFICATIONS 1. MATERIALS AND INSTALLATION, AS A MINIMUM, ARE TO CONFORM WITH THE ADOPTED EDITION OF THE NATIONAL ELECTRIC CODE, N.F.P.A., LOCAL CODES, ORDINANCES, INCLUDING ALL AMENDMENTS TO THE N.E.C. EQUIPMENT, WHERE APPLICABLE, WILL BE LISTED WITH THE UNDERWRITERS LABORATORIES, INC. QUALITY AND WORKMANSHIP ESTABLISHED BY DRAWINGS AND SPECIFICATIONS ARE NOT TO BE REDUCED BY THE ABOVE MENTIONED CODES. 2. BIDDERS ARE TO VISIT THE SITE AND FAMILIARIZE THEMSELVES WITH EXISTING CONDITIONS AND SATISFY THEMSELVES AS TO THE NATURE AND SCOPE OF WORK. THE SUBMISSION OF A BID WILL BE EVIDENCE THAT SUCH AN EXAMINATION HAS BEEN MADE. LATER CLAIMS FOR LABOR, EQUIPMENT, OR MATERIALS REQUIRED, OR FOR DIFFICULTIES ENCOUNTERED WHICH COULD HAVE BEEN FORESEEN HAD AN EXAMINATION BEEN MADE, WILL NOT BE ALLOWED. 3. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST -CLASS WORKMANLIKE MANNER. THE COMPLETED SYSTEM IS TO BE FULLY OPERABLE AND ACCEPTANCE OF THIS SYSTEM BY THE ENGINEER MUST BE A CONDITION OF THE SUB CONTRACT. 4. ALL WORK TO BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH THE PROGRESS OF CONSTRUCTION. 5. CONTRACTOR TO GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS FOR PERIOD OF NOT LESS THAN ONE (1) YEAR FROM DATE OF ACCEPTANCE. G. CORRECTION OF ANY DEFECTS TO BE COMPLETED WITHOUT ADDITIONAL CHARGE AND TO INCLUDE REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY. 7. ALL REQUIRED INSURANCE TO BE PROVIDED FOR PROTECTION AGAINST PUBLIC LIABILITY OF PROPERTY DAMAGE FOR THE DURATION OF THE WORK. a. CONTRACTOR TO PAY FOR ALL PERMITS, FEES INSPECTIONS AND TEST1NGS. 9. ELECTRICAL INSTALLATION TO MEET ALL STANDARD REQUIREMENTS OF LOCAL POWER AND TELEPHONE COMPANIES. ELECTRICAL CONTRACTOR SHALL CONTACT LOCAL POWER AND TELEPHONE COMPANIES PRIOR TO START OF CONSTRUCTION. 10. ALL WIRING SHALL BE IN CONDUIT UNLESS OTHERWISE NOTED, MINIMUM WIRE SIZE SHALL BE #12 AWG, EXCLUDING CONTROL WIRING. ALL CONDUCTORS SHALL BE COPPER WITH THWN/THHN INSULATION. CONDUCTORS #10 AND SMALLER MAY BE SOLID; ALL THOSE #a AND LARGER TO RE STRANDED. ' 11. ALL UNDERGROUND RACEWAYS SHALL BE MINIMUM 3/4 ", GALVANIZED RIGID STEEL CONDUIT OR SCHEDULE 40 PVC. ALL OTHER RACEWAYS TO COMPLY WITH GOVERNING CODES. WHERE RIGID STEEL IS USED, IT SHALL BE COMPLETELY COATED WITH AN ALKALI AND RUST RESISTANT BITUMASTIC PAINT, COPPER NO. 50, AND THREADS SHALL BE COATED WITH ZINC CHROMATE. RIGID STEEL SHALL ALSO BE USED WHEN CONDUIT IS EXPOSED TO EXTERIOR ENVIRONMENT SUCH AS EXTERIOR OF BUILDING OR WHERE IT IS EXPOSED AND SUBJECT TO DAMAGE, INSIDE OF BUILDING. 12. OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS, CAST ALLOY WITH THREADED HUBS IN WET OR DAMP LOCATIONS, AND BE OF SPECIAL CONSTRUCTION FOR OTHER CLASSIFIED AREAS. ALL BOXES SHALL BE RECESSED (FLUSH) IN WALLS OR CEILINGS WHENEVER POSSIBLE. 13. DISCONNECT SWITCHES SHALL BE H.P. RATED, GENERAL DUTY, QUICK -MAKE, QUICK -BREAK TYPE. ENCLOSURES SHALL BE AS REQUIRED BY N.E.C. AND LOCATION (WEATHERPROOF, EXPLOSION PROOF, ETC.). ENGRAVED LAMINATED PLASTIC IDENTIFICATION PLATES SHALL BE FURNISHED AND INSTALLED ON ALL DISCONNECT SWITCHES, CONTACTORS AND STARTERS. 14. ALL FUSES FOR SAFETY SWITCHES SHALL BE DUAL ELEMENT, CARTRIDGE TYPE. FUSES SHALL BE THOSE MANUFACTURED BY EITHER BUSSMAN OR LITTLEFUSE. THE CONTRACTOR SHALL FURNISH TO THE OWNER ONE SPARE FUSE FOR EACH SIZE AND TYPE OF FUSE INSTALLED. FUSES 600 AMPS OR LESS SHALL BE CLASS RK1, TYPICAL UNLESS OTHERWISE NOTED, FUSES OVER 600 AMPS SHALL BE CLASS L. 15. ALL GENERAL PURPOSE SWITCHES AND RECEPTACLES SHALL DE THE PRODUCT OF A SINGLE MANUFACTURER. CATALOG NUMBERS LISTED ARE LEVITON: HOWEVER, COMPARABLE DEVICES BY PASS & SEYMOUR, BRYANT, OR ARROW HART WILL BE ACCEPTED. COLOR OF DEVICES AND PLATES SHALL BE WHITE UNLESS DICTATED OTHERWISE BY ARCHITECT /OWNER. A. SWITCHES: LEVITON #CS151 -20W 3. RECEPTACLES: LEVITON #13R20 -W C. COVER PLATES: SMOOTH PLASTIC NOTE: ALL OTHER REQUIRED DEVICES SHALL MATCH IN COLOR AND STYLE. 16. IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. THE CONTRACTOR IS EXPECTED TO FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL SYSTEM, AND PROVIDE ALL NECESSARY DEVICES AND COMPONENTS FOR EQUIPMENT BE PLACED IN PROPER WORKING ORDER. 17, A SEPARATE, GREEN TYPE THWN COPPER GROUND CONDUCTOR SHALL BE RUN FROM GROUND LUG OF EACH GROUNDED RECEPTACLE TO AN APPROVED CONNECTION INSIDE THE ENCLOSING STEEL OUTLET BOX. DEVICE MOUNTING SCREWS SHALL NOT BE CONSIDERED AN APPROVED GROUND. A SEPARATE GROUND CONDUCTOR SHALL BE INSTALLED IN EVERY CONDUIT AND RACEWAY AND SECURELY BONDED IN AN APPROVED GROUNDING TERMINAL AT BOTH ENDS OF THE RUN. THE GROUNDING CONDUCTOR SHALL BE SIZED IN ACCORDANCE WITH TABLE 250 -122 OF THE N.E.C. CONTRACTOR SHALL SIZE CONDUIT TO ACCOMMODATE ADDITIONAL CONDUCTOR. i 18. LOAD DATA IS BASED ON INFORMATION GIVEN TO THE ENGINEER AT THE TIME OF DESIGN. VERIFY ALL EQUIPMENT NAMEPLATE RATINGS BEFORE ORDERING. 19. CIRCUITS SHOWN ON PLANS ARE TO DETERMINE LOAD DATA AND PANEL SIZES. THE CONTRACTOR IS TO PROVIDE CIRCUITS AND ROUTING OF CONDUITS TO SUIT JOB CONDITIONS. 20. FURNISH AND INSTALL DISCONNECT SWITCHES, WIRING, AND CONNECTIONS ON AIR CONDITIONING SYSTEM AS SHOWN ON PLANS. ELECTRICAL CONTRACTOR SHALL PROVIDE CONDUIT AND WIRING FROM C.U.TO A.H.U. ,TERMINATION SHALL BE PERFORMED TRY MECHANICAL CONTRACTOR. 21. ALL FLUORESCENT LIGHT FIXTURES SHALL HAVE IN LINE FUSING AND ENERGY SAVING BALLASTS. (ONLY REQUIRED IN MIAMI DADE COUNTY) 22. ALL SWITCHGEAR, PANELS, STARTERS, CONTACTORS ETC., SHALL BE THE PRODUCT OF A SINGLE MANUFACTURER, THE SYSTEM DESIGN IS BASED ON SQUARE "D "; HOWEVER, COMPARABLE EQUIPMENT BY G.E. is SIEMENS ONLY WILL BE ACCEPTABLE. TANDEM AND HALF -SPACE CIRCUIT BREAKERS SHALL NOT BE USED. 23. PROVIDE IDENTIFICATION FOR ALL PANELS, CABINETS, ENCLOSURES, DISCONNECTS & TRANSFORMERS USING ENGRAVED NAMEPLATES, WHITE LETTERING ON A BLACK BACKGROUND. NAMEPLATES SHALL IDENTIFY PANEL DESIGNATION (NAME,) VOLTAGE, PHASE h WIRE CONFIGURATION. PROVIDE TYPEWRITTEN DIRECTORIES UNDER PLASTIC COVER FOR ALL PANEL BRANCH CIRCUITS, CLEARLY INDICATING AREA AND ME OF LOAD SERVED BY EACH BRANCH CKT PROTECTIVE DEVICE, INCLUDING SPARES. HAND PRINTED WILL NOT E ACCEPTED. 24. NGRAVED, LAMINATED PLASTIC IDENTIFICATION PLATES SHALL BE FURNISHED AND INSTALLED ON ALL PANELS AND SWITCHGEAR. PLATES SHALL BE AFFIXED TO FRONT OF PANELS, INDICATING PANEL NAME, VOLTAGE AND AMPERAGE. 25. ALL UNDERGROUND PVC CONDUIT RUNS SHALL HAVE RIGID STEEL ELBOWS AND RIGID STEEL SECTIONS AT SLAB PENETRATIONS WHERE SUBJECT TO POSSIBLE DAMAGE. WHERE RIGID STEEL IS USED, IT SHALL BE COMPLETELY COATED WITH AN ALKALI AND RUST - RESISTANT BITUMAS11C PAINT, COPPER NO. 50, AND THREADS SHALL BE COATED WITH ZINC CHROMATE, 26. THE ELECTRICAL CONTRACTOR SHALL MEET AND COORDINATE WITH THE LOCAL POWER COMPANY AT THE SITE PRIOR TO CONSTRUCTION. AT THAT TIME, THE CONTRACTOR SHALL COORDINATE ALL RELATED WORK WITH THE UTILITY COMPANY'S RESPONSIBILITIES TO MEET THE OWNER'S SCHED. 27. ALL ELECTRICAL CONDUCTORS SHALL BE INSTALLED IN AN APPROVED RACEWAY, EMT, IMC, RIGID GALVANIZED CONDUIT OR SCHEDULE 40 P.V.C. THERE SHALL BE NO TYPE 'NM', ELECTRICAL NON- METALLIC TUBING, k FLEXIBLE METAL CONDUIT USED FOR BRANCH CIRCUITING. MAXIMUM NUMBER OF 120V CIRCUITS ALLOWED IN A COMMON CONDUIT SHALL BE SIX (6). "MC" TYPE CABLE SHALL NOT BE USED AS HOME RUNS. THE CONTRACTOR SHALL STRICTLY CONFORM TO THE N.E.C. REQUIREMENTS OF DERATING FOR CONDUCTOR AMPACITY AND CONDUIT FILL 28. CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS: 209V SYSTEM 480V SYSTEM PHASE SEQUENCE NEUTRAL - WHITE NEUTRAL- WHITE /STRIPE ABC, TOP TO BOTTOM PHASE A - BLACK PHASE A - BROWN LEFT TO RIGHT, FRONT PHASE B - RED PHASE B - PURPLE TO BACK PHASE C - BLUE PHASE C - YELLOW GRD.CON - GREEN GRD.CON - GREEN 29. CONTRACTOR SHALL BE RESPONSIBLE FOR SEALING ALL CONDUIT PENETRA1ONS MADE THROUGH FIRE RATED WALLS, CEILINGS, SLABS, ETC. PENETRATION SEALS SHALL BE PER U.L ASSEMBLY STANDARDS. 30. CONTRACTOR SHALL MAINTAIN A COMPLETE SET OF CONTRACT DRAWINGS AT JOB SITE WITH COLORED MARKINGS INDICATING PROGRESS OF WORK. THIS SET OF CONTRACT DRAWINGS IS TO BE SEPARATE FROM AND IN ADDITION TO CONTRACTOR'S CONSTRUCTION SET. EVERY UNIT OF EQUIPMENT, DEVICE, CONDUIT AND WIRE IS TO MARKED WHEN INSTALLED. USE GREEN TO INDICATE INSTALLATION AS SHOWN ON DRAWINGS AND USE AM TO INDICATE FIELD CHANGES. UPON COMPLE11ON OF WORK, THIS SET OF CONTRACT DRAWINGS IS TO BE TURNED OVER TO, AND BECOME PROPERTY OF THE ELECTRICAL ENGINEER. 31. IF ELECTRICAL CONTRACTOR HAS QUESTIONS, OR IN THEIR OPINION FINDS OMISSIONS OR ERRORS ON ELECTRICAL DOCUMENTS, IT IS THEIR RESPONSIBILITY TO BRING THIS TO THE ATTENTION OF THE ELECTRICAL ENGINEER IMM ED IA TEL Y. IF ELECTRICAL CONTRACTOR R PROCEEDS WITH AU CHANGES TO THE CONTRACT DOCUMENTS, WITHOUT WRITTEN PRIOR APPROVAL FROM THE ELECTRICAL ENGINEER, CONTRACTOR WILL NOT BE COMPENSATED. RISER DIAGRAM LEGEND SYMBOL DESCRIPTION DATA ROOM I I PAN.. I I NEW LOADCENTERS - QO PANEL PANEL 'UPS' PANELBOARD - NQOD 100A ML0 MLO 277/480 PANELBOARD - NF 225A NEMA 1 REVISED SIGNED AND SEALED PLANS AND SPECIFICATIONS. (PNLS SHALL BE MTD m +60" A.F.F, U.N.D) METER MLO 0 ME,ER NETAA 3R 5' -0" TO 6' -0" A.F.G. FEED THRU BUS nrac. FUSED DISCONNECT NETAA 3R 5' -0" TO 6' -0" A.F.G. MAIN CIRCUIT BREAKER OF BATTERY CIRCUIT BREAKER BACK -UP 0 V u ® 480Y/277V 3P,4W DISCONNECT NEMA 3R u 5' -0" TO 6' -0" A.F.G. u NEMA 1 11 �111 TRANSFER SWITCH "MCE 5'--0" TO 6' -0" A.F.G. RATED uun• W •ruuu I' — ... ............ ......- - - -- - - - - - GROUND SYSTEM u TvSS TRANSIENT VOLTAGE SURGE SUPPRESSOR -TIT T INTERMATIC SEE PNL SCHEDULE FOR MD_L. _ri- CIRCUIT BREAKER LIGHTING CONTACTOR (MECHANICAL LATCH) -- - - -- - -- ----- _.._ ................... - - - - - - -- - .............._._......._..... TIME— SWITCH BY INTERMATIC Q - MDL#ET70815CR. EXISTING TO REMAIN BOLD LINES DENOTE NEW WORK OR EQUIPMENT vrNn�ATEo AS TRAN7FNtMER NEMA 1 TYPICAL 480 A 277 V TO 208Y /1120 V DRY TYPE TRANSF. NEW 3-#4, 1-0 GND, AWG THWN CU IN 1 "EMT II EXISTING NEW 3-#4, 1-0 GND, AWG THWN CU IN 1 "EMT DATA ROOM I I _— I I I NEW I I i PANEL PANEL 'UPS' 'H A' 100A r V V VV MLO 'LE' 225A UPS REVISED SIGNED AND SEALED PLANS AND SPECIFICATIONS. 12KVA NEMA 1 MLO MLO PROVIDE 45 MLO MINUTES MIN, 480Y/277V OF BATTERY LOU BACK -UP 0 V u 1007 OF 480Y/277V 3P,4W RATING 20&Y/120V -10,3W u NEMA 1 NEW 3-#4, 1-0 GND, AWG THWN CU IN 1 "EMT II EXISTING EXISTING EXISTING 'D P A' EXISTING EXISTING PANEL PANEL 1310 PANEL PANEL 'H A' 'LC' r V V VV 'LD' 'LE' 225A 225A REVISED SIGNED AND SEALED PLANS AND SPECIFICATIONS. 225A 225A MLO MLO rW• MLO MLO 480Y/277V I V•• T4 LOU • V u NEMA 1 480Y/277V 3P,4W •YC+r uy NEMA 1 u NEMA 1 u NEMA 1 r EXISTING 4 -#3/0, 1 - #1/0 GND, AWG THWN CU IN 2 "EMT EXISTING 2 SETS OF 4 - #500 Kcmil, 1 - #1/0 GND, AWG THWN CU IN *"EMT EACH SET EXISTING 3 - #500 Kcmil, 1 - #3 GND, AWG THWN CU IN "EMT VENTILATED 300 KVA TRANSFORMER 480,L V TO 208Y/120 V DRY TYPE NEMA 1 EXISTING #3/0 GND TO C.W.P k EXPOSEU BUILDING STEEL = EXISTING 4 - #4/0, EXISTING 4 - #3/0, EXISTING 3 - #4/0, 1 - #1/0 GND, AWG 1 - #1 /0 GND, AWG 1 - #4 GND, AWG THWN THWN CU IN 2 1/2 "C THWN CU IN 2 "C CU IN 2 "C EXISTING EXISTING EXISTING 400 AMP PANEL PANEL 120V/201Y 'LB' 'LA' 3 PHASE I 225A 200A 225A L MCB MCB 3400A � EXISTING NEMA 1 NEMA 1 VENTILATED NEMA 1 i 150 KVA TRANSFORMER 480,L V TO EXISTING 3 - #4/0, 208Y/120 V 1 - #4 GND, AWG THWN DRY TYPE CU W 2 "C I NEMA 1 -- ------ --- EXISTING #3/0 GND. TO C.W.P & EXPOSED BUILDING STEEL EXISTING ELECTRICAL RISER L W V4u VWV V • •uu•• VYV EXISTING 'DPB' EXISTING 'D P A' 800A Fri 1 MCB V • U LITIGATION. THE CONTRACTOR IS HEREBY NOTIFIED THAT IT IS THEIR RESPONSIBILITY FOR FINAL m 1310 i • i V u•• ri-1 • r V V VV V v u 208Y/120V 3P,4W • VV V W EXISTING 2 SETS OF 4 - #500 Kcmil, 1 - #1/0 GND, AWG THWN CU IN *"EMT EACH SET EXISTING 3 - #500 Kcmil, 1 - #3 GND, AWG THWN CU IN "EMT VENTILATED 300 KVA TRANSFORMER 480,L V TO 208Y/120 V DRY TYPE NEMA 1 EXISTING #3/0 GND TO C.W.P k EXPOSEU BUILDING STEEL = EXISTING 4 - #4/0, EXISTING 4 - #3/0, EXISTING 3 - #4/0, 1 - #1/0 GND, AWG 1 - #1 /0 GND, AWG 1 - #4 GND, AWG THWN THWN CU IN 2 1/2 "C THWN CU IN 2 "C CU IN 2 "C EXISTING EXISTING EXISTING 400 AMP PANEL PANEL 120V/201Y 'LB' 'LA' 3 PHASE I 225A 200A 225A L MCB MCB 3400A � EXISTING NEMA 1 NEMA 1 VENTILATED NEMA 1 i 150 KVA TRANSFORMER 480,L V TO EXISTING 3 - #4/0, 208Y/120 V 1 - #4 GND, AWG THWN DRY TYPE CU W 2 "C I NEMA 1 -- ------ --- EXISTING #3/0 GND. TO C.W.P & EXPOSED BUILDING STEEL EXISTING ELECTRICAL RISER L W V4u VWV V • •uu•• VYV I I I I I I SECOND LVLJ TO MAIN IN MAIN ELECTRICAL ROOM EXISTING 3 SETS OF 4- #400 KCMIL, 1 - #210 AWG GND CU THWN IN 4 "NMC I I I I I I I I GROUND LVL N.T.S. NOTES: 1. WITHIN 30 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDED TO THE BUILDING OWNER AS PER FBC 13- 413.1.ABC.2.1. 2. AN OPERATING MANUAL AND MAINTENANCE MANUAL SHALL BE PROVIDED TO THE BUILDING OWNER AS PER FBC 13- 413.1.ABC,2.2. OVERRIDE TIME SHALL BE SET AT 30 MINUTES MAX. THE BEST OF MY KNOWLEDGE, THE PLANS AND SPECIFICATIONS SUBMITTED REWITH COMPLY WITH EXISTING INTERPRETATIONS AND PROVISIONS OF THE PLICABLE BUILDING CODES. THIS DRAWING IS THE SOLE PROPERTY OF :NZ ENGINEERING INC.' AND IS AN INSTRUMENT OF SERVICE NOT TO BE PRODUCED W WHOLE OR IN PART WITHOUT THE EXPRESS WRITTEN PERMISS] HENZ ENGINEERING INC. I, THOMAS E. HENZ, P.E #34261, CERTIFY THAT I CURRENTLY HOLD AN ACTIVE LICENSE IN THE STATE OF FLORIDA AND I AM COMPETENT THROUGH EDUCATION OR EXPERIENCE TO PROVIDE ENGINEERING SERVICES IN THE ELECTRICAL DISCIPLINE CONTAINED IN THIS PLAN, I FURTHER CERTIFY THAT THIS PLAN WAS PREPARED BY ME OR UNDER MY RESPONSIBLE CHARGE AS DEFINED IN CHAPTER 61G15- 18.001 F.A.C. MOREOVER I CERTIFY THAT THE COMPANY OFFERING THE ENGINEERING SERVICES, 'HFNZ ENGINEERING INC', HOLDS AN ACTIVE CERTIFICATE OF AUTHORIZATION #3880 TO PROVIDE THE ENGINEERING SERVICE. WARNING! _ archintect EXISTING 'D P A' ELECTRICAL CHARACTERISTICS IS A MAJOR SOURCE OF CONSTRUCTION DELAYS, EXTRA COSTS AND V • U LITIGATION. THE CONTRACTOR IS HEREBY NOTIFIED THAT IT IS THEIR RESPONSIBILITY FOR FINAL • • m i • i V u•• V u • • r V V VV V v u r V • VV V W REVISED SIGNED AND SEALED PLANS AND SPECIFICATIONS. V W ELEC ROOM `"" W rW• WHERE PREPARED BY ME OR UNDER V••u VuuVU •r4 I V•• T4 LOU • V u V 480Y/277V 3P,4W •YC+r uy I u r • • u • r V • W • li r • uun• W •ruuu •V• W uu.y I u I I I I I I SECOND LVLJ TO MAIN IN MAIN ELECTRICAL ROOM EXISTING 3 SETS OF 4- #400 KCMIL, 1 - #210 AWG GND CU THWN IN 4 "NMC I I I I I I I I GROUND LVL N.T.S. NOTES: 1. WITHIN 30 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDED TO THE BUILDING OWNER AS PER FBC 13- 413.1.ABC.2.1. 2. AN OPERATING MANUAL AND MAINTENANCE MANUAL SHALL BE PROVIDED TO THE BUILDING OWNER AS PER FBC 13- 413.1.ABC,2.2. OVERRIDE TIME SHALL BE SET AT 30 MINUTES MAX. THE BEST OF MY KNOWLEDGE, THE PLANS AND SPECIFICATIONS SUBMITTED REWITH COMPLY WITH EXISTING INTERPRETATIONS AND PROVISIONS OF THE PLICABLE BUILDING CODES. THIS DRAWING IS THE SOLE PROPERTY OF :NZ ENGINEERING INC.' AND IS AN INSTRUMENT OF SERVICE NOT TO BE PRODUCED W WHOLE OR IN PART WITHOUT THE EXPRESS WRITTEN PERMISS] HENZ ENGINEERING INC. I, THOMAS E. HENZ, P.E #34261, CERTIFY THAT I CURRENTLY HOLD AN ACTIVE LICENSE IN THE STATE OF FLORIDA AND I AM COMPETENT THROUGH EDUCATION OR EXPERIENCE TO PROVIDE ENGINEERING SERVICES IN THE ELECTRICAL DISCIPLINE CONTAINED IN THIS PLAN, I FURTHER CERTIFY THAT THIS PLAN WAS PREPARED BY ME OR UNDER MY RESPONSIBLE CHARGE AS DEFINED IN CHAPTER 61G15- 18.001 F.A.C. MOREOVER I CERTIFY THAT THE COMPANY OFFERING THE ENGINEERING SERVICES, 'HFNZ ENGINEERING INC', HOLDS AN ACTIVE CERTIFICATE OF AUTHORIZATION #3880 TO PROVIDE THE ENGINEERING SERVICE. WARNING! _ archintect EXISTING 'D P A' ELECTRICAL CHARACTERISTICS IS A MAJOR SOURCE OF CONSTRUCTION DELAYS, EXTRA COSTS AND MAIN FUSE 13 200A 1000A LITIGATION. THE CONTRACTOR IS HEREBY NOTIFIED THAT IT IS THEIR RESPONSIBILITY FOR FINAL SUITE # 202 m r REQUIREMENTS FOR THE ELECTRICAL DESIGN. THE ENGINEERS' REVIEW OF SHOP DRAWINGS IS FOR THE 1;T�T) OF FLORIDA , Lr3 rr CHANGES TO EQUIPMENT AND /OR CHARACTERISTICS CANNOT BE MADE THROUGH THE SHOP DRAWING COPT' 6,14 T © 2010 LA , uN_ REVISED SIGNED AND SEALED PLANS AND SPECIFICATIONS. DATE: AS N DRAWN s` ,4S 1 CHECKED TEP I HEREBY CERTIFY THAT THESE PLANS WHERE PREPARED BY ME OR UNDER MY SUPERVISION, AND TO THE BEST OF MY KNOWLEDGE, COMPLY WITH ALL APPLICABLE CODES. LOU A R Q U I T E C T 0 S A S 0 C I A D 0 S RUT :76.575.840 -E AURELIO GONZALEZ 3330 480Y/277V 3P,4W I I I I I I SECOND LVLJ TO MAIN IN MAIN ELECTRICAL ROOM EXISTING 3 SETS OF 4- #400 KCMIL, 1 - #210 AWG GND CU THWN IN 4 "NMC I I I I I I I I GROUND LVL N.T.S. NOTES: 1. WITHIN 30 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDED TO THE BUILDING OWNER AS PER FBC 13- 413.1.ABC.2.1. 2. AN OPERATING MANUAL AND MAINTENANCE MANUAL SHALL BE PROVIDED TO THE BUILDING OWNER AS PER FBC 13- 413.1.ABC,2.2. OVERRIDE TIME SHALL BE SET AT 30 MINUTES MAX. THE BEST OF MY KNOWLEDGE, THE PLANS AND SPECIFICATIONS SUBMITTED REWITH COMPLY WITH EXISTING INTERPRETATIONS AND PROVISIONS OF THE PLICABLE BUILDING CODES. THIS DRAWING IS THE SOLE PROPERTY OF :NZ ENGINEERING INC.' AND IS AN INSTRUMENT OF SERVICE NOT TO BE PRODUCED W WHOLE OR IN PART WITHOUT THE EXPRESS WRITTEN PERMISS] HENZ ENGINEERING INC. I, THOMAS E. HENZ, P.E #34261, CERTIFY THAT I CURRENTLY HOLD AN ACTIVE LICENSE IN THE STATE OF FLORIDA AND I AM COMPETENT THROUGH EDUCATION OR EXPERIENCE TO PROVIDE ENGINEERING SERVICES IN THE ELECTRICAL DISCIPLINE CONTAINED IN THIS PLAN, I FURTHER CERTIFY THAT THIS PLAN WAS PREPARED BY ME OR UNDER MY RESPONSIBLE CHARGE AS DEFINED IN CHAPTER 61G15- 18.001 F.A.C. MOREOVER I CERTIFY THAT THE COMPANY OFFERING THE ENGINEERING SERVICES, 'HFNZ ENGINEERING INC', HOLDS AN ACTIVE CERTIFICATE OF AUTHORIZATION #3880 TO PROVIDE THE ENGINEERING SERVICE. WARNING! _ archintect MECHANICAL EQUIPMENT ORDERED AND DELIVERED TO THE CONSTRUCTION SITE WITH THE WRONG ELECTRICAL CHARACTERISTICS IS A MAJOR SOURCE OF CONSTRUCTION DELAYS, EXTRA COSTS AND THOM SF N�, P.E.., LITIGATION. THE CONTRACTOR IS HEREBY NOTIFIED THAT IT IS THEIR RESPONSIBILITY FOR FINAL SUITE # 202 COORDINATION BETWEEN TRADES TO GUARANTEE THAT ALL EQUIPMENT HAS THE CORRECT ELECTRICAL " ... t"� �ROFEfALGINEER No,342C1 REQUIREMENTS FOR THE ELECTRICAL DESIGN. THE ENGINEERS' REVIEW OF SHOP DRAWINGS IS FOR THE 1;T�T) OF FLORIDA , PURPOSE OF ATTEMPTING TO HELP THE CONTRACTOR CONFORM TO PLANS AND SPECIFICATIONS. r CHANGES TO EQUIPMENT AND /OR CHARACTERISTICS CANNOT BE MADE THROUGH THE SHOP DRAWING COPT' 6,14 T © 2010 PROCESS. CHANGES TO EQUIPMENT SPECIFICATIONS CAN ONLY BE MADE THROUGH THE ISSUANCE OF " W REVISED SIGNED AND SEALED PLANS AND SPECIFICATIONS. DATE: AS N flRZ RGlUMHG, InC. r0HSHLIIHG LnGln�tRE 2320 NE 9th Street, Suite 200 Fort Lauderdale, Florida 33304 T 954.523.4933 F 954.523.5052 www.henz.com PROJECT No.: 10012.00 NFL _ archintect NORBERTO ROSENSTEIN ARCHITECT , INC. MCHI CIff - NTM DELI - K AM= 126 S. FEDERAL HIGHWAY SUITE # 202 DANIA BEACH, FLORiP'DA 33004 PH: (954) 922 -6551 FAX= (954) 922 -7388 EMAIL -WooroseWeinuehiteetcom WEB: www,rosensteharchitectcom STATE RECs. NO. AR- 0016674 NATL. RECs. NO, 61BI70 COPT' 6,14 T © 2010 NOlq5ERTO ROWN5TEIN ARG- RTECT, INC. ALL RICsHTT5 RE5ERVED. TI-11I5 DOC'LB'ENT OR PARTS TWEWOF, MAY NOT 15E FiEPRODUCED IN ANY FORM UTI-= F'STi1II66I0N. DESIGNED AS N DRAWN s` ,4S 1 CHECKED TEP I HEREBY CERTIFY THAT THESE PLANS WHERE PREPARED BY ME OR UNDER MY SUPERVISION, AND TO THE BEST OF MY KNOWLEDGE, COMPLY WITH ALL APPLICABLE CODES. elton + leniz A R Q U I T E C T 0 S A S 0 C I A D 0 S RUT :76.575.840 -E AURELIO GONZALEZ 3330 VITACU RA 08/11/10 GEN. REVISION AS R E V I S 1 0 N S COMM. DATE 2010 -31 8/3/2010 Casaicoea,,110'. 5701 SUNSET DR. SUITE 13-10 SOUTH MIAMI FLORIDA, 33143 ELECTRICAL SPECS, RISER AND DETAILS E -5 °�