11-959-022MECHANICAL NOTES 1. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, AND EQUIPMENT NECESSARY FOR THE INSTALLATION OF A COMPLETE SYSTEM IN ACCORDANCE WITH THESE DRAWINGS, THE FLORIDA BUILDING CODE 2007 AND ALL OTHER APPLICABLE STATE, COUNTY AND LOCAL ORDINANCES AND THE LATEST EDITION OF THE FOLLOWING PUBLICATIONS; SMACNA -85, 95, 03; ASHRAE 15 -01, 34 -04, 62 -04; NFPA 70 -05, 72 -02, 9OA -02, 9OB -02, 91 -99, 96 -01, 101 -06; ANSI Z10.1 -98, Z10.3 -98, Z21.8 -94, Z21.83 -98. 2. THE CONTRACTOR SHALL PAY ALL COSTS OF PERMIT, INSPECTIONS AND ALL OTHER COSTS INCIDENTAL TO THE COMPLETION AND TESTING OF THIS WORK. 3. THE CONTRACTOR SHALL VISIT THE SITE AND COORDINATE WORK WITH OTHER TRADES. 4. THE CONTRACTOR SHALL SUPPLY THE ARCHITECT /ENGINEER WITH "AS- BUILT" DRAWINGS. 5. CONTRACTOR SHALL SUBMIT, FOR APPROVAL FIVE (5] COPIES OF A COMPLETE SET OF SHOP DWGS, MANUFACTURER'S SUBMITTALS FOR EACH PIECE OF EQUIPMENT & CONTROLS INCLUDED IN CONTRACT. 6. ALL MATERIAL SHALL BE NEW OF U.S. MANUFACTURER OF GOOD QUALITY. ALL WORK SHALL BE PERFORMED AT INDUSTRY STANDARD QUALITY LEVEL BY CERTIFIED PROFESSIONALS. ALL EQUIPMENT SHALL BE UL OR ETL LISTED. ALL INSTALLATIONS SHALL COMPLY WITH FMC 2007, CH. 3, GENERAL REGULATIONS. BUILDINGS LOCATED WITHIN 3,000 FT FROM THE OCEAN SHALL UTILIZE NON- FERROUS MATERIALS FOR ALL OUTDOOR EXPOSED SUPPORTS, STANDS, FASTENERS, ETC. 7. DUCTWORK: ALL DUCTWORK SHALL BE GALVANIZED SHEETMETAL WITH SEALED SEAMS AND JOINTS WITH EXTERNAL BLANKET INSULATION R -6 MIN. THE CONTRACTOR SHALL PROVIDE ALL SHEETMETAL DUCTWORK, HANGERS, AUX. SUPPORT STEEL, ETC., ALL FLEX DUCT SHALL BE RATED CLASS I, UL -181 LISTED WITH METALLIZED INNER AND OUTER FOIL LINERS, MIN. R -6 WITH A MAX. TOTAL LENGTH NOT TO EXCEED 5 FT. INSTALL UL LISTED FOR PLENUM, FLEXIBLE DUCTWORK ELBOW SUPPORTS AT EACH DIFFUSER, GRILLE, AND REGISTER EQUAL TO "FLEXFLOW ELBOW" AS MANUFACTURED BY "THERMAFLEX ". ALL METAL DUCTS SHALL BE FABRICATED IN ACCORDANCE WITH LATEST EDITION OF S.M.A.C.N.A. SPECIAL NOTE SMACNA DUCT PRESSURE CLASSES BASED ON OPERATING PRESSURE ARE: 1/2 ", 1 ", 2 ", 3 ", 4 6 ", AND 10 ". EACH DUCT SYSTEM SHALL BE CONSTRUCTED FOR THE SPECIFIC DUCT PRESSURE CLASS SHOWN ON PLANS. WHERE NO PRESSURE CLASS IS SPECIFIED FOR CONSTANT VOLUME SYSTEMS, 1" W.G. PRESSURE CLASS IS THE BASIS OF COMPLIANCE WITH THE SMACNA STANDARDS REGARDLESS OF VELOCITY. WHERE NO PRESSURE CLASS IS SPECIFIED FOR VARIABLE VOLUME SYSTEMS, 2" W.G. PRESSURE CLASS IS THE BASIS OF COMPLIANCE WITH THE SMACNA STANDARDS FOR DUCTWORK UPSTREAM OF VAV BOXES. ALL DUCTWORK SHALL BE SEALED TO SMACNA "HVAC DUCT CONSTRUCTION STANDARDS" FOR ITS PRESSURE CLASS SEALING METHODS. 8. ALL EXHAUST DUCTS AND OUTSIDE AIR DUCTS SHALL BE GALVANIZED SHEET METAL WITH SEALED SEAMS AND JOINTS. ALL OUTSIDE AIR DUCT SHALL BE INSULATED WITH EXTERNAL BLANKET INSULATION R -6 MIN. ALL METAL EXHAUST, MAKE -UP OR OTHERWISE DUCTS INSTALLED IN LOCATIONS WHERE DEWPOINT CONDITIONS CAN OCCUR INSIDE THE DUCT SHALL BE EXTERNALLY INSULATED WITH R -6 MIN. 9. DUCT SIZES SHOWN ARE INSIDE DIMENSIONS. 10. ALL AIR DEVICES (DIFFUSERS, REGISTERS AND GRILLES) SHALL BE ALL ALUMINUM CONSTRUCTION WITH EXPOSED SURFACE OFF WHITE BAKED ENAMEL FINISH OR AS SPECIFIED BY ARCHITECT. DEVICES SHALL BE AS SPECIFIED OR EQUAL TO TITUS OR METALAIRE. PROVIDE OPPOSED BLADE DAMPERS AT ALL DIFFUSERS AND REGISTERS AS INDICATED ON PLANS. PROVIDE BALANCING DAMPERS FOR ALL SUPPLY AND RETURN DIFFUSERS AND REGISTERS TO ENSURE COMPLIANCE WITH FMC 2007, PAR. 603.4 FOR BALANCED AIR FLOW AND WITH PAR. 601.4 FOR BALANCED RETURN TRANSFER AIR FLOW. TEMPERATURE CONTROLS /THERMOSTAT: A. FOR EXISTING EQUIPMENT: SHALL BE SERVICED AND RELOCATED AS SHOWN. IF NEW THERMOSTAT IS PROVIDED IT SHALL MATCH BUILDING STANDARDS AND SHALL BE CONNECTED TO EMS (IF ANY) 12. THERMOSTAT LOCATION SHALL BE APPROVED BY OWNER AND ENGINEER BEFORE INSTALLATION. INSTALL THERMOSTAT 48" TO 54" A.F.F. PER A.D.A REQUIREMENTS WHERE APPLICABLE. MECHANICAL CONTRACTOR SHALL COORDINATE WITH ELECTRICAL CONTRACTOR ALL REQUIREMENTS FOR JUNCTION BOXES, CONDUITS, CONTROL WIRING, POWER, ETC. AND DEFINE RESPONSIBILITIES AND SCOPE OF WORK FOR EACH TRADE PRIOR TO ANY PURCHASING OR INSTALLATION. SPECIAL NOTEt WHENEVER THERE ARE MORE THAN ONE SENSOR OR THERMOSTAT, SIDE BY SIDE, THEY SHALL BE GANGED TOGETHER WITHIN THE SAME COVER PLATE WHEREVER POSSIBLE. CONTRACTOR SHALL COORDINATE THIS ISSUE WITH ARCHITECT /OWNER PRIOR TO INSTALLATION AND SHALL BRING ANY DISCREPANCY TO THE ENGINEER'S ATTENTION. 13. ALL BRANCH TAKE -OFFS TO BE PROVIDED W/ MANUAL VOLUME DAMPERS. PROVIDE RADIUS ELBOWS WHERE FEASIBLE, SQUARE ELBOWS AND TEE'S SHALL BE FURNISHED W /SINGLE FOIL TURNING VANES. PROVIDE MANUAL VOLUME DAMPERS WITH EXTRACTOR AT ALL FLEX TAKE -OFFS. PROVIDE REMOTE, CABLE OPERATED VOLUME DAMPERS IN INACCESIBLE AND HARD CEILING AREAS, "YOUNG REGULATOR" OR EQUAL. 14. PROVIDE NEW FILTERS FOR ALL AIR CONDITIONING EQUIPMENT BEFORE START -UP, REPLACE PRIOR TO FINAL ACCEPTANCE BY OWNER. 15. PROVIDE SMOKE DETECTORS WITH SERVICE ACCESS DOORS IN ALL SUPPLY AIR DUCTS FOR FANS AND AHU'S SERVING A COMMON PLENUM OF 2000 CFM OR ABOVE. FOR SMOKE DETECTORS NOT VISIBLE, IN CONCEALED SPACES, PROVIDE REMOTE ANNUNCIATION /TEST STATION AS REQUIRED BY AUTHORITY HAVING JURISDICTION, COORDINATE PRIOR TO INSTALLATION. DETECTORS SHALL BE BY ONE MANUFACTURER, COORDINATE VOLTAGE ETC. WITH ELECTRICAL CONTRACTOR AND FIRE ALARM SYSTEM BEFORE ORDERING. UPON DETECTION, SMOKE DETECTORS SHUT DOWN ASSOCIATED AIR MOVING EQUIPMENT AND ALL AIR MOVING EQUIPMENT SERVING THAT COMMON PLENUM. SPECIAL NOTE ALL INSTALLED ELECTRICAL DEVICES, ACTUATORS, APPURTENANCES, AUXILIARY EQUIPMENT, ETC. REQUIRING ENVIRONMENTAL PROTECTION SHALL BE PROVIDED WITH ADEQUATE NEMA ENCLOSURES FOR THE CONDITIONS WHERE INSTALLED, WEATHER INDOORS OR OUTDOORS, EVEN IF NOT SPECIFICALLY INDICATED ON PLANS. 16. HVAC CONTRACTOR SHALL PROVIDE A T & B REPORT PER F.B.C. 2007, CH. 13, 410.ABC.4 (THE T & B REPORT SHALL BE INDEPENDENT FOR SYSTEMS OVER 15 TONS) FOR ALL MECHANICAL EQUIPMENT, AIR DEVICES, DAMPERS, AHU'S AND FANS. THE TEST AND BALANCE REPORT SHALL BE IN ACCORDANCE WITH THE AIR BALANCE COUNCIL STANDARDS AND SHALL INCLUDE AIR QUANTITIES FOR ALL SUPPLY GRILLES, RETURN GRILLES AND EXHAUST GRILLES AND THE LEAVING AND ENTERING AIR TEMPERATURE (F) FROM SUPPLY GRILLES AND EVAPORATORS. FOR (EXISTING) SMOKE EVACUATION SYSTEMS HVAC CONTRACTOR SHALL PROVIDE A T & B REPORT PRIOR TO ANY NEW WORK, PROVING THAT THE SMOKE EVACUATION SYSTEM PERFORMS PER ORIGINAL DESIGN DOCUMENTS AND IS COMPLIANT WITH LOCAL CODE REQUIREMENTS. SPECIAL NOTE AS PART OF BID, CONTRACTOR SHALL INCLUDE COSTS NECESSARY TO MAKE ONE CHANGE IN EACH UNITS SHEAVE, BUSHINGS AND BELTS, BALANCING DAMPERS REQUIRED AND ANY OTHER DEVICES REQUIRED FOR THE CORRECT BALANCE OF THE SYSTEM AS REQUIRED BY THE TAB FIRM. 17. ALL INSULATION WILL HAVE FIRE /SMOKE RATING LESS THAN 25/50. 18. HVAC CONTRACTOR SHALL PROVIDE VENTILATION CONTROLS COMPLIANT WITH FBC 2007, SEC. 13- 409.AB.3 FOR ALL SYSTEMS AND SHALL VERIFY EXISTING CONDITIONS FOR COMPLIANCE, AS REQUIRED, FOR A FULLY OPERATIONAL SYSTEM. 19. PROVIDE A MIN. OF 36" CLEARANCE IN FRONT OF ALL 120 -208 VOLT PANELS AND MIN. 42" CLEARANCE IN FRONT OF ANY 240 -480 VOLT PANEL. PROVIDE ADEQUATE SIDE CLEARANCE PER NEC. 20. MECHANICAL PLANS IN GENERAL, ARE DIAGRAMMATIC IN NATURE, AND ARE TO BE READ IN CONJUNCTION WITH ARCHITECTURAL, PLUMBING, ELECTRICAL, FIRE SPRINKLER, AND STRUCTURAL PLANS AND SHALL BE CONSIDERED AS ONE SET OF DOCUMENTS. DUCT AND PIPING OFFSETS, BENDS AND TRANSITIONS SHALL BE REQUIRED TO PROVIDE AND INSTALL A COMPLETE FUNCTIONAL SYSTEM AND SHALL BE PROVIDED BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER. CHANGES IN DUCTWORK SIZE AND ROUTE WILL BE REQUIRED TO AVOID STRUCTURAL, PLUMBING, FIRE SPRINKLER AND ARCHITECTURAL BUILDING FEATURES. DUCTWORK CHANGES MAY BE MADE BY CONTRACTOR USING EQUIVALENT SIZED DUCT. CONTACT ENGINEER IF DUCT AREA WILL NOT FIT. 21. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS PRIOR TO BIDDING, ORDERING, FABRICATION OR INSTALLATION OF MATERIALS OR EQUIPMENT, IN ORDER TO PROVIDE A FULLY INTEGRATED MECHANICAL AND CONTROLS SYSTEMS WITH THE EXISTING ONES. ANY DISCREPANCY BETWEEN EXISTING CONDITIONS AND PLANS, OR ADDITIONAL CLARIFICATION REQ'D SHALL BE BROUGHT TO THE ATTENTION OF ENGINEER PRIOR TO FINAL BIDDING AND WORK. 22. CONDENSATE DRAIN PIPING TO BE AS SPECIFIED PER PLUMBING PLANS, IF NOT SPECIFIED TO BE TYPE "L" COPPER OR PVC WHERE ALLOWED BY CODE WITH 1/2" ARMAFLEX INSULATION. PROVIDE APPROVED WATER LEVEL DETECTOR OR FLOAT SWITCH TO AUTOMATICALLY SHUT DOWN THE AIR COND. UNIT, AS A SECONDARY DRAIN SYSTEM TO COMPLY WITH FMC 2007, SEC. 307 SUPPLY CONDENSATE PUMP WHERE NECESSARY AS IMPOSED BY FIELD CONDITIONS OR INSTALLATION CHANGES AND PIPE TO CONDENSATE DRAIN PER PLUMBING PLANS. 23. CLEARANCE FOR MAINTENANCE, SERVICE, REPAIRS, AND REPLACEMENT FOR ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED TO COMPLY WITH FMC 2007, SEC. 306. SERVICE ACCESS PANELS FOR MECH. EQUIPMENT IN CONCEALED SPACES SHALL BE PROVIDED TO COMPLY WITH THE REQUIREMENTS OF SEC. 306. 24. MANUFACTURER'S WARRANTY: CONTRACTOR SHALL PROVIDE WARRANTY FOR A PERIOD OF (1) ONE YEAR AFTER BUILDING C.O. FOR ALL MECHANICAL SYSTEMS, DUCTWORK, CONTROLS ACCESSORIES AND ALL OTHER EQUIPMENT, PARTS AND LABOR UNDER THESE DRAWINGS AND AND SPECIFICATIONS. CONTRACTOR SHALL PROVIDE WARRANTY FOR COMPRESSORS FOR (5) FIVE YEARS. ANY REPAIRS REQUIRING SYSTEM SHUTDOWN WILL BE DONE DURING NON - OPERATIONAL PERIODS OR AS AGREED WITH OWNER. 25. IF REMODELLING AN EXISTING SPACE, THE CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID. CONTRACTOR SHALL INSPECT ALL EXISTING AND NEW COMPONENTS OF THE MECHANICAL SYSTEMS AND ENSURE THAT ALL ARE OPERATIONAL AND WORKING AS SHOWN ON THE APPROVED CD PLANS AT THE TIME OF C.O. NOTE: EXISTING AIR CONDITIONING SPACE. ENERGY CALCULATIONS NOT REQUIRED AS PER FLORIDA BUILDING CODE 2007, CHAPTER 13, ENERGY CODE, SECTION 101.5.1. HVAC DESIGN REQUIRES MECHANICAL SHEET INDEX SHAT# DE8CRPT10N - - ; _ MS01 MECHANICAL NOTES & INDEX M100 MECHANICAL PLAN M200 MECHANICAL DETAILS = - - MCA NOTE: EXISTING AIR CONDITIONING SPACE. ENERGY CALCULATIONS NOT REQUIRED AS PER FLORIDA BUILDING CODE 2007, CHAPTER 13, ENERGY CODE, SECTION 101.5.1. HVAC DESIGN REQUIRES HVAC ABBREVIATION LEGEND AFF ABOVE FINISH FLOOR CML /DZK GR GRILLE AHU AIR HANDLING UNIT MCA MINIMUM CIRCUIT AMPS (FOR WIRE SIZING) CU CONDENSING UNIT FIRE RATED ROOF / FLOOR CEILING ASSEMBLY MOCP MAXIMUM OVERCURRENT PROTECTION DEVICE AMPS EWT ENTERING WATER TEMPERATURE LWT LEAVING WATER TEMPERATURE EAG EXHAUST AIR GRILLE R/A RETURN AIR EF EXHAUST FAN RAG RETURN AIR GRILLE EXH EXHAUST 00 i 0/A OUTSIDE AIR FD FIRE DAMPER _O M/A MAKE -UP AIR E/A EXHAUST AIR WMS WIRE MESH SCREEN S/A SUPPLY AIR CG CEILING N .-.I CL1 \ Z P� BDD BACK DRAFT DAMPER NOTE: EXISTING AIR CONDITIONING SPACE. ENERGY CALCULATIONS NOT REQUIRED AS PER FLORIDA BUILDING CODE 2007, CHAPTER 13, ENERGY CODE, SECTION 101.5.1. HVAC DESIGN REQUIRES YES NO DUCT SMOKE DETECTOR (existing) • CML /DZK FIRE DAMPER(S) SCALE: • SMOKE DAMPER(S) • FIRE RATED ENCLOSURE PERMIT • FIRE RATED ROOF / FLOOR CEILING ASSEMBLY • FIRE STOPPING • SMOKE CONTROL • CONTRACTOR NOTES CONTRACTOR UIPMENTCASAND REQUIRED. CONTRACTOR SHALL VISIT THE SITE AND VERIFY EXISTING CONDITIONS PRIOR TO SUBMITTING ANY BID OR COMMENCING ANY WORK. ANY DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER. ALL INFORMATION SHOWN ON THESE PLANS WAS OBTAINED FROM ORIGINAL CONSTRUCTION DOCUMENTS, AND LIMITED FIELD OBSERVATIONS. THE ENGINEER MAKES NO REPRESENTATION FOR THE ACCURACY OF SUCH INFORMATION AND /OR ALL THE EXISTING MATERIALS, DIMENSIONS, CONDITIONS, ETC. CONTRACTOR SHALL VERIFY ALL THE SIZES AND CAPACITIES OF EXISTING DUCTWORK PRIOR TO SUBMITTING ANY BID OR COMMENCING ANY WORK. ANY DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER. ALL WORK SHALL BE DONE IN STRICT COORDINATION WITH THE RETAIL TENANT CRITERIA MANUAL. CONTRACTOR SHALL INSPECT EXISTING AHU AND ENSURE COMPLIANCE WITH TEMPERATURE CONTROLS REQUIREMENTS FROM BASE BUILDING /LANDLORD. SEE TEMPERATURE CONTROLS BULLETIN FOR DETAILS AND /OR CONTACT: ROTH BROS. INC. 800 - 872 -7684. ISSUED FOR PERMIT - ISSUED FOR CONSTRUCTION - KAMM CONSULTING PROJECT #: 2011 -0347 PROJECT MANAGER. Juan J. Bedoya 1407 West *am M Deerfield Phone 954-4 �%%N" SCEA P -"/iy,''� )oli ter Drive F1ori ; 33 , 220A �mconsul uthoriza ' 8189 __ O La AT : JOB NO.: 11025 DRAWN /CHECKED BY: CML /DZK SCALE: AS NOTED ISSUE FOR: PERMIT 09/14/11 I o 00 i o a Q Q) 4-> _O kD :3 L_ c In %-/ > O i Q -I-> _c d LL_ -0 � d i vCL (L d U 0 N .-.I CL1 \ Z P� d' m O) o (U m J O N A Q • — In � L U W Q� u H E-*_c N P U— Q� Q ry 0 o M I— /LU Q V L0 Q LU o _I d. z Li 0- ,. *_ M W _ 1(0 _I Z Z DLL Ld > LU O 5 :� t- y) _ CL Q 000 � Z Fes- W L0 wL OM4as SHEET NO: msoi TI TLE: MECHANICAL NOTES