11-959-022MECHANICAL NOTES
1. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, AND EQUIPMENT NECESSARY
FOR THE INSTALLATION OF A COMPLETE SYSTEM IN ACCORDANCE WITH THESE
DRAWINGS, THE FLORIDA BUILDING CODE 2007 AND ALL OTHER APPLICABLE STATE,
COUNTY AND LOCAL ORDINANCES AND THE LATEST EDITION OF THE FOLLOWING
PUBLICATIONS; SMACNA -85, 95, 03; ASHRAE 15 -01, 34 -04, 62 -04; NFPA 70 -05, 72 -02,
9OA -02, 9OB -02, 91 -99, 96 -01, 101 -06; ANSI Z10.1 -98, Z10.3 -98, Z21.8 -94, Z21.83 -98.
2. THE CONTRACTOR SHALL PAY ALL COSTS OF PERMIT, INSPECTIONS AND ALL OTHER
COSTS INCIDENTAL TO THE COMPLETION AND TESTING OF THIS WORK.
3. THE CONTRACTOR SHALL VISIT THE SITE AND COORDINATE WORK WITH OTHER TRADES.
4. THE CONTRACTOR SHALL SUPPLY THE ARCHITECT /ENGINEER WITH "AS- BUILT" DRAWINGS.
5. CONTRACTOR SHALL SUBMIT, FOR APPROVAL FIVE (5] COPIES OF A COMPLETE SET OF SHOP DWGS,
MANUFACTURER'S SUBMITTALS FOR EACH PIECE OF EQUIPMENT & CONTROLS INCLUDED IN CONTRACT.
6. ALL MATERIAL SHALL BE NEW OF U.S. MANUFACTURER OF GOOD QUALITY. ALL WORK SHALL
BE PERFORMED AT INDUSTRY STANDARD QUALITY LEVEL BY CERTIFIED PROFESSIONALS.
ALL EQUIPMENT SHALL BE UL OR ETL LISTED.
ALL INSTALLATIONS SHALL COMPLY WITH FMC 2007, CH. 3, GENERAL REGULATIONS.
BUILDINGS LOCATED WITHIN 3,000 FT FROM THE OCEAN SHALL UTILIZE NON- FERROUS
MATERIALS FOR ALL OUTDOOR EXPOSED SUPPORTS, STANDS, FASTENERS, ETC.
7. DUCTWORK:
ALL DUCTWORK SHALL BE GALVANIZED SHEETMETAL WITH SEALED SEAMS AND JOINTS WITH
EXTERNAL BLANKET INSULATION R -6 MIN.
THE CONTRACTOR SHALL PROVIDE ALL SHEETMETAL DUCTWORK, HANGERS, AUX. SUPPORT
STEEL, ETC., ALL FLEX DUCT SHALL BE RATED CLASS I, UL -181 LISTED WITH METALLIZED INNER
AND OUTER FOIL LINERS, MIN. R -6 WITH A MAX. TOTAL LENGTH NOT TO EXCEED 5 FT.
INSTALL UL LISTED FOR PLENUM, FLEXIBLE DUCTWORK ELBOW SUPPORTS AT EACH DIFFUSER,
GRILLE, AND REGISTER EQUAL TO "FLEXFLOW ELBOW" AS MANUFACTURED BY "THERMAFLEX ".
ALL METAL DUCTS SHALL BE FABRICATED IN ACCORDANCE WITH LATEST EDITION OF S.M.A.C.N.A.
SPECIAL NOTE
SMACNA DUCT PRESSURE CLASSES BASED ON OPERATING PRESSURE ARE: 1/2 ", 1 ", 2 ", 3 ", 4
6 ", AND 10 ". EACH DUCT SYSTEM SHALL BE CONSTRUCTED FOR THE SPECIFIC DUCT PRESSURE
CLASS SHOWN ON PLANS.
WHERE NO PRESSURE CLASS IS SPECIFIED FOR CONSTANT VOLUME SYSTEMS, 1" W.G. PRESSURE
CLASS IS THE BASIS OF COMPLIANCE WITH THE SMACNA STANDARDS REGARDLESS OF VELOCITY.
WHERE NO PRESSURE CLASS IS SPECIFIED FOR VARIABLE VOLUME SYSTEMS, 2" W.G. PRESSURE
CLASS IS THE BASIS OF COMPLIANCE WITH THE SMACNA STANDARDS FOR DUCTWORK UPSTREAM
OF VAV BOXES.
ALL DUCTWORK SHALL BE SEALED TO SMACNA "HVAC DUCT CONSTRUCTION STANDARDS" FOR
ITS PRESSURE CLASS SEALING METHODS.
8. ALL EXHAUST DUCTS AND OUTSIDE AIR DUCTS SHALL BE GALVANIZED SHEET METAL
WITH SEALED SEAMS AND JOINTS. ALL OUTSIDE AIR DUCT SHALL BE INSULATED WITH
EXTERNAL BLANKET INSULATION R -6 MIN.
ALL METAL EXHAUST, MAKE -UP OR OTHERWISE DUCTS INSTALLED IN LOCATIONS WHERE DEWPOINT
CONDITIONS CAN OCCUR INSIDE THE DUCT SHALL BE EXTERNALLY INSULATED WITH R -6 MIN.
9. DUCT SIZES SHOWN ARE INSIDE DIMENSIONS.
10. ALL AIR DEVICES (DIFFUSERS, REGISTERS AND GRILLES) SHALL BE ALL ALUMINUM
CONSTRUCTION WITH EXPOSED SURFACE OFF WHITE BAKED ENAMEL FINISH OR AS
SPECIFIED BY ARCHITECT. DEVICES SHALL BE AS SPECIFIED OR EQUAL TO TITUS OR METALAIRE.
PROVIDE OPPOSED BLADE DAMPERS AT ALL DIFFUSERS AND REGISTERS AS INDICATED ON
PLANS. PROVIDE BALANCING DAMPERS FOR ALL SUPPLY AND RETURN DIFFUSERS AND REGISTERS
TO ENSURE COMPLIANCE WITH FMC 2007, PAR. 603.4 FOR BALANCED AIR FLOW AND WITH
PAR. 601.4 FOR BALANCED RETURN TRANSFER AIR FLOW.
TEMPERATURE CONTROLS /THERMOSTAT:
A. FOR EXISTING EQUIPMENT: SHALL BE SERVICED AND RELOCATED AS SHOWN. IF NEW THERMOSTAT
IS PROVIDED IT SHALL MATCH BUILDING STANDARDS AND SHALL BE CONNECTED TO EMS (IF ANY)
12. THERMOSTAT LOCATION SHALL BE APPROVED BY OWNER AND ENGINEER BEFORE INSTALLATION.
INSTALL THERMOSTAT 48" TO 54" A.F.F. PER A.D.A REQUIREMENTS WHERE APPLICABLE.
MECHANICAL CONTRACTOR SHALL COORDINATE WITH ELECTRICAL CONTRACTOR ALL REQUIREMENTS
FOR JUNCTION BOXES, CONDUITS, CONTROL WIRING, POWER, ETC. AND DEFINE RESPONSIBILITIES
AND SCOPE OF WORK FOR EACH TRADE PRIOR TO ANY PURCHASING OR INSTALLATION.
SPECIAL NOTEt
WHENEVER THERE ARE MORE THAN ONE SENSOR OR THERMOSTAT, SIDE BY SIDE, THEY SHALL
BE GANGED TOGETHER WITHIN THE SAME COVER PLATE WHEREVER POSSIBLE.
CONTRACTOR SHALL COORDINATE THIS ISSUE WITH ARCHITECT /OWNER PRIOR TO INSTALLATION
AND SHALL BRING ANY DISCREPANCY TO THE ENGINEER'S ATTENTION.
13. ALL BRANCH TAKE -OFFS TO BE PROVIDED W/ MANUAL VOLUME DAMPERS. PROVIDE RADIUS ELBOWS
WHERE FEASIBLE, SQUARE ELBOWS AND TEE'S SHALL BE FURNISHED W /SINGLE FOIL TURNING VANES.
PROVIDE MANUAL VOLUME DAMPERS WITH EXTRACTOR AT ALL FLEX TAKE -OFFS.
PROVIDE REMOTE, CABLE OPERATED VOLUME DAMPERS IN INACCESIBLE AND HARD CEILING AREAS,
"YOUNG REGULATOR" OR EQUAL.
14. PROVIDE NEW FILTERS FOR ALL AIR CONDITIONING EQUIPMENT BEFORE START -UP,
REPLACE PRIOR TO FINAL ACCEPTANCE BY OWNER.
15. PROVIDE SMOKE DETECTORS WITH SERVICE ACCESS DOORS IN ALL SUPPLY AIR DUCTS
FOR FANS AND AHU'S SERVING A COMMON PLENUM OF 2000 CFM OR ABOVE.
FOR SMOKE DETECTORS NOT VISIBLE, IN CONCEALED SPACES, PROVIDE REMOTE ANNUNCIATION /TEST
STATION AS REQUIRED BY AUTHORITY HAVING JURISDICTION, COORDINATE PRIOR TO INSTALLATION.
DETECTORS SHALL BE BY ONE MANUFACTURER, COORDINATE VOLTAGE ETC. WITH
ELECTRICAL CONTRACTOR AND FIRE ALARM SYSTEM BEFORE ORDERING. UPON
DETECTION, SMOKE DETECTORS SHUT DOWN ASSOCIATED AIR MOVING EQUIPMENT AND
ALL AIR MOVING EQUIPMENT SERVING THAT COMMON PLENUM.
SPECIAL NOTE
ALL INSTALLED ELECTRICAL DEVICES, ACTUATORS, APPURTENANCES, AUXILIARY EQUIPMENT, ETC.
REQUIRING ENVIRONMENTAL PROTECTION SHALL BE PROVIDED WITH ADEQUATE NEMA
ENCLOSURES FOR THE CONDITIONS WHERE INSTALLED, WEATHER INDOORS OR OUTDOORS, EVEN
IF NOT SPECIFICALLY INDICATED ON PLANS.
16. HVAC CONTRACTOR SHALL PROVIDE A T & B REPORT PER F.B.C. 2007, CH. 13, 410.ABC.4
(THE T & B REPORT SHALL BE INDEPENDENT FOR SYSTEMS OVER 15 TONS)
FOR ALL MECHANICAL EQUIPMENT, AIR DEVICES, DAMPERS, AHU'S AND FANS.
THE TEST AND BALANCE REPORT SHALL BE IN ACCORDANCE WITH THE AIR BALANCE COUNCIL
STANDARDS AND SHALL INCLUDE AIR QUANTITIES FOR ALL SUPPLY GRILLES, RETURN GRILLES
AND EXHAUST GRILLES AND THE LEAVING AND ENTERING AIR TEMPERATURE (F) FROM
SUPPLY GRILLES AND EVAPORATORS.
FOR (EXISTING) SMOKE EVACUATION SYSTEMS HVAC CONTRACTOR SHALL PROVIDE A T & B
REPORT PRIOR TO ANY NEW WORK, PROVING THAT THE SMOKE EVACUATION SYSTEM PERFORMS
PER ORIGINAL DESIGN DOCUMENTS AND IS COMPLIANT WITH LOCAL CODE REQUIREMENTS.
SPECIAL NOTE
AS PART OF BID, CONTRACTOR SHALL INCLUDE COSTS NECESSARY TO MAKE ONE CHANGE IN EACH UNITS SHEAVE,
BUSHINGS AND BELTS, BALANCING DAMPERS REQUIRED AND ANY OTHER DEVICES REQUIRED FOR THE CORRECT
BALANCE OF THE SYSTEM AS REQUIRED BY THE TAB FIRM.
17. ALL INSULATION WILL HAVE FIRE /SMOKE RATING LESS THAN 25/50.
18. HVAC CONTRACTOR SHALL PROVIDE VENTILATION CONTROLS COMPLIANT WITH FBC 2007,
SEC. 13- 409.AB.3 FOR ALL SYSTEMS AND SHALL VERIFY EXISTING CONDITIONS FOR COMPLIANCE,
AS REQUIRED, FOR A FULLY OPERATIONAL SYSTEM.
19. PROVIDE A MIN. OF 36" CLEARANCE IN FRONT OF ALL 120 -208 VOLT PANELS AND MIN. 42"
CLEARANCE IN FRONT OF ANY 240 -480 VOLT PANEL. PROVIDE ADEQUATE SIDE CLEARANCE
PER NEC.
20. MECHANICAL PLANS IN GENERAL, ARE DIAGRAMMATIC IN NATURE, AND ARE TO BE READ
IN CONJUNCTION WITH ARCHITECTURAL, PLUMBING, ELECTRICAL, FIRE SPRINKLER, AND
STRUCTURAL PLANS AND SHALL BE CONSIDERED AS ONE SET OF DOCUMENTS.
DUCT AND PIPING OFFSETS, BENDS AND TRANSITIONS SHALL BE REQUIRED TO PROVIDE AND
INSTALL A COMPLETE FUNCTIONAL SYSTEM AND SHALL BE PROVIDED BY THE CONTRACTOR
AT NO ADDITIONAL COST TO THE OWNER. CHANGES IN DUCTWORK SIZE AND ROUTE
WILL BE REQUIRED TO AVOID STRUCTURAL, PLUMBING, FIRE SPRINKLER AND ARCHITECTURAL
BUILDING FEATURES. DUCTWORK CHANGES MAY BE MADE BY CONTRACTOR USING
EQUIVALENT SIZED DUCT. CONTACT ENGINEER IF DUCT AREA WILL NOT FIT.
21. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS PRIOR TO BIDDING, ORDERING,
FABRICATION OR INSTALLATION OF MATERIALS OR EQUIPMENT, IN ORDER TO PROVIDE
A FULLY INTEGRATED MECHANICAL AND CONTROLS SYSTEMS WITH THE EXISTING ONES.
ANY DISCREPANCY BETWEEN EXISTING CONDITIONS AND PLANS, OR ADDITIONAL CLARIFICATION REQ'D
SHALL BE BROUGHT TO THE ATTENTION OF ENGINEER PRIOR TO FINAL BIDDING AND WORK.
22. CONDENSATE DRAIN PIPING TO BE AS SPECIFIED PER PLUMBING PLANS, IF NOT SPECIFIED
TO BE TYPE "L" COPPER OR PVC WHERE ALLOWED BY CODE WITH 1/2" ARMAFLEX INSULATION.
PROVIDE APPROVED WATER LEVEL DETECTOR OR FLOAT SWITCH TO AUTOMATICALLY SHUT DOWN
THE AIR COND. UNIT, AS A SECONDARY DRAIN SYSTEM TO COMPLY WITH FMC 2007, SEC. 307
SUPPLY CONDENSATE PUMP WHERE NECESSARY AS IMPOSED BY FIELD CONDITIONS OR INSTALLATION
CHANGES AND PIPE TO CONDENSATE DRAIN PER PLUMBING PLANS.
23. CLEARANCE FOR MAINTENANCE, SERVICE, REPAIRS, AND REPLACEMENT FOR ALL MECHANICAL
EQUIPMENT SHALL BE PROVIDED TO COMPLY WITH FMC 2007, SEC. 306. SERVICE ACCESS
PANELS FOR MECH. EQUIPMENT IN CONCEALED SPACES SHALL BE PROVIDED TO COMPLY WITH
THE REQUIREMENTS OF SEC. 306.
24. MANUFACTURER'S WARRANTY: CONTRACTOR SHALL PROVIDE WARRANTY FOR A PERIOD OF
(1) ONE YEAR AFTER BUILDING C.O. FOR ALL MECHANICAL SYSTEMS, DUCTWORK, CONTROLS
ACCESSORIES AND ALL OTHER EQUIPMENT, PARTS AND LABOR UNDER THESE DRAWINGS AND
AND SPECIFICATIONS. CONTRACTOR SHALL PROVIDE WARRANTY FOR COMPRESSORS FOR
(5) FIVE YEARS. ANY REPAIRS REQUIRING SYSTEM SHUTDOWN WILL BE DONE DURING
NON - OPERATIONAL PERIODS OR AS AGREED WITH OWNER.
25. IF REMODELLING AN EXISTING SPACE, THE CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID.
CONTRACTOR SHALL INSPECT ALL EXISTING AND NEW COMPONENTS OF THE MECHANICAL SYSTEMS
AND ENSURE THAT ALL ARE OPERATIONAL AND WORKING AS SHOWN ON THE APPROVED CD PLANS
AT THE TIME OF C.O.
NOTE:
EXISTING AIR CONDITIONING SPACE.
ENERGY CALCULATIONS NOT REQUIRED
AS PER FLORIDA BUILDING CODE 2007,
CHAPTER 13, ENERGY CODE, SECTION
101.5.1.
HVAC DESIGN REQUIRES
MECHANICAL SHEET INDEX
SHAT#
DE8CRPT10N - - ; _
MS01
MECHANICAL NOTES & INDEX
M100
MECHANICAL PLAN
M200
MECHANICAL DETAILS = - -
MCA
NOTE:
EXISTING AIR CONDITIONING SPACE.
ENERGY CALCULATIONS NOT REQUIRED
AS PER FLORIDA BUILDING CODE 2007,
CHAPTER 13, ENERGY CODE, SECTION
101.5.1.
HVAC DESIGN REQUIRES
HVAC
ABBREVIATION LEGEND
AFF
ABOVE FINISH FLOOR
CML /DZK
GR
GRILLE
AHU
AIR HANDLING UNIT
MCA
MINIMUM CIRCUIT AMPS (FOR WIRE SIZING)
CU
CONDENSING UNIT
FIRE RATED ROOF / FLOOR CEILING ASSEMBLY
MOCP
MAXIMUM OVERCURRENT PROTECTION DEVICE AMPS
EWT
ENTERING WATER TEMPERATURE
LWT
LEAVING WATER TEMPERATURE
EAG
EXHAUST AIR GRILLE
R/A
RETURN AIR
EF
EXHAUST FAN
RAG
RETURN AIR GRILLE
EXH
EXHAUST
00
i
0/A
OUTSIDE AIR
FD
FIRE DAMPER
_O
M/A
MAKE -UP AIR
E/A
EXHAUST AIR
WMS
WIRE MESH SCREEN
S/A
SUPPLY AIR
CG
CEILING
N
.-.I
CL1
\ Z P�
BDD
BACK DRAFT DAMPER
NOTE:
EXISTING AIR CONDITIONING SPACE.
ENERGY CALCULATIONS NOT REQUIRED
AS PER FLORIDA BUILDING CODE 2007,
CHAPTER 13, ENERGY CODE, SECTION
101.5.1.
HVAC DESIGN REQUIRES
YES
NO
DUCT SMOKE DETECTOR (existing)
•
CML /DZK
FIRE DAMPER(S)
SCALE:
•
SMOKE DAMPER(S)
•
FIRE RATED ENCLOSURE
PERMIT
•
FIRE RATED ROOF / FLOOR CEILING ASSEMBLY
•
FIRE STOPPING
•
SMOKE CONTROL
•
CONTRACTOR NOTES
CONTRACTOR UIPMENTCASAND
REQUIRED.
CONTRACTOR SHALL VISIT THE SITE AND
VERIFY EXISTING CONDITIONS PRIOR
TO SUBMITTING ANY BID OR COMMENCING
ANY WORK. ANY DISCREPANCIES SHALL
BE BROUGHT TO THE ATTENTION OF
THE ENGINEER.
ALL INFORMATION SHOWN ON THESE PLANS WAS
OBTAINED FROM ORIGINAL CONSTRUCTION DOCUMENTS,
AND LIMITED FIELD OBSERVATIONS. THE ENGINEER
MAKES NO REPRESENTATION FOR THE ACCURACY OF
SUCH INFORMATION AND /OR ALL THE EXISTING
MATERIALS, DIMENSIONS, CONDITIONS, ETC.
CONTRACTOR SHALL VERIFY ALL THE SIZES
AND CAPACITIES OF EXISTING DUCTWORK
PRIOR TO SUBMITTING ANY BID OR
COMMENCING ANY WORK. ANY DISCREPANCIES
SHALL BE BROUGHT TO THE ATTENTION OF
THE ENGINEER.
ALL WORK SHALL BE DONE IN STRICT COORDINATION
WITH THE RETAIL TENANT CRITERIA MANUAL.
CONTRACTOR SHALL INSPECT EXISTING AHU AND
ENSURE COMPLIANCE WITH TEMPERATURE CONTROLS
REQUIREMENTS FROM BASE BUILDING /LANDLORD. SEE
TEMPERATURE CONTROLS BULLETIN FOR DETAILS
AND /OR CONTACT: ROTH BROS. INC.
800 - 872 -7684.
ISSUED FOR PERMIT -
ISSUED FOR CONSTRUCTION -
KAMM CONSULTING PROJECT #: 2011 -0347
PROJECT MANAGER. Juan J. Bedoya
1407 West
*am M
Deerfield
Phone 954-4
�%%N" SCEA P -"/iy,''�
)oli ter Drive
F1ori ;
33
, 220A
�mconsul
uthoriza ' 8189 __
O La AT :
JOB NO.:
11025
DRAWN /CHECKED BY:
CML /DZK
SCALE:
AS NOTED
ISSUE FOR:
PERMIT
09/14/11
I
o
00
i
o
a
Q
Q)
4->
_O
kD
:3 L_
c
In
%-/
> O
i Q -I->
_c
d
LL_
-0 �
d i
vCL
(L d
U
0
N
.-.I
CL1
\ Z P�
d'
m
O) o
(U
m
J O
N
A
Q • —
In
�
L
U
W Q�
u
H
E-*_c
N
P
U—
Q�
Q
ry
0
o M
I— /LU
Q V L0
Q LU
o _I
d.
z
Li 0- ,.
*_
M
W _
1(0
_I
Z Z DLL
Ld
>
LU
O
5 :�
t- y)
_
CL
Q 000
�
Z
Fes- W L0
wL OM4as
SHEET NO:
msoi
TI TLE:
MECHANICAL
NOTES