11-516-040Ll <o t2 w- N n 0 M N ti GENERAL NOTES 1. CONTRACTORS SHALL FAMILIARIZE THEMSELVES WITH MECHANICAL AND PLUMBING DRAWINGS AND SPECIFICATIONS. NEITHER THE DRAWINGS NOR THE SPECIFICATIONS SHALL BE COMPLETE WITHOUT THE OTHER. 2. PRIOR TO FINAL BID, THE PLUMBING CONTRACTOR SHALL VISIT THE SPACE AND FIELD VERIFY THE LOCATIONS OF ALL EXISTING PIPING TO REMAIN, UTILITY STUB -INS, ETC., FOR MECHANICAL AND PLUMBING SYSTEMS WITHIN THE SPACE.. ALL TAP FEES, IMPACT FEES AND PUBLIC ASSESSMENT FEES SHALL BE INCLUDED IN THIS CONTRACTORS PRICE. 3. PLUMBING CONTRACTOR IS RESPONSIBLE FOR CONFORMANCE TO ALL LOCAL CODES AND HEALTH DEPARTMENT REGULATIONS. PROVIDE CLEARANCE FOR CLEANING BEHIND AND UNDER EXPOSED PIPING AS REQUIRED BY HEALTH DEPARTMENT. CONFORM TO HEALTH DEPARTMENT REQUIREMENTS FOR LOCATIONS OF FLOOR SINKS AND FLOOR DRAINS. ENTIRE INSTALLATION SHALL BE IN ACCORDANCE WITH BUILDING CODE, STATE AND /OR LOCAL HEALTH AUTHORITIES. 4. PLUMBING CONTRACTOR SHALL VERIFY ALL EQUIPMENT ROUGH -INS AND DETERMINE THE MOST FEASIBLE AND ECONOMICAL LOCATION TO INSTALL THE NEW WASTE LINES BELOW THE EXISTING SW, BASED ON CURRENT PLUMBING CONDITIONS. ROUGH -INS SHOWN ARE FOR EQUIPMENT ITEMS SUPPLIED BY KITCHEN EQUIPMENT VENDOR. ALL EQUIPMENT SUPPLIED BY OTHERS MUST BE VERIFIED BY THE RESPECTIVE TRADES, UNLESS OTHERWISE NOTED INDIVIDUALLY. PROVIDE SHUT --OFF VALVES TO EACH PLUMBING FIXTURE AND WHERE NOTED ON PLANS. FOR EQUIPMENT SCHEDULE, SEE DRAWING P400. FOR PLUMBING FIXTURE SCHEDULE, SEE DRAWING P400. 5. PLUMBING CONTRACTOR SHALL BE RESPONSIBLE FOR ALL FINAL CONNECTIONS TO THE BASE BUILDING SYSTEMS. 6. ALL ROOF PENETRATIONS, PATCHING AND FLASHING SHALL BE BY THE ROOFING CONTRACTOR AT THE EXPENSE OF THE PLUMBING CONTRACTOR. 7. ALL FLOOR SINKS SHALL BE 12" X 12" WITH STRAINER UNLESS OTHERWISE NOTED. ALL FLOOR DRAINS /SINKS SHALL HAVE P -TRAPS EVEN IF NOT VISIBLE ON DRAWING. REFER TO ARCHITECTURAL DRAWINGS FOR DIMENSIONED LOCATIONS OF FLOOR DRAIN /SINK AND TRENCH DRAINS. S. ALL DIMENSIONS ARE FROM FINISHED WALLS AND /OR COLUMN CENTERLINES. FLOOR DIMENSIONS: "AFF (ABOVE FINISHED FLOOR)" ARE TO THE CENTERLINE OF THE ROUGH -IN. 9. ALL WATER LINES SHALL HAVE AN ACCESSIBLE SHUT OFF VALVE AT EACH CONNECTION POINT. 10. PLUMBING CONTRACTOR SHALL INSTALL NEW HAND SINKS, MOP SINKS, AND HOSE 0111S WITH MIXING VALVES AND VACUUM BREAKERS. 11. ALL SANITARY VENTS SHALL BE 1 1/2" UNLESS OTHERWISE NOTED. FLAT VENTING IS NOT ALLOWED. 12. ALL PLUMBING MATERIALS AND LABOR NECESSARY TO PERFORM COMPLETE CONNECTION OF EQUIPMENT SHALL BE PROVIDED BY PLUMBING CONTRACTOR. 13. STORM WATER PIPING TO BE INSULATED WITH FIBERGLASS INSULATION WITH CONTINUOUS VAPOR BARRIER. 14. PLUMBING CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT ANY CONFLICTS TO THE ARCHITECT /ENGINEER PRIOR TO THE START OF WORK. 15. PROVIDE PIPE BRACING FOR INDIRECT WASTE PIPING. BRACE PIPING FROM EQUIPMENT OR BACK WALL TO PREVENT MOVEMENT OR DAMAGE. PLUMBING CONTRACTOR TO INSTALL INDIRECT WASTE PIPING FROM EQUIPMENT TO DRAIN RECEPTOR BELOW. TERMINATE WITH CODE APPROVED AIR -GAP. VERIFY INDIRECT WASTE FOR ALL EQUIPMENT, REFERENCE KITCHEN PLANS FOR SIZING. 16. DRAIN LINES TO BE INSIDE OF WALLS, SURFACE MOUNTED WORK IS NOT ACCEPTABLE. KEY NOTES FLOOR DRAIN /FLOOR SINK REFER TO ARCHITECTURAL SHEETS FOR DIMENSIONED LOCATIONS. PROVIDE TRAP PRIMING FOR EACH. SEE SHEET P200 FOR TRAP PRIMER LOCATION. ALL FLOOR DRAINS /SINKS SHALL ICI INSTALLED SUCH THAT THE TOP ISFLUSH WITH FINISHED FLOOR. OPROVIDE FLOOR SINK FOR COCKTAIL /BLENDER STATION EQUIPMENT. BRING DRAIN PIPES TO FLOOR SINK. KITCHEN EQUIPMENT VENDOR SHALL PROVIDE SINK AND EQUIPMENT. SEE DETAIL 6 /P101 FOR TYPICAL INSTALLATION. OPROVIDE 6" PVC ELECTRICAL TYPE CONDUIT SWEEP FOR POP LINES TO BE TRENCHED UNDERGROUND. REFER TO ARCHITECTURAL DRAWINGS FOR DIMENSIONED CHASE LOCATIONS. COORDINATE WITH OTHER UNDERGROUND PIPING AND EQUIPMENT. 4 TRAP PRIMER: LOCATE TRAP PRIMER PIPING TO NEW FLOOR DRAIN /SINK BELOW SLAB. 5 RELOCATE EXISTING HAND SINK AND FAUCET. VERIFY IN GOOD CONDITION. REPAIR AS NEEDED. RELOCATE, REFURBISH TO 'LIKE -NEW' CONDITION AND REINSTALL EXISTING DISHWASHER IN ACCORDANCE WITH MANUFACTURERS INSTALLATION INSTRUCTIONS. SANITIZE UNIT IN ACCORDANCE WITH LOCAL CODES. O7 VERIFY EXISTING WATER HEATERS ARE IN GOOD WORKING ORDER. CONTRACTOR SHALL REFURBISH AND/QR REPLACE BURNERS, IGNITORS AND T&P VALVE. FLUSH AND SANITIZE UNITS IN ACCORDANCE WITH LOCAL CODE REQUIREMENTS. OEXISTING RESTROOM FIXTURES TO REMAIN. CONTRACTOR SHALL VERIFY THAT THEY ARE IN GOOD CONDITION. OEXISTING GREASE WASTE PIPING TO REMAIN. CONTRACTOR SHALL TEMPORARILY SEAL EXISTING FLOOR SINKS AND FIXTURES AND JET WASTE SYSTEM PRIOR TO INSTALLATION OF NEW FIXTURES. NOTIFY GENERAL CONTRACTOR IMMEDIATELY IF OBSTRUCTIONS EXIST OR IF PIPING IS DETERMINED TO BE DAMAGED. 10 EXISTING KITCHEN FIXTURES /EQUIPMENT TO REMAIN. CONTRACTOR SHALL VERIFY FAUCETS, WATER AND WASTE PIPING TO EACH ARE IN GOOD CONDITION. SANITIZE IN ACCORDANCE WITH LOCAL REQUIREMENTS. 11 CONTRACTOR SHALL VERIFY EXISTING WASTE PIPE INVERT AND ELEVATION PRIOR TO PERFORMING WORK. NOTIFY GENERAL CONTRACTOR IMMEDIATELY IF ELEVATION TOO SHALLOW FOR BAR WASTE PIPING CONNECTION. 12 EXISTING WALK -IN COOLER CONDENSATE PIPING SHALL REMAIN. CONTRACTOR TO JET LINES AND REPAIR AS NECESSARY FOR PROPER OPERATION. 13 EXISTING MOPSINK BASIN TO REMAIN. REFER TO ARCHITECTURAL SHEETS FOR ADDITIONAL INFORMATION. VERIFY FAUCET AND DRAIN ARE IN GOOD OPERATING CONDITION. 14 CLEANOUT (CO) CONTRACTOR SHALL PROVIDE FULL SIZE CLEANOUT. <a> PLUMBING CONTRACTOR SHALL INSTALL COPPER CONDENSATE PIPE. FIELD - VERIFY EXACT LOCATION OF EVAPORATORS. HOLD CONDENSATE PIPE TIGHT TO DRIP PAN AND ROUTE COOLER WALL AS HIGH AS POSSIBLE. SLOPE 1/4" PER FOOT. CONDENSATE LINE SH DRAIN TO FLOOR SINK WHERE SHOWN. PROVIDE FLOOR SUPPORT AT FLOOR SINK. CONDENSATE PIPE HEAT TRACING AND POWER BY ELECTRICAL CONTRACTOR. CONDEN PIPE INSULATION BY PLUMBING CONTRACTOR. SEE DETAIL 18/P101. SYMBOL LIST ABBREVIATIONS FD FLOOR DRAIN FS FLOOR SINK FCO FLOOR CLEAN -OUT WCO WALL CLEAN -OUT VTR VENT THROUGH ROOF IND. W. INDIRECT WASTE WH WALL HYDRANT PIPE SIZES SHOWN ON SHEET P300 REFER TO P400 FOR PLUMBING FIXTURE AND MECHANICAL EQUIPMENT SCHEDULE �I �I TO EXISTING FC 0 2'' � I i wco „ I SCALE 11,V-V-0" MALL GW ��DD 22 I� DIPPERWELLLL ..III 1 IN /� 3 "FS �'% 3" FTT - 1 KITCHEN � FlNw„ 3 Im 1 109 1 1/2" a. "4 DISHWASHER 6 PICK UP I \ 108 I -cw - v 0, 3" - �4 \ _ 1D ►NITARY WASTE AND VENT PLAT 0 4- B' 16' ua: SCALE BASED ON A 30 "x42" SHEET SIZE CD n LEGEND W SANITARY WASTE t- :S I _ YV i1V RWL RAINWATER LEADER UNDERGROUND GW GREASE WASTE s „ C ,BLEES RAINWATER LEADER 1• U V V N u 4 • Y• PATRICK G. BLEES, ARCHITECT ��..` —V— — VENT © GAS METER " PHOttL (512 335 -5677 SCHEDULE 40 FAX: (s1) 333 -2995 _ PVC PIPING Q WATER METER CW COLD WATER PIPING (CW) JAMES H. ART, P.E. TIE INTO EXISTING HW HOT WATER PIPING b BALANCING GLOBE VALVE NEW BRIGHTON, MN 55112 110-F (HW) PHONE: (651) 632-2300 ' FAX: (651) 632 -2397 ' GATE VALVE HOT WATER PIPING 160'HW 160 -F (160-HW) Csl RECALCULATING PUMP HOT WATER PIPING RHW RECIRC (HWR) fzl REDUCED PRESSURE BACKFLOW PREVENTER G GAS MIXING VALVE FLOOR SINK CD CONDENSATE LINE FLOOR DRAIN — --°- TP — — TRAP PRIMER LINE E, BALL VALVE �I �I TO EXISTING FC 0 2'' � I i wco „ I SCALE 11,V-V-0" MALL GW ��DD 22 I� DIPPERWELLLL ..III 1 IN /� 3 "FS �'% 3" FTT - 1 KITCHEN � FlNw„ 3 Im 1 109 1 1/2" a. "4 DISHWASHER 6 PICK UP I \ 108 I -cw - v 0, 3" - �4 \ _ 1D ►NITARY WASTE AND VENT PLAT 0 4- B' 16' ua: SCALE BASED ON A 30 "x42" SHEET SIZE CD n 11 FWH- ((11) •• • • t- :S I _ YV i1V �I 0 rI� vu P�-��r�1cK 11 FWH- ((11) i i _ 1 SEAL: ,,1 `•1.1•••1••1• • �t�I No 631fi w • p';• STATE IDS �:�w 10 ��'AtiiafrN� I HEREBY CERTIFY THAT THE PORTION OF THIS TECHNICAL SUBMISSION DESCRIII BELOW WAS PREPARED BY ME OR UNDER MY DIRECT SUPERVISION AND RESPONSIBLE CHARGE. I AM A DULY REGISTERED ENGINEER UNDER THE LAWS OF THE STATE' FLORIDA. JAMES H. :ART MAY 20, 2011 DATE ISSUED 63167 REG. NO. CONSTRUCTION DEPARTMENT 5500 WAYZATA BLVD., STE 1500 MINNEAPOLIS. MN 55416 RHONE (552) 5S3 -9543 FAX (952) 593 -9797 EDMOND FARRAN THE SHOPS AT SUNSET PLACE 5701 SUNSET DRIVE,, #1313A SOUTH MIAMI. FL . 3143 FRANCHISEE- SETH DEKANTER EMAIL ssthdskChatmsll.com FRANCHISE STORE SHEET TITLE: STORM AND SANITARY WASTE AND VENT PLAN PERMIT" SET REVISIONS: NO: DATE: BY- __. - -- _ k: I, .. r PROJECT N0: 11136.001 DRAWN BY: MIS p 10 0 5770.11 COPYRIGHT PATRICK G. BLEES, AIA 2011 •• • • t- :S I _ YV i1V rI� vu P�-��r�1cK . s „ C ,BLEES . 1• U V V N u 4 • Y• PATRICK G. BLEES, ARCHITECT ��..` VVV•Y •VV 4Nl.v 2' N 2.Nb Sr., SUITE 301 �MINNEAFPLIS, N' 55401 �•NN" " PHOttL (512 335 -5677 FAX: (s1) 333 -2995 E —MAIL: Info0cmarch.com CONSULTANTS: JAMES H. ART, P.E. 305 2ND ST NW, SUITE 105 NEW BRIGHTON, MN 55112 PHONE: (651) 632-2300 ' FAX: (651) 632 -2397 ' i i _ 1 SEAL: ,,1 `•1.1•••1••1• • �t�I No 631fi w • p';• STATE IDS �:�w 10 ��'AtiiafrN� I HEREBY CERTIFY THAT THE PORTION OF THIS TECHNICAL SUBMISSION DESCRIII BELOW WAS PREPARED BY ME OR UNDER MY DIRECT SUPERVISION AND RESPONSIBLE CHARGE. I AM A DULY REGISTERED ENGINEER UNDER THE LAWS OF THE STATE' FLORIDA. JAMES H. :ART MAY 20, 2011 DATE ISSUED 63167 REG. NO. CONSTRUCTION DEPARTMENT 5500 WAYZATA BLVD., STE 1500 MINNEAPOLIS. MN 55416 RHONE (552) 5S3 -9543 FAX (952) 593 -9797 EDMOND FARRAN THE SHOPS AT SUNSET PLACE 5701 SUNSET DRIVE,, #1313A SOUTH MIAMI. FL . 3143 FRANCHISEE- SETH DEKANTER EMAIL ssthdskChatmsll.com FRANCHISE STORE SHEET TITLE: STORM AND SANITARY WASTE AND VENT PLAN PERMIT" SET REVISIONS: NO: DATE: BY- __. - -- _ k: I, .. r PROJECT N0: 11136.001 DRAWN BY: MIS p 10 0 5770.11 COPYRIGHT PATRICK G. BLEES, AIA 2011