11-516-025a 1i'm to M N f` O N KEY NOTES OSM!2KE DETECTOR: PROVIDE SMOKE DETECTOR IN AIR HANDLING UNIT SUPPLY AIR STREAM. INTERLOCK AIR HANDLING UNIT WITH THE DETECTOR. AIR HANDLING UNIT SHALL DEACTIVATE ON DETECTION OF SMOKE. PROVIDE AN AUDIBLE/VISUAL ALARM DEVICE AND KEYED TESTING STATION IN MONITORED AREA, PER LOCAL CODE. TIE THE SMOKE DETECTOR INTO THE FIRE ALARM SYSTEM AS REQUIRED. SEE ELECTRICAL DRAWINGS FOR LOCATIONS. OPROVIDE 1" THICK ACOUSTICAL LINING IN RETURN AIR DUCTWORK AND 1/2 "x1/2" WIRE MESH COVERING AT OPENINGS ON SIDES OF RETURN AIR DUCTWORK. EACH OPENING SHALL HAVE AN AREA EQUAL TO THE CROSS SECTIONAL AREA OF THE RETURN DUCTWORK. O EXIOINQ AIR HANQUNQ UNIT, THERMOSTAT, REMOTE SENSOR, AND CO2 SENSOR. PROVIDE STRUCTURAL SUPPORT AS REQUIRED FOR NEW ROOFTOP UNIT, DISCONNECT SHALL BE PROVIDED BY THE EQUIPMENT SUPPLIER. COORDINATE GFI CONVENIENCE OUTLET WITH ELECTRICAL. ROUTE RTU CONDENSATE DRAIN TO NEAREST ROOF DRAIN OR SPLASH BLOCK. VERIFY IN FIELD. SEE SHEET M102 FOR DETAILS. OREMOTE TEMPERATURE SENSOR: PROVIDE A REMOTE SENSOR FOR THE THERMOSTAT. MOUNT 48" AFF WHERE SHOWN ON PLANS OR AS DIRECTED BY ARCHITECT. COORDINATE SENSOR LOCATION WITH WALL COVERINGS AND EQUIPMENT. PROVIDE WIRING THROUGH THE THERMOSTAT AS REQUIRED FOR CONTROL OF THE UNIT. OKITCHEN HOOD ,SYSTEMv CONTRACTOR SHALL INSTALL OWNER- FURNISHED CAPTIVEAIRE KITCHEN HOOD FROM BWW VENDOR. THE PACKAGE INCLUDES STAINLESS STEEL EXHAUST HOOD WITH FIRE CABINET, GREASE FILTERS, GREASE CATCH PAN ON THE ROOF, WIRE WAYS WITH SWITCHES, INCANDESCENT LIGHT FIXTURE RATED FOR EXHAUST HOODS, FULL ANSUL FIRE SUPPRESSION SYSTEM WITH TANKS, AND AUTOMATIC TEMPERATURE BASED ACTIVATION SYSTEM. MECHANICAL CONTRACTOR IS RESPONSIBLE FOR THE INSTALLATION OF A STAINLESS STEEL BACK SPLASH AT EACH KITCHEN HOOD. REFER TO SHEETS M200 -M201 FOR ADDITIONAL INFORMATION. KITCHEN HOOD ANSUL SYSTEM: WET TYPE CHEMICAL FIRE EXTINGUISHING SYSTEM SHALL BE IN COMPLETE CONFORMANCE WITH NFPA 96. SYSTEM SHALL BE CONTAINED IN A REMOVABLE STAINLESS STEEL COMPARTMENT LOCATED ON THE END OF KITCHEN HOOD. LIGHT SWITCH TO BE LOCATED ON FACE OF SYSTEM COMPARTMENT. (MODIFIED AND TESTED BY ANSUL SYSTEM CONTRACTOR). OCARBON DIOXIDE SENSOR: CO2 SENSOR SHALL CONTROL THE MINIMUM OUTSIDE AIR QUANTITY. CONTROLLER SHALL MODULATE OUTSIDE AIR TO MAINTAIN 700 PPM DIFFERENTIAL BETWEEN THE OUTSIDE AIR AND THE INDOOR AIR CO2 CONCENTRATION. MOUNT 49" AFF WHERE SHOWN ON PLANS OR AS DIRECTED BY ARCHITECT. COORDINATE WITH ARCHITECTURAL FINISH. OLOCATION OF ANSUL SYSTEM REMOTE MANUAL PULL STATION. VERIFY EXACT LOCATION WITH KITCHEN EQUIPMENT SUPPLIER_ 9 LOCATION OF DUCT SMOKE DETECTOR TEST /RESET - MOUNT 60" A.F.F. 10 EXISTING RETURN AIR DUCT TO REMAIN. 11 PROVIDE GREASE DUCT CLEANOUTS FOR HOOD DUCTWORK. SEE DETAIL 11/M101. 12 PROVIDE A WALL FINISH DUCT RING WHERE DUCTWORK PENETRATES THE WALL. 13 SIDE WALL RETURN AIR GRILLE, SURFACE - MOUNTED AT A MAXIMUM OF 6" BELOW THE CEILING, WHERE SHOWN ON THE PLANS. 14 THERMOSTATS: THERMOSTATS FOR ROOF TOP UNITS AND DUCT HEATER CONTROL SHALL BE MOUNTED IN THE MANAGERS OFFICE. FIELD - VERIFY THE LOCATION WITH OWNER AND ARCHITECT PRIOR TO PERFORMING THE WORK. MOUNT 48' AFF, WHERE SHOWN ON PLANS, OR AS DIRECTED BY THE ARCHITECT /OWNER. COORDINATE WITH ARCHITECTURAL FINISH. 15 ELECTRIC --DUCT HEATER - COORDINATE MOUNTING LOCATION WITH STRUCTURAL AND ELECTRICAL. REFER TO SCHEDULE ON M102. WIRING BY ELECTRICAL 1 G EXISTING GREASE EXHAUST DUCT. REFER TO SPECIFICATIONS REGARDING DUCT CLEANING. KITCHEN EXHAUST HOOD. REFER TO CAPTIVEAIRE SHEETS IN FOODSERVICE PLANS FOR ADDITIONAL INFORMATION. REFER TO SHEET M200 -201 FOR FAN ROOM PLAN. 17 CONNECT NEW 406 (COORDINATE SIZE WITH DISHMACHINE) BRANCH DUCTS FROM DISHWASER COMBINES TO EXISTING 12x& EXHAUST DUCT. SLOPE 1/8" PER FOOT BACK TOWARDS DISHMACHINE. 18 RELOCATE EXISTING DIFFUSER TO LOCATION SHOWN ON PLANS. COORDINATE DIFFUSER LOCATION WITH CEILING GRID. CONNECT TO EXISTING MAIN DUCT AS NEEDED. 19 EXISTING TOILET ROOM EXHAUST TO REMAIN. 0 EXISTING DUCTWORK TO REMAIN. 21 TAP DUCT FROM TOP OF DUCT. PROVIDE MANUAL BALANCING DAMPER AT DIFFUSER. REBALANCE SUPPLY DIFFUSER TO 460 CFM. 23 REBALANCE SUPPLY DIFFUSER TO 200 CFM. 4 EXISTING TOLIET ROOM EXHAUST FAN TO REMAIN. REFER TO SPECIFICATIONS REGARDING DUCT CLEANING. A. Ductwork Materials 1. Exposed Ductwork Materials. Where ductwork is indicated to be exposed to view in occupied spaces, provide materials which are free from visual imperfections including pitting, seam marks, roller marks, stains and discolorations, and other imperfections, including those which would impair painting. 2. Sheet Metal. Except as otherwise indicated, fabricate ductwork from galvanized sheet steel of lockforming quality; with zinc coating in accordance with code requirements. B. Miscellaneous Ductwork Materials 1. General. Provide miscellaneous materials and products of types and sizes indicated and, where not otherwise indicated, provide type and size required to comply with ductwork system requirements including proper connection of ductwork anrrl equipment. 2. Duct Sealant. Non hardening, non migrating mastic or liquid elastic water -based sealant, type applicable for fabrication /installation detail, as compounded and recommended by manufacturer specifically for sealing joints and seams in ductwork. 3. Ductwork Support Materials. Except as otherwise indicated, provide hot dipped galvanized steel fasteners, anchors, rods, straps, trim and angles for support of ductwork. a. Except where space is indicated as "High Humidity" area, interior support materials of not less than 1/4" diameter or 3/16" thickness may be plain (not galvanized). A. External Insulation (Rigid Board Type) (FSK Facing); CertainTeed 1112' thick, 3 lb. density Fiberglass Board (FSK Facing) Knauf Insulation 1 YZ' thick, 3 lb. density Fiberglass (FSK Facing) Owens - Coming 11/2" thick, 3 Ib. density Fiberglass Board (FSK Facing) Johns Manville 11/2" thick, 3 lb. density Fiberglass Board (FSK Facing) B. External Insulation (Blanket Type): Johns Manville, R6. 11/2" thick, 0.75 lb. density, FSK facing, 1 -2" Tab Knauf Insulation 1 YW' thick, 0.75 lb. density, FSK 1 -2" Tab Owens - Coming, ED75, 142" thick, 0.75 lb. density, FRK -25, 1 -2" Tab CertainTeed, Type IV, 11/2" thick, 0.75 lb. density, FSK 1 -2" Tab C. External Insulation for Kitchen Hood Exhaust Ducts: 1. Blanket type insulation, UL classified for zero clearance, 2 -hour fire -rated grease duct enclosure system. h m A ■ REMOTE S 36 CO2.SENS FOR ' . , BAP wk �yl�l tl� 1 �. 4 � `.�VPI11Il�IIIIlabgII I Nell3i ( •i ` III, r, 13 354 D12--1- 184'2301 1202 p , I 12.D_J- 18x6 -�00 c i ® 0<2 <=> 1 / p DD-1 -184 -2301 V V \62j OD- 2- 12� -40 4362 U 11111`•i 10 EX -AHU -3 1 2 Z 26x12 P BEER COOLER N 124 MEAT o I r COOLER 24x24 110 I 4 4 REMOTE SENSOR AND -I CO2 SENSOR FOR X -RTU -2 ly TO lOR -- 14x12 14x16 11 7 D t 7T - D- j -15XG -300 - -1 ix - -1 ixFi -300 4Gx 10 _ _� 1 I Lam, I D�� c., + + 41 o 2 1x24 11 u JDQ_, - 13x6001 PRODUCE Ti PATRICK G. PLEES PATRICK G. GLEES, ARCHITECT 219 N. 2ND ST,, SUITE 301 MINNEAPOLIS, MN 55401 PHONE: (612) 338 -6677 FAX: (6172) 336 -2995 E -MAIL: infoftmarch,com CONSULTANTS: JAMES H. ART, P.E. 305 2ND ST NW, SUITE 105 NEW BRIGHTON, MN 55112 PHONE: (651) 632 -2300 FAX: (651) 632 -2397 _ EX- HU -2 SID, 113 1 / DI' NING B � 1 F1_2 2 351 � p <7 J 3 362 1- As, �- N ' 1/ _ n�_._ J o ; n E -AHU 4 DDD= 1 -1 &x6 -230 N 12 \ - SEAL: 1 7 N `ttNlltti /tr�r� -18x6 -2301 p - -23 I QD� -18x6 -230 1 DD-1 -184- -230 1 - - - 3 - 351 i �. .. ( j No b3/67 10x$ 16x16 OX16 (�(R P l C E 20 \ *� • 362 .... 18 � DD= 1 -1 &x6 -too t DD 1 & -1- 18x6 -230 o - p 1 - \ - 109 x6 -2ao i � �, � : TAT E 4 • '^ O / �i - -- l � 12 � o 0 0 � � � •---_- X- AIiU -1 4x16 362 364 364 362 !�� 1 w�S�Q •...L� ` -- = -- - -_ MOTE--S AND 24x N N ����I�j%ijlltltlt �� 17 362 64 -� X64 - 4 7 SENSOR 0� �� 1 2 o \ N 1 4x16 1 oe I HEREBY CERTIFY THAT THE OE ICE - PORTION OF THIS TECHNICAL 13 / SUBMISSION DESCRIPED BELOW 20x16 30x20 4 8x6 -260 12 Lzi2 354 I Sl / 0 C5> ? - - - - - - - - -- - - - - -- W R _ ._ " _.. - - - - -- - - - -I - ® AS PREPARED !�Y ME OR UNDER MY DIRECT SUPERVISION AND - r RESPONSIBLE CHARGE. I AM A 362 ® �� RG1 -24x24 1 Ox, o TRASH TOILET _ DULY REGISTERED ENGINEER UNDER THE LAWS OF THE STATE FLORIDA. 16x1 0-1 -184-270 - 3 - - - _ 1 0 JAMES W. T DD-1 -18x& -270 QD -18x6 -260 0 8 15 _ __ AR / ) _ cl1 G- -24x 21 REMOTE SENSOR D 1 23 T -STATS FOR 11 O MAY 20, 2011 7 CO2 SENSOR FOR - _ -.- //3/63 � / '/7/ r p -- EX- AHU -1 -4 - -- 22 DATE ISSUED LCOVE AND DtL-1 18 4 EX -RTU -4 UTILITY MEN'S - _. (S - - CL -� -.. - - ' >{ 63167 {� 1 U I LE T _ �� I0x8 - - o (G 2x10 3 jjj PEG. NQ. M 1+J 9 ' __ __ T QQ=� - 18x6 -270 - - 354 x - DD _-J-186-260 /� 2 1040x16 - -5 DINING A 121 `° / - - - - - -- -J "� « �• :. DL-J - &x6- 60 1 - DD -1 -18x6 -270r '•,e _j� .! '.^ /lei. �. `"'. 4 354 ' awl. a bras w: 351 `D BUFFALO WILD WINGS =__ j CONSTRUCTION DEPARTt;1ENT 351 �i ® ® 351 �_ 18 5500 WAYZATA BLVD., STE 1600 - _ MINNEAPOLIS, MN 55416 PtGriE (S52) $J3 -B�43 FAx (452) 5933-4787 6-260 D- x WOMEN'S \ / I I I EDMOND FARRAN 0D_-j -18x6 -270 FO L I 0 1 DD- 1 -1�x6-260 Iti� THE SHOPS AT SUNSET PLACE - Q - - - - -- -� - - - - 5701 SUNSET DRIVE,, #1313A - - -- -- - ® ® ® J 16x12 ' - SOUTH MIAMI, FL' 33143 I'I DD�- 18x6 -270 DD- 13X6_28 - - - - - -- - - - - -- - -- ..- - -- 354 1 MECHANICAL PLAN ! ! FRANCHISEE: D)') -, -1 &x6'270 I N 362 "' \ laJ 4 M100 SCALE: 1/4' -1' -0" SETH Dtseth4e R (� Q)Za- 18x6 -260 EMAIL seth�ekChefineil.eem \ � FRANCHISE STORE 1 0 4' i' 16' - -- -I DD -1 -18x6 -100 { SHEET TITLE: c� I PJL-J-134-270 1 SCALE BASED ON A 30 "x42" SHEET SIZE MECHANICAL PLAN p 363 y � PER -MIT SET REVISIONS: GENERAL NOTES OPTIONAL ITEMS -SHALL BE VERIFIED WITH CONSTRUCTION MANAGER PRIOR TO � E: N0: DATAT BY: IMPLEMENTING INTO PLANS - ALL PLANS AND SPECIFICATIONS SHALL BE -_. T_.- .___.______-r.- -.._._ _ VERIFIED WITH SITE -- SPECIFIC CONDITIONS AND SHALL BE IN COMPLIANCE WITH 1 N0 FVi310N45 PIS ALL LOCAL CODES AND JURISDICTIONAL REQUIREMENTS 1. THE MECHANICAL CONTRACTOR SHALL VERIFY THAT ALL EQUIPMENT, AS SHOWN ON THESE DRAWINGS, WILL 10. ALL ITEMS PROJECTING THROUGH ROOFS SHALL BE FLASHED THROUGH CURBS OR PIPE SEALS A MINIMUM OF 01g,2- JUN(=- 2rr?11, J___.___._.I____.__. i�lfi1+ILti4 NOT CONFLICT WITH ANY DRAINS, JOINTS, VENTS, PIPING OR EQUIPMENT. 12" ABOVE THE ROOF. THE PIPE CURBS AND SEALS SHALL DE SUPPLIED BY THE MECHANICAL CONTRACTOR t -�___ _ ALL HORIZONTAL GREASE DUCT SHALL SLOPE 1/4" PER FOOT PER NFTA 96, AND INSTALLED BY THE ROOFING CONTRACTOR. INSURE THAT AMPLE BOOT OPENINGS ARE PROVIDED TO � N 15- JULY -2011` �allLalt� 2004 EDITION. 2. ALL ROOFTOP EQUIPMENT SHALL HAVE MANUFACTURER SUPPLIED ROOF CURBS AND PIPE SEALS. ANY ELECTRICAL CONDUIT PENETRATIONS REQUIRED. - --kr- - - -' -- - {-- - - - - -- 3. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ADMINISTERING ALL WARRANTIES ON EQUIPMENT 11. ALL SUPPLY AND RETURN AIR DEVICES SHALL BE PAINTED AS REQUIRED BY THE OWNER. ? ALL TURNS IN KITCHEN EXHAUST DUCT ARE SHALL IZE ACCOMPLISHED BY THE WHICH THEY PROVIDE. THIS INCLUDES, BUT IS NOT LIMITED TO REFRIGERANT LINES. (CONTRACTOR USE OF 1.5 CENTERLINE RADIUS SMOOTH RADIUS ELBOWS. 12. SHALL VERIFY ALL DIMENSIONS IN FIELD PRIOR TO CONSTRUCTION, AND REPORT TO 4. ALL OUTSIDE AIR INTAKES SHALL BE A MINIMUM OF 10' -0" FROM ANY EXHAUST FANS OR PLUMBING VENTS. ARCHITECT /ENGINEER ALL ERRORS, DISCREPANCIES, OMISSIONS, DEFECTS, OR UNUSUAL CONDITIONS BEFORE INSTALLING CONTRACTOR SHALL PROVIDE ALL CODE REQUIRED FIRE RATED COMMENCING CONSTRUCTION. ANY CONFLICT BETWEEN THE SPECIFICATIONS AND DRAWINGS IS SHALL ACCESS DOORS IN GREASE DUCTS AT ALL LOCATIONS REQUIRED BY CODE AND 5. PROVIDE VIBRATION ISOLATION DEVICES AND FLEXIBLE CONNECTIONS TO ALL MOVING MACHINERY. BROUGHT TO THE ATTENTION OF THE ARCHITECT /ENGINEER PRIOR TO WORK. BY THE LOCAL AUTHORITY HAVING JURISDICTION. t 6. ALL FLEXIBLE DUCTS SHALL BE SUPPORTED EVERY 3' -0" WITH 2" WIDE GALV. STEEL BANDS WITH A MINIMUM 13. ALL DEFECTIVE OR UNACCEPTABLE WORK SHALL BE REMOVED AND REPLACED TOGETHER WITH SURROUNDING HOOD EXHAUST SYSTEMS SHALL BE FURNISHED AND INSTALLED PER NFPA 96, OF ONE PER EACH SECTION OF FLEXIBLE DUCT. THE MAXIMUM ALLOWABLE LENGTH OF THE FLEX DUCT SHALL AFFECTED AREAS AT NO ADDITIONAL EXPENSE TO THE OWNER. 2004 EDITION AND CRY, BUILDING, AND FIRE CODES. BE 5' -0 ". (CLEAN 14. ALL DUCTWORK BOTH INSIDE AND OUT BEFORE START-UP OF ROOFTOP UNITS. - ALL EXPOSED DUCT AND FITTINGS SHALL BE PROVIDED WITH A MILL 7• NO FLEXIBLE DUCTWORK SHALL BE ALLOWED ABOVE INACCESSIBLE CEILINGS. PHOSPHATIZED FINISH PAINT GRIP ", "ZINC GRIP" OR SIMILAR ETCH TREATME � 8. ALL DUCT'DIMENSIONS SHOWN ON DRAWINGS ARE CLEAR INSIDE DIMENSIONS, NO ALLOWANCE HAS BEEN 15. LOCATE ALL THERMOSTATS AT 4i" MAXIMUM A.F.F.. TO ALLOW THE DUCTWORK TO BE PAINTED. MADE FOR LINER OR WRAP. 16. (PROVIDE TURNING VANES IN ALL 90 DEG ELBOWS IN SUPPLY AND RETURN DUCTWORK. ' PROJECT NO: 11136.001 THE INSTALLING CONTRACTOR SHALL PROVIDE THE OWNER WITH A COMPLETE SET 9. THE MECHANICAL CONTRACTOR SHALL COORDINATE ALL REQUIRMENTS AND EXCAVATION WITH THE GENERAL 17. AIR BALANCING OF HVAC SYSTEM SHALL BE PREFORMED BY AN INDEPENDENT AIR BALANCING CONTRACTOR QRAWN BY: TCK OF AS -BUILT DRAWINGS, SHOWING ALL FIELD MODIFICATIONS, AT THE CONCLUSION CONTRACTOR AND OTHER TRADES. ALL REQUIRED OPENINGS IN FOUNDATIONS, FLOORS, WALLS AND ROOF AT THE EXPENSE OF THE MECHANICAL CONTRACTOR. SUBMIT 5 COPIES OF THE BAUWCING REPORT TO OF THE PROJECT. SHALL BE BUILT INTO THE STRUCTURE WITH THE USE OF SLEEVES, CURBS, ETC. CUTTING AND PATCHING A,RCHrrECT /ENGINEER. SHALL BE HELD TO A MINIMUM. DUCT SMOKE DETECTORS REQUIRE A REMOTE LED INDICATOR THRU THE CEILING LEVEL NFPA 72 3- 8.4,2.2 AND 2- 10.54. 13. PROVIDE ADEQUATE ACCESS FOR SERVICE AND MAINTENANCE OF ALL EQUIPMENT. M 1 0 0 5770.11 ,.I tM+..af.':Ye`- `-''mot..- ....:a - wW.N.R.rr,k..S.wf2al.L..1:.' • u ..L::i.uW • --•.•. 'w..;F.ikL4. wk,.. \i.J ".,•. - -.: r ^• ':' -•�.. -. .:�.tL4+1+..iwuLw.fw'.�l•. y's..� y'.G4wW ✓/_� ' I�r�e...,..1,i.s.'v_s:3r�,' ,+i,+M�iu �,.�ti.YS'i .r �,.....wai ".C5.v: ..,. .- ..._t �.N11�/w ✓.. COPYRIGHT PATRICK G RI A.A 2011 G. ,