KEY NOTES
SMOKE DETECTOR: PROVIDE SMOKE DETECTOR IN AIR HANDLING UNIT SUPPLY AIR STREAM. INTERLOCK AIR
HANDLING UNIT WITH THE DETECTOR. AIR HANDLING UNIT SHALL DEACTIVATE ON DETECTION OF SMOKE. PROVIDE
AN AUDIBLE/VISUAL ALARM DEVICE AND KEYED TESTING STATION IN MONITORED AREA, PER LOCAL CODE. TIE THE
SMOKE DETECTOR INTO THE FIRE ALARM SYSTEM AS REQUIRED. SEE ELECTRICAL DRAWINGS FOR LOCATIONS.
OPROVIDE 1" THICK ACOUSTICAL LINING IN RETURN AIR DUCTWORK AND 1/2 "x1/2" WIRE MESH COVERING AT
OPENINGS ON SIDES OF RETURN AIR DUCTWORK. EACH OPENING SHALL HAVE AN AREA EQUAL TO THE CROSS
SECTIONAL AREA OF THE RETURN DUCTWORK.
QalSTING AIR HANDLING UNIT, THERMOSTAT, REMOTE SENSOR, AND CO2 SENSOR. PROVIDE STRUCTURAL SUPPORT
AS REQUIRED FOR NEW ROOFTOP UNIT. DISCONNECT SHALL BE PROVIDED BY THE EQUIPMENT SUPPLIER.
COORDINATE GFI CONVENIENCE Ot.ITLET WITH ELECTRICAL. ROUTE RTU CONDENSATE DRAIN TO NEAREST ROOF
DRAIN OR SPLASH BLOCK. VERIFY IN FIELD. SEE SHEET M102 FOR DETAILS.
{ 4� REMOTE TEUEEEMBE SENSOR: PROVIDE A REMOTE SENSOR FOR THE THERMOSTAT. MOUNT 48" AFF WHERE
SHOWN ON PLANS OR AS DIRECTED BY ARCHITECT. COORDINATE SENSOR LOCATION WITH WALL COVERINGS AND
EQUIPMENT. PROVIDE WIRING THROUGH THE THERMOSTAT AS REQUIRED FOR CONTROL OF THE UNIT.
OKITCHEN HOOD SYSTEM: CONTRACTOR SHALL INSTALL OWNER- FURNISHED CAPTIVEAIRE KITCHEN HOOD FROM BWW
VENDOR. THE PACKAGE INCLUDES STAINLESS STEEL EXHAUST HOOD WITH FIRE CABINET, GREASE FILTERS, GREASE
CATCH PAN ON THE ROOF, WIRE WAYS WITH SWITCHES, INCANDESCENT LIGHT FIXTURE RATED FOR EXHAUST
HOODS, FULL ANSUL FIRE SUPPRESSION SYSTEM WITH TANKS, AND AUTOMATIC TEMPERATURE BASED ACTIVATION
SYSTEM. MECHANICAL CONTRACTOR IS RESPONSIBLE FOR THE INSTALLATION OF A STAINLESS STEEL BACK SPLASH
AT EACH KITCHEN HOOD. REFER TO SHEETS M200 -M201 FOR ADDITIONAL INFORMATION.
OKITCHEN HOOD ANSUL SYSTEM: WET TYPE CHEMICAL FIRE EXTINGUISHING SYSTEM SHALL BE IN COMPLETE
CONFORMANCE WITH NFPA 96. SYSTEM SHALL BE CONTAINED IN A REMOVABLE STAINLESS STEEL COMPARTMENT
LOCATED ON THE END OF KITCHEN HOOD. LIGHT SWITCH TO BE LOCATED ON FACE OF SYSTEM COMPARTMENT.
(MODIFIED AND TESTED BY ANSUL SYSTEM CONTRACTOR).
O7 CARBON DIOXIDE SENSOR: CO2 SENSOR SHALL CONTROL THE MINIMUM OUTSIDE AIR QUANTITY. CONTROLLER
SHALL MODULATE OUTSIDE AIR TO MAINTAIN 700 PPM DIFFERENTIAL BETWEEN THE OUTSIDE AIR AND THE INDOOR
AIR CO2 CONCENTRATION. MOUNT 48" AFF WHERE SHOWN ON PLANS OR AS DIRECTED BY ARCHITECT.
^ COORDINATE WITH ARCHITECTURAL FINISH.
8, LOCATION OF ANSUL SYSTEM REMOTE MANUAL PULL STATION. VERIFY EXACT LOCATION WITH KITCHEN EQUIPMENT
v SUPPLIER.
9 LOCATION OF DUCT SMOKE DETECTOR TEST /RESET - MOUNT 60" A.F.F.
10 EXISTING RETURN AIR DUCT TO REMAIN.
11 PROVIDE GREASE DUCT CLEANOUTS FOR HOOD DUCTWORK. SEE DETAIL 11/M101.
12 PROVIDE A WALL FINISH DUCT RING WHERE DUCTWORK PENETRATES THE WALL.
13 SIDE WALL RETURN AIR GRILLE, SURFACE - MOUNTED AT A MAXIMUM OF 6" BELOW THE CEILING, WHERE SHOWN
ON THE PLANS.
14 THERMOSTATS: THERMOSTATS FOR ROOF TOP UNITS AND DUCT HEATER CONTROL SHALL BE MOUNTED IN THE
MANAGERS OFFICE. FIELD - VERIFY THE LOCATION WITH OWNER AND ARCHITECT PRIOR TO PERFORMING THE WORK.
MOUNT 48" AFF, WHERE SHOWN ON PLANS, OR AS DIRECTED BY THE ARCHITECT /OWNER. COORDINATE WITH
ARCHITECTURAL FINISH.
15 ELEQMIQ QQQJ HEATE - COORDINATE MOUNTING LOCATION WITH STRUCTURAL AND ELECTRICAL REFER TO
SCHEDULE ON M102. WIRING BY ELECTRICAL
1 G EXISTING GREASE EXHAUST DUCT. REFER TO SPECIFICATIONS REGARDING DUCT CLEANING.
KITCHEN EXHAUST HOOD. REFER TO CAPT€VEAIRE SHEETS IN FOODSERVICE PLANS FOR ADDITIONAL INFORMATION.
REFER TO SHEET M200 -201 FOR FAN ROOM PLAN.
17 CONNECT NEW 406 (COORDINATE SIZE WITH DISHMACHINE) BRANCH DUCTS FROM DISHWASER COMBINES TO
EXISTING 12x8 EXHAUST DUCT. SLOPE 1/8" PER FOOT BACK TOWARDS DISHMACHINE.
1 a RELOCATE EXISTING DIFFUSER TO LOCATION SHOWN ON PLANS. COORDINATE DIFFUSER LOCATION WITH CEILING
GRID. CONNECT TO EXISTING MAIN DUCT AS NEEDED.
19 EXISTING TOILET ROOM EXHAUST TO REMAIN.
0 EXISTING DUCTWORK TO REMAIN.
21 TAP DUCT FROM TOP OF DUCT. PROVIDE MANUAL BALANCING DAMPER AT DIFFUSER.
REBALANCE SUPPLY DIFFUSER TO 460 CFM.
3 REBALANCE SUPPLY DIFFUSER TO 200 CFM.
4 EXISTING TOLIET ROOM EXHAUST FAN TO REMAIN. REFER TO SPECIFICATIONS REGARDING DUCT CLEANING.
z
_ y
A. Ductwork Materials
1. Exposed Ductwork Materials, Where ductwork is indicated to be exposed to view in
occupied spaces, provide materials which are free from visual imperfections including
pitting, seam marks, roller marks, stains and discolorations, and other imperfections,
including those which would impair painting.
2. Sheet Me '21. Except as otherwise indicated, fabricate ductwork from galvanized sheet
steel of lockforming quality; with zinc coating in accordance with code requirements.
B. Miscellaneous Ductwork Materials
1. General. Provide miscellaneous materials and products of types and sizes indicated
and, where not otherwise indicated, provide type and size required to comply with ductwork
system requirements including proper connection of ductwork and equipment.
2. Duct Sealant. Non hardening, non migrating mastic or liquid elastic water -based
sealant, typo applicable for fabrication /installation detail, as compounded and
recommend,:d by manufacturer specifically for sealing joints and seams in ductwork:
3. Ductwork Support Materials. Except as otherwise indicated, provide hot dipped
galvanized steel fasteners, anchors, rods, straps, trim and angles for support of ductwork.
a. Except where space is indicated as "High Humidity" area, interior support materials of
not less than 1/4" diameter or 3/16" thickness may be plain (not galvanized).
A. External Insulation (Rigid Board Type) (FSK Facie:
CertalnTeed 11/2" thick, 3 Ib. density Fiberglass Board (FSK Facing)
Knauf Insulation 1 A" thick, 3 lb. density Fiberglass (FSK Facing)
Owens- Corning 1, /i' thick, 3 lb. density Fiberglass Board (FSK Facing)
Johns Manville lib" thick, 3lb. density Fiberglass Board (FSK Facing)
B. External Insulation Blanket Type)
Johns Manville, R6. 144" thick, 0.75 lb. density, FSK facing, 1 -2" Tab
Knauf Insulation 11/2" thick, 0.75 lb. density, FSK 1 -2" Tab
Owens- Corning, ED75, 11/2" thick, 0.75 lb. density, FRK -25, 1 -2" Tab
CertainTeed, Type IV, 1,12" thick, 0.75 lb. density, FSK 1 -2" Tab
C. Extemal Insulation for Kitchen Hood Exhaust Ducts:
1. Blanket type insulation, UL classified for zero clearance, 2 -hour fire -rated grease duct
enclosure system.
PAN
B =�3
3z - -,,-
REMOTE SENSOR AND 362 �_
CO2 SENSOR FOR O
0 R D E R I N C- IX -RTU -3
104 364 364 __
S{l \� BAF
- -12f -400 23
r9
_ r 4111_ •
_�i • ���► /!�I��►!�� I III`
�►S 1 f► ' - ' - - - =
rig
E
1,4b ',,>
nf J
13 - -
- L
\ EX -AHU -3 1 2
3
° 26x12 I COOLER
124 0
1,362 A
III 2
IV
0
1a � MEAT ! I
p
7 4x24 J 110
4 REMOTE SENSOR AND ❑�
- - CO2 SENSOR FOR 5
354 �7 D(- RTU -2 T= 0:_..A R 2
DD -1 -1 IX6 -230 N 1 a
12 2 14x12 14x16
351 -A 46x
p 1 DD- 1- lixfi- 00 0_-J -134-300 Qom, -1 ax -, -18x6 -300
1 1
U p II °- M
CD / I I
362 �_ -�` 11
® f O 2x24 I ii
p D D- 1- 13 x6' 2 30 III
DD- 1 -1ixS X500 - » J -
/ �I - PRODUCE
I ,
EX- HU - -2 ;' 1a SID 113
DINIIJG
- K V V W
W V V v V V
kM
A f J1IGK
vG. E3LEE�S
PATRICK G. I LEES, ARCHITECT
N. ?CIO Sf., SUITE 3C-1
- ,M1ANE!R_P0! IS,".HN � - 55`40'1
PHONE: (612) 335 -6677
FAX: (612) 338 -2995
4a E-MAIL: info0cmcrch.COM
CONSULTANTS:
JADES H. ART, P.E.
305 2ND ST NW, SUITE 105
NEW BRIGHTON, MN 55112
PHONE: (651) 632 -2300
FAX: (651) 632 -2397
1 / 122 351 J x
362 �\ \ 26 20
1 I U II N
U
° 12 I p E -�HU SEAL:
DD-1 -, 9x6 -230 -
13x6' 230 -
II II N �nrrri
N 22 1 �� ,%���E5
_ _ 6_230 r DD_ 1 -1 3x6 -230 DD-J-1&6-2 30
\l 1 t o `� " � . F- .�
351 ® ® \
16x16 0x16 I� 9 �R R� _ J PI _- _ 20
1 oxi x III �(RSrR --
18 2
i
p�� -, 3x6 -200 -, 3x6' 230 I 1 I �, x6
13-200 -
p 12 EX -AHU -1
b
362 364 364 362_ 1
- - - SMOTE - SENSR AND 24x N
4 7- 2�ENS01� Q 1 2 1 4x16- 1
362. X364 364 /
EX 0 - IF
o
OF ICE o - N
20x16 30x20 13 _ 0 47- 5 ICJ - - - - - -- -
_ _
C: pp- J -l8x6 -260 12 12 354 Sl 0 11 _.._._...
1% � y j 6� -24x24 1 0 \ p TRASH
"OX ® Oxi
�- l�
DD- J -1lx6 -270 2
DD -1 -18x6 -270 1 per J - 18x6 -�I _
-24x_ .
n' Q3 T -STATS FOR
L\ E R EX-AHLIl -1 -4
T01 LET AND DH -1
> A
'3 6 4
DD--J -13x-260
® DINING ---
„ 121 `.°
DD -1 -13x6- 60I
DD--J-18x6-270 X
354} --
1
ff352 351 351
� ® � 351
II 351
VI \ per, -13x6 -260 \I'
\ '
WOMENS
-
DD -1 -13x6 -270 � 7<- T01L
119
M=-j -18X6 -260 L�
�-
\ I 354
0
���tIJI
make: �IIIBIB•I■ w REMOTE SENSOR A D
CO2 SENSOR FO
I�� �►
API - ■ � ��
1.
I
V, F % �r
No 63167 ;*
•11 i :
I HEREBY CERTIFY THAT THE
- PORTION OF THIS TECHNICAL
SUBMISSION DESCRIBED BELOW
WAS PREPARED BY ME OR UNDER
.. .... ... . .... .. _.__._ ... ___ .. -- MY DIRECT SUPERVISION AND
RESPONSIBLE CHARGE. I AM A
TOILET DULY REGISTERED ENGINEER UNDER
THE LAWS OF THE STATE FLORIDA.
164 16x�
- JAME H. ART
I� - - - --
' �'• MAY 20, 2011
-� U TI 1_1 TY DATE ISSUED
63167
2X102
x10 0 -- -_ .....,... - 6
- -- REG. N0.
F0
- - - -- ----- ...
-- ..__......._...__. ..... _... .
[2Q. -� -13x6 -270
jZQ=1- 13x6 -26 ........... _ - -- - -- - - -
�
w
\' 1 MECHANICAL PLAN N
QIL - 13x6 -270
�- I2>L -1 -13x6 --260 / /�� 1R 1 4 M100 SCALE 1 /4' -i' -o"
362 � N ��" \
N I QD� -13x6 -270 ® -18x6 -100
HVAC DESIGN REQUIRES:
YES NO
D07 5,>T[1 :4
rl� r, irl � I
•
PERMIT SET
rl r
I, •
0 4' a' 16'
SCALE BASED ON A 30 "x42" SHEET SIZE
BUFFALO WILD WINGS
CONSTRUCTION•! DEPARTMENT
1 a 5500 WAYZATA BLVD., STE: 1600
NEAQLIS, MN 51116
FHO NE (852)
5!13 -9W FAX (952) s1113 -a,92
EDMOND FARRAN
I I
I I THE SHOES AT SUNSET PUCE
5701 SUNSET DRIVE, B13A
SOUTH MIAMI, FL 33143
16x12
FRANCHISEE:
SETH GEKANTER
EMAIL: sethclek0hetmel1cem
FRANCHISE STORE
SHEET TITLE:
MECHANICAL PLAN
PERMIT SET
REVISIONS:
G E N E RAL
NOTES
BY-
OPTIONAL ITEMS - SHALL BE VERIFIED WITH CONSTRUCTION MANAGER PRIOR TO
_
IMPLEMENTING NOO C C SPECIFICATIONS
E ON
aO FMVISIa46
j
FlC 0 S AND SHALL BE IN COMPLIANCE WITH
WITH TS
ALL LOCAL CODES AND JURISDICTIONAL REQUIREMENTS
1.
THE MECHANICAL CONTRACTOR SHALL VERIFY THAT ALL EQUIPMENT, AS SHOWN ON THESE DRAWINGS, WILL
10.
ALL ITEMS PROJECTING THROUGH ROOFS SHALL BE FLASHED THROUGH CURBS OR PIPE SEALS A MINIMUM OF
II, 22 »JUiy""_20111
FlRTtLTI4
NOT CONFLICT WITH ANY DRAINS, JOINTS, VENTS, PIPING OR EQUIPMENT.
12" ABOVE THE ROOF. THE PIPE CURBS AND SEALS SHALL BE SUPPLIED BY THE MECHANICAL CONTRACTOR
AND INSTALLED BY THE ROOFING CONTRACTOR. INSURE THAT AMPLE BOOT OPENINGS ARE PROVIDED
s
�a
l J!LD€t 1Cr
ALL HORIZONTAL GREASE DUCT SHALL SLOPE 1/4" PER FOOT PER NFPA 96,
2,
ALL ROOFTOP EQUIPMENT SHALL HAVE MANUFACTURER SUPPLIED ROOF CURBS AND PIPE SEALS.
ACCOMMODATE ANY ELECTRICAL CONDUIT PENETRATIONS REQUIRED.
^
! I5 -JU: Y -20111
......__....._._..._
2004 EDITION.
•
I
I
ALL TURNS IN KITCHEN EXHAUST DUCT ARE SHALL BE ACCOMPLISHED BY THE
3.
THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ADMINISTERING ALL WARRANTIES ON EQUIPMENT
WHICH THEY PROVIDE. THIS INCLUDES, BUT IS NOT LIMITED TO REFRIGERANT LINES.
11.
ALL SUPPLY AND RETURN AIR DEVICES SHALL RE PAINTED AS REQUIRED BY THE OWNER.
-
l - - -- •- - ____i..___�______.._..__._
_....
ALL DIMENSIONS IN FIELD PRIOR TO CONSTRUCTION, AND REPORT TO
USE OF 1.5 CENTERLINE RADIUS SMOOTH RADIUS ELBOWS.
12.
CONTRACTOR SHALL VERIFY
4.
ALL OUTSIDE AIR INTAKES SHALL BE A MINIMUM OF 10' -0" FROM ANY EXHAUST FANS OR PLUMBING VENTS.
ARCHITECT /ENGINEER ALL ERRORS, DISCREPANCIES, OMISSIONS, DEFECTS; OR UNUSUAL CONDITIONS BEFORE
COMMENCING CONSTRUCTION. ANY CONFLICT BETWEEN THE SPECIFICATIONS AND DRAWINGS IS SHALL
-- -
' !
INSTALLING CONTRACTOR SHALL PROVIDE ALL CODE REQUIRED FIRE RATED
ACCESS DOORS IN GREASE DUCTS AT ALL LOCATIONS REQUIRED BY CODE AND
5.
PROVIDE VIBRATION ISOLATION DEVICES AND FLEXIBLE CONNECTIONS TO ALL MOVING MACHINERY.
BROUGHT TO THE ATTENTION OF THE ARCHITECT ENGINEER PRIOR TO WORK.
/
_-
_...__ .....
BY THE LOCAL AUTHORITY HAVING JURISDICTION.
6.
"
ALL FLEXIBLE DUCTS SHALL BE SUPPORTED EVERY 3' -0" WITH 2 WIDE GALV. STEEL BANDS WITH A MINIMUM
13.
ALL DEFECTIVE OR UNACCEPTAi1LE WORK SHALL BE REMOVED AND REPLACED TOGETHER WITH SURROUNDING
-
i - --- --
r
HOOD EXHAUST SYSTEMS SHALL BE FURNISHED AND INSTALLED PER NFPA 96,
OF ONE PER EACH SECTION OF FLEXIBLE DUCT. THE MAXIMUM ALLOWABLE LENGTH OF THE FLEX DUCT SHALL
AFFECTED AREAS AT NO ADDITIONAL EXPENSE TO THE OWNER.
2004 EDITION AND CITY, BUILDING, AND FIRE CODES.
BE 5' -0 ".
14.
CLEAN ALL DUCTWORK BOTH INSIDE AND OUT BEFORE START -UP OF ROOFTOP UNITS.
- - --
-- --
- -
ALL EXPOSED DUCT AND FITTINGS SHALL BE PROVIDED WITH A MILL
7•
NO FLEXIBLE DUCTWORK SHALL BE ALLOWED ABOVE INACCESSIBLE CEILINGS.
15.
LOCATE ALL THERMOSTATS AT 4a" MAXIMUM A F.F..
PHOSPHATIZED FINISH "PAINT GRIP ", "ZINC GRIP" OR SIMILAR ETCH TREATMENT)
( �
8.
ALL DUCT DIMENSIONS SHOWN ON DRAWINGS ARE CLEAR INSIDE DIMENSIONS. NO ALLOWANCE HAS BEEN
TO ALLOW THE DUCTWORK TO BE PAINTED.
MADE FOR LINER OR WRAP.
16.
PROVIDE TURNING VANES IN ALL RO DEG ELBOWS IN SUPPLY AND RETURN DUCTWORK.
PROJECT NO: 11130.001
... _ ..... _- _.- ._.....--- - -....
THE INSTALLING CONTRACTOR SHALL PROVIDE THE OWNER WITH A COMPLETE SET
9.
THE MECHANICAL CONTRACTOR SHALL COORDINATE ALL REQUIRMENTS AND EXCAVATION WITH THE GENERAL
17.
AIR BALANCING OF HVAC SYSTEM SHALL BE PREFORMED BY AN INDEPENDENT AIR BALANCING CONTRACTOR
__. _
DRAWN BY: TCK
OF AS -BUILT DRAWINGS, SHOWING ALL FIELD MODIFICATIONS, AT THE CONCLUSION
CONTRACTOR AND OTHER TRADES. ALL REQUIRED OPENINGS IN FOUNDATIONS, FLOORS, WALLS AND ROOF
AT THE EXPENSE OF THE MECHANICAL CONTRACTOR. SUBMIT 5 COPIES OF THE BALANCING REPORT TO
-- ....... .... -- .... - --
OF THE PROJECT.
SHALL BE BUILT INTO THE STRUCTURE WITH THE USE OF SLEEVES, CURBS, ETC. CUTTING AND PATCHING
ARCHITECT /ENGINEER.
»
SHALL BE HELD TO A MINIMUM.
1
DUCT SMOKE DETECTORS REQUIRE A REMOTE LED INDICATOR THRU THE CEILING
13.
PROVIDE ADEQUATE ACCESS FOR SERVICE AND MAINTENANCE OF ALL EQUIPMENT.
10
0
LEVEL. NFPA 72 3- 8.4.2.2 AND 2- 10.5.9.
i
.
I r
5770.11
COPYRIGHT PATRICK G. BYE , AIA 2011