04-04-049x GENERAL NOTES: 1. IT IS THE INTENT OF THE DESIGN TO REUSE AS MUCH OF THE EXISTING HVAC' SYSTEMS AS IS POSSIBLE. 2. THE FOLLOWING AIR HANDLING UNITS WILL BE CONVERTED FROM CONSTANT VOLUME UNITS TO VARIABLE AIR FLOW UNITS BY REPLACING THE EXISTING FAN MOTOR WITH A NEW MOTOR RATED FOR OPERATION AT VARYING SPEEDS: AHU -1D, AHU -2D, AHU -3D, AHU -4D AND AHU -8D. SEE EXISTING SCHEDULES ON SHEET MO.2 FOR MORE DIRECTION. 3. ALL RETURN AND TRANSFER AIR DUCTWORK TO BE INTERNALLY LINED GALVANIZED SHEETMETAL DUCTWORK. 4. NEW S.A. DUCTWORK SERVING AHU -1 D UP TO VAV UNITS TO BE INTERNALLY LINED GALVANIZED SHEETMETAL SAME AS EXISTING DUCTWORK. 5. NEW S.A. DUCTWORK FOR AMU ®3D BEING ROUTED DOWN IN VERTICAL DUCT CHASE TO BE INTERNALLY LINED GALVANIZED STEEL SIMILAR TO EXISTING DUCTWORK. 6. ALL EXHAUST DUCTWORK TO BE OF ALUMINUM CONSTRUCTION. 7. PROVIDE MANUFACTURE'S RECOMMENDED CLEARANCES FOR /AROUND ALL NEW EQUIPMENT. REFERENCE NOTES: �1 12X12 E.A. DUCT UP TO NEW EF -1D ON ROOF. THERE IS AN EXISTING FAN LABELED EF -1D IN THIS LOCATION. RE —USE THE EXISTING LOCATION AND CURB IF POSSIBLE TO AVOID A NEW ROOF PEN TR TION. 1 2 NOT USED Q3 R.A. DUCT UP TO AHU -4D ON ROOF. TRANSITION NEW 18X18 DUCT TO EXISTING DUCTWORK. EXISTING 54X20 R.A. DUCT UP TO RTU -2D ON ROOF. EXISTING 48X18 S.A. DUCT UP TO RTU -2D ON ROOF. O EXISTING 18X16 S.A. DUCT UP TO AHU -6D ON ROOF. IT MAY BE NECESSARY TO MODIFY THIS DUCT KEEPING IT TIGHT TO THE UNDERSIDE OF THE STRUCTURE TO PERMIT THE S.A. DUCT FROM AHU -3D TO BE ROUTED UNDERNEATH AND DOWN WITHIN THE DUCT CHASE. 7D EXISTING 16X14 R.A. DUCT UP TO AHU -6D ON ROOF. NECK OF RETURN RN CONNECTION OF M1 A R C H I T E C T S 3501 Griffin Road Ft. Lauderdale, FL 33312 (954) 266 -2700 Fx: (954) 266 -2701 sma�c,s altzmi chels on. com AA- 0002897 0 Thompson Company, Inc. 6220 South. Orange Blossom Trail Suite 195 Orlando, FL 32809 TC1#52316 407 - 438 -1860 phone 407- 438 -1872 fax a Brian S. Hessinger, PE 52660 ggqq Lv -� •:-° ° U U U 0009 0 q Project No_:'U0 Uc1Uq° °3,03 -160 ° U U U 00 q J b U q Drawn By: ° U UUU gfiUU U 1 K V U O U U il )U U UUgUV'v U J ° C h e c SdBV U � u o UU0 U t, U U U V BU U g a o ') 7 U q ° °qUq 0 0 0 EIq U J U U 4 UUUU 00 q U q J UUUUU ° 12 -16 -03 PERMIT SET 02 -06 -04 BID SET %a L F. REVISIONS: A I BUILDING DEPARTMENT COMMENTS 03 -09 -04 3rd FLR PLAN MECHANICAL M3.3 � x X. 1 k�