Loading...
07-1661-091REMOVE EXISTING 1/2' UPRIGHT SPRINKLER & REPLACE WITH NEW 1 \2" x 0' -2' SCHAD NIPPLE EXISTING BRANCHLINE NEW 1'x 1 /2 "BLK C.I. 90' ELL NEW 1" BLT PIPE 3LK C.I. 90' ELL ,IT . 15 F1� NEW CEILING ARMOVER DETAIL FOR 1 " OUTLET �NY X G& MITERFLY VA. W/ TAMPER STITCH POTTER ® FLOW swlral 300 L PIlESSIIRE wa TO SYSTEM \-SECT. DUM VA. \ `LEST VA. UN011 SIGHT CLASS EXIST. STANDPIPE TO REMAIN NOT TO SCALE HANGER SCHEDULE FIRE SPRINKLER Ox HYDRAULIC REPEFEl34CE POINT NFPA 13 TABLE 4- 6.2.2.1 MAXIMUM DISTANCE BETWEEN HANGERD (FT - IN) CEILING H W*n -0 RISE UP OR DROP DOIN NOMINAL. PIPE SIZE 31e 1- 1-1/4-1 1-1/2' 2' 2 -1 Ir 3' 3-1/2- 4- b' 6- 8- STEEL PIPE EXCEPT THREADED LIGHT- N/A 12 -0 12 -0 15-0 15-0 15 -0 15-0 15-0 15-0 15-0 15-0 15 -0 WALL 5.6 QUICK 1/2' TYCO TY-FRB TY3231 SILVER Thread KITCHEN - SEMI - RECCESED PENDENT THREADED LJGHT N/A 12 -0 12 -0 12 -0 12 -0 12 -0 12 -0 N/A N/A N/A N/A N/A WALL STEEL PIPE 5.8 QUICK 1/2' - - - - Thread EXISTING TO REMAIN - UPRIGHT NOTES 1. THERE SHALL BE NOT LESS THAN ONE HANGER FOR EACH SECTION OF PIPE 5.6 QUICK 1/2' 2. SUPPORT SPACING DISTANCE FOR END LINE SPRINKLER DROP ELBOWS AND DROP TEES TO BE IN ACCORDANCE WITH TY -FRB NFPA 13 AND THE PRODUCT APPROVAL USTINQ BRASS Thread OPEN CEILING AREAS I #tl Pov*rr' nrlven stun or Equal T. Ir 3/B' Rod Concrete Construction 3/8' Ali TMegd F r,':