07-1661-084IPIPING ARRANGEMENT SHOWN IS SCHEMATIC. ADJUST TO SUIT
FIELD CONDITIONS. REFER TO ISOMETRIC RISER FOR PIPE SIZES.
SIZES. SET HEATER THERMOSTAT AT 110' F.
HEAT
HOT WATER TO FIXTURES \
AS SHOWN ON PLANS
PROVIDE FULL PORT BALL ;
SHUTOFF VALVES
PROVIDE PIPE UNIONS,
DIELECTRIC IF REQUIRED
FOR DISSIMILAR METALS.
GAS SHUTOFF COCK
6' LONG DIRT LEG
GROUND JOINT UNION �
BURNER THERMOSTAT -
AND PRESSURE REGU-
LATOR FURNISHED
WITH WATER HEATER.
WATER HEATER FRESH AIR INTAKE
3" OR 4" PVC. ABS OR CPVC
INTAKE VERTICALLY OR HORIZONTALLY.
3" MAX. 50 EQUIVALENT FEET.
4" MAX. 120 EQUAVALENT FEET.
EOVIDE A 210E
TPERATURE AND
1 PSI PRESSURE
RELIEF VALVE
WITH TEST LEVER
SIZED WITH AGA /CGA
TEMPERATURE STEAM
RATING 10X OVER
HEATER INPUT.
PROVIDE A HARD
COPPER RELIEF
VALVE DISCHARGE
LINE FULL SIZE OF
VALVE OUTLET RUN
TO INDIRECT WASTE
IN SAME ROOM OR
TO OUTSIDE BUILDING
e' ABOVE GRADE WITH
A VISIBLE AIR GAP IN
SAME ROOM PER FLORIDA
BUILDING CODE 2004 SEC.
504.7 AND 504.7.1
MIN. 4 GAL. COLD WATER SUPPLY
EXPANSION TO WATER HEATER.
TANK
RECIRCULATION
CHECK PUMP AQUASTAT AND
VALVE TIME CLOCK
:AT TR
♦ ~ HOT WATER
RECIRCULATION LINE
WATER HEATER EXHAUST VENT
3' OR 4' PVC. ABS OR CPVC
VENT VERTICALLY OR HORIZONTALLY.
3" MAX. 50 EQUIVALENT FEET.
4" MAX. 120 EQUIVALENT FEET.
DRAIN VALVE B VDRAJN PAN WITH
PROVIDE A DRAIN PAN, RUN HEATER MANUFACT. MINIMUM 2" HIGH SIDES
OVERFLOW LINE TO EXTERIOR
OF BUILDING AT 6" ABOVE
FINISHED GRADE OR NEAREST
APPROVED INDIRECT WASTE.
NOTE- DETAIL BASED ON 'A.O. SMITH CYCLONE' MODEL FOR THE PRE - ENGINEERED
VENTILATION SYSTEM. CONSULT WITH ACTUAL MANUFACTURE FOR EXACT VENTILATION REQUIREMENTS
IF DIFFERENT MODEL IS INSTALLED.
GAS WATER HEATER DETAIL
NOT TO SCALE
1
NOTES, PIT RAIN PAN FOR TRAP
CH DRAIN FOR PROPER RUNOFF.
3. MANUALLY PRIME FILL TRAP BEFORE START -UP TO FORM
INITIAL DRAIN SEAL.
4. SUPPORT LENGTHY DRAIN LINES TO PREVENT SAG AND
CONDENSATE OVERFLOW.
FV
A/C UNIT CLEANOUT VENT LINE
CAP (TYP.) PERFORATED
CAP
PITCH
DRAIN PAN
PITCH o
c,
DRAIN PIPE
TO MATCH DRAIN ,
OUTLET SIZE. $
(a) THIS DIMENSION IN INCHES MUST BE
EQUAL TO THE MAXIMUM FAN SUCTION
THIS STANDARD DETAIL MUST V GE (MAH PRESSURE
BE REVIEWED AND SITE TDIRTY FILTERS,OILS. INCHES
ADAPTED BY CONTRACTOR MAXIMUM AIR FLOW) + 1" W.G.
PRIOR TO USE FOR FINAL
EQUIPMENT. (b) EQUAL DIMENSION IN INCHES MUST BE
UALTO MIN. 1/2 OF THE (a) ABOVE
(c) EQUALS (a) + (b) + PIPE DIA. +
+ INSULATION
DRAW THRU UNITaCONDENSATE TRAP
N TO SCALE
PROVIDE TEST TEE
WITH SCREWED COUNTER-
SUNK ABS PLASTIC PLUG:
TAPERED - THREAD WITH
TFE JOINT COMPOUND. -
WHERE CLEANOUT TEE
IS CONCEALED IN A
CHASE OR PARTITION,
PROVIDE A ROUND 18
GAUGE STAINLESS STEEL
COVER WITH BEVELED
EDGES AND FLATHEAD
MACHINE SCREW.
.
CONCRETE
FLOOR
SLAB -
a
COLUMN OR PARTITION
AS SHOWN ON FLOOR PLAN
CLEANOUT FACE SHALL
BE WITHIN 4' OF WALL
SURFACE. PROVIDE
PIPE EXTENSION IF REQUIRED.
HOTEL
PROVIDE WCO WHERE SHOWN ON PLAN, AND ON SANITARY WASTE BRANCHES
NOT SERVED WITH A FLOOR CLEANOUT' LOCATE ABOVE FIXTURE FLOOD RIM
WITHIN 4' OF FLOOR. CONSULT LOCAL CODES FOR OTHER WCO REQUIREMENTS.
WALL CLEANOUT DETAIL
NOT TO SCALE
BY GAS COMPANY (VERIFY)
BY PLUMBING CONTRACTOR
PRESSURE TEST COCK
BUILDING WALL
GAS METER OF CFH
1/2'
B
GAS PIPE UP INTO BLDG.
CAPACITY SHOWN
3/4"
C
SIOUX CHIEF 654-C
SIZE AS SHOWN ON PLAN.
ON PLANS
ACCESS DOOR REQUIRED. CONFORMS CONFORMS TO ANSI /ASS INSTALLATION 1 N STANDARDS.
DOMESTIC HOT WATER
WATER CLOSET, FLUSH VALVE BOWL: FLOOR MOUNTED, SIPHON JET ACTION VITREOUS CHINA,
ELONGATED RIM AND 1 -1/2" TOP SPUD, AMERICAN STANDARD 2234.015 MADERA AQUAMETER, 1.6
USE BLACK STEEL PIPE.
STRAINER
NOTES
S- - ---5
HOT WATER PIPING (140')
PIPE INCREASER.
(OPTIONAL)
WITH ELONGATED RIM AND 1 -1/2' TOP SPUD. 18' HIGH AMERICAN STANDARD /3043.102 ELDERLY
NEW CADET AQUAMETER, 1.6 GPF TOILET WITH SLOAN ROYAL /111 FLUSH VALVE AND A COMFORT
SEAT MODEL IS C106C, OPEN FRONT SEAT LESS COVER.
PO 1
S- -CD-S
CONDENSATE PIPING
�Q
GATE VALVE
DIRT LEG AT BOTTOM
FGNHWATER
i
GAS COCK
�- G -S
OF RISER. ANCHOR
SPECIFIED FAUCET AND PER ARCHITECTURAL FINISH SCHEDULE.
(4) - ALL FIXTURES SHALL BE ROUGHED IN PER MANUFACTURER CUT SHEET TO MAINTAIN UNIFORMITY.
WATER HAMMER ARRESTER (PDI No.)
S-o-S
PIPE RISE UP
RISER TO WALL.
GRADE OR
u
FLOOR DRAIN
FLOOR
PAVEMENT
F--
CAPPED END OF PIPE
N
CHECK VALVE
PRESSURE REGULATOR TO REDUCE PRESSURE TO 7" WC.
SHUT -OFF VALVE
VERIFY REQUIREMENTS FOR METERING AND PIPING WITH GAS COMPANY.
CONTRACTOR SHALL PAY ALL GAS COMPANY FEES FOR INSTALLATION.
USE WELDED OR SCREWED PIPE AND FITTINGS PER PLUMBING SPECS.
PROVIDE AN INDIVIDUAL VENT ON ALL FLOOR DRAINS. INSTALL VENT
IN PARTITION OR CHASE WHERE SHOWN ON PLAN. HORIZONTAL VENT
BELOW FLOOR IS NOT PERMITTED. OTHER VENTING METHODS MAY BE
USED IF APPROVED BY LOCAL CODE.
A • - a
UNLIMITED DISTANCE
WHERE ENLARGED WASTE
LINE IS USED AS A
COMBINATION DRAIN
AND VENT SYSTEM.
PROVIDE TRAP PRIMER
CONCRETE FLOOR
1 a•
MEMBRANE CLAMP-
ING COLLAR AND
SEEPAGE PAN
MAXIMUM TAILPIECE
LENGTH IS 2 FEET
SLOPE WASTE AT
TWO PERCENT
ON 3" WASTI
ON 2" WASTE
LOCATE FLOOR DRAINS WHERE SHOWN ON DIMENSIONED ARCHITEC-
TURAL PLAN. IF FLOOR STRUCTURE INTERFERES WITH FLOOR DRAIN,
MOVE SIDEWAYS IF POSSIBLE. OTHERWISE MOVE BACK. ALWAYS LOCATE
WHERE EASILY ACCESSIBLE, BUT NOT IN FOOT TRAFFIC. IF SITUATION
IS FLOOR SLAB ON GRADE. PROVIDE BACKFILL PER SPECIFICATIONS.
IF CONCRETE FLOOR IS NOT EXISTING, SET DRAIN IN PLACE AND POUR
AROUND IT. IF CONCRETE FLOOR IS EXISTING, SAW CUT OR CORE DRILL
IT. SET DRAIN BODY IN PLACE AND POUR AROUND IT. RECESS TOP OF
FLOOR DRAIN 1/2" BELOW FLOOR SURFACE AND SLOPE FLOOR TO IT.
PLUMBING NOTES
1. ALL WORKMANSHIP AND MATERIALS SHALL BE IN STRICT ACCORDANCE WITH FBC 2004-
APPLICABLE LOCAL CODES, RULES AND ORDINANCES.
2. PLUMBING CONTRACTOR SHALL VISIT THE JOB SITE AND THOROUGHLY FAMILIARIZE
HIMSELF WITH ALL EXISTING CONDITIONS.
3. ALL MATERIALS SHALL BE NEW.
4. ALL WORK SHALL BE PERFORMED BY A LICENSED PLUMBING CONTRACTOR IN A FIRST
CLASS WORKMANLIKE MANNER. THE COMPLETED SYSTEM SHALL BE FULLY OPERATIVE. ALL
EXCAVATION AND BACKFILL AS REQUIRED FOR THIS PHASE OF CONSTRUCTION SHALL BE
A PART OF THIS CONTRACT.
5. REQUIRED INSURANCE SHALL BE PROVIDED BY THE PLUMBING CONTRACTOR FOR PROTECTION
AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK.
6. PLUMBING CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, FEES. INSPECTION AND
TESTS, PLUMBING CONTRACTOR TO OBTAIN PERMIT AND APPROVED SUBMITTALS PRIOR TO
BEGINNING WORK OR ORDERING EQUIPMENT. PLUMBING CONTRACTOR MUST BE PRESENT FOR
ALL INSPECTIONS OF HIS WORK BY REGULATORY AUTHORITIES.
7. DRAWINGS ARE DIAGRAMMATIC. DO NOT SCALE FOR THE EXACT LOCATION OF FIXTURES,
PIPING, EQUIPMENT, ETC.
8. THE WORK
ROGRESSS OF CONSTRUCTION. OTHER IN
STRUCTION. REP ANY DISCREPANCY M ENGINEER/ARCHITECT
CT
PRIOR TO BEGINNING CONSTRUCTION.
9. VERIFY LOCATION, SIZE, DIRECTION OF FLOW AND INVERTS OF ALL EXISTING UTILITIES
PRIOR TO BEGINNING OF CONSTRUCTION. ADVISE ENGINEER OF ANY DISCREPANCIES.
10. WATER DISTRIBUTION PIPING ABOVE AND BELOW GROUND SHALL BE TYPE "L' COPPER.
COORDINATE WITH LOCAL JURISDICTION FOR ADDITIONAL REQUIREMENTS.
PROVIDE ALTERNATE FOR CPVC PIPING EQUAL TO BFGOODRICH 'FLOWGUARD GOLD" FOR WATER
KNOWN OR DETERMINED TO HAVE ACIDIC CHARACTERISTICS. CONTRACTOR SHALL PERFORM A
WATER TEST TO DETERMINE WATER CHEMISTRY PRIOR TO ANY WORK OR PIPING INSTALLATION
AND SHALL SUBMIT TEST RESULTS TO ENGINEER FOR REVIEW AND APPROVAL
11. SOIL, WASTE, VENT AND RAINWATER PIPING SHALL BE CAST IRON OR PVC, WHERE CODE ALLOWS.
PVC MAY NOT BE USED THRU RATED ASSEMBLIES OR IN PLENUMS.
12. ALL FIXTURES MUST BE PROVIDED WITH READILY ACCESSIBLE STOPS AND APPROPRIATELY
MARKED ACCESS PANELS. COORDINATE LOCATIONS WITH GENERAL CONTRACTOR PRIOR
TO INSTALLATION.
13. FURNISH AND INSTALL APPROVED WATER HAMMER ARRESTORS FOR ALL (GROUP) PLUMBING
FIXTURES, SIZED AND LOCATED PER MANUF.'S INSTALLATION INSTRUCTIONS AND WH -PDI 201.
14. DIELECTRIC COUPLINGS ARE REQUIRED BETWEEN ALL DISSIMILAR METAL IN PIPING AND
EQUIPMENT CONNECTIONS.
15. ISOLATE COPPER PIPE FROM HANGER OR SUPPORTS WITH ISOLATOR PADS OR MATERIAL
16. ALL FIRE RATED FLOOR AND WALL PENETRATIONS SHALL BE PROPERLY PROTECTED FROM
FIRE, SMOKE AND WATER PENETRATION BY FILLING VOIDS BETWEEN PIPE AND WALL/FLOOR
SLEEVES WITH FIRE RATED FOAM, TO ACHIEVE THE SAME RATING AS WALLS OR FLOORS
AS PART OF THE PLUMBER'S WORK. FROM
17 PLUMBING CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND
DEFECTSFOR A PERIOD OF NO LESS THAN ONE (1) YEAR FROM DATE OFIACCEPTANCE BY
OWNER. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE
AND SHALL INCLUDE REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION
WHICH MAY HAVE BEEN DAMAGED.
18. PROVIDE ACCESS PANELS FOR ALL CONCEALED VALVES AND ALL WATER HAMMER
ARRESTORS. ACCESS PANELS IN RATED WALLS MUST MAINTAIN THE SAME RATING AND
MUST MATCH THE FINISH OF THE WALL IN WHICH IT IS INSTALLED.
19. PROVIDE COMBINATION COVER PLATE AND CLEANOUT PLUG OR ACCESS
PANEL FOR ALL WALL CLEANOUTS FINISH TO MATCH FIXTURE TRIM.
20.NO COMBUSTIBLE MATERIAL TO BE USED IN MECHANICAL ROOMS OR IN CEILING SPACES
WHERE USED AS RETURN AIR PLENUMS.
21. NO WATER, SANITARY OR DRAINAGE PIPING PERMITTED IN ELECTRICAL OR ELEVATOR
EQUIPMENT ROOMS.
22.ALL CONTROL VALVES SHALL BE TAGGED AND MARKED. A REPRODUCIBLE DIAGRAM
LOCATING ALL VALVES SHALL BE PROVIDED FOR OWNER /OPERATOR.
23.ALL CONDENSATE DRAIN PIPING SHALL BE TYPE "L" COPPER WITH ARMAFLEX INSULATION
PER TABLE 411.1 F.B.C. 2004 WHERE USED IN A RETURN AIR PLENUM. PVC PIPING WITH
ARMAFLEX INSULATION MAY BE USED IN LOCATIONS WHERE ALLOWED BY LOCAL CODES.
SEE PLUMBING DRAWINGS FOR SIZE AND LOCATION OF PIPING.
24.CONDENSATE LINES SHALL NOT DRAIN ON THE ROOFING SYSTEM OR ANY OF ITS COMPONENTS
AND CONDENSATE LINES NEED NOT COMPLY WITH MIN. CLEARANCE REQUIREMENTS
PER FBC 2004, PAR. 1522.3.5
25.PROVIDE ANGLE STOPS ON ALL WATER SERVICE LINES TO FIXTURES FOR INDIVIDUAL
SHUT -OFF.
26. WATER PIPING INSULATION SHALL BE ARMAFLEX OR EQUAL INSTALLED IN ACCORDANCE
NTH MANUFACTURERS INSTRUCTIONS FOR ALL HOT WATER PIPING. WHERE DOMESTIC
WATER TEMPERATURES CAN CAUSE SWEATING ALL COLD WATER PIPING SHALL BE INSULATED
WITH ARMAFLEX INSULATION. THICKNESS AS PER TABLE 411.1 OF FLORIDA ENERGY CODE.
27. ALL HORIZONTAL RAINWATER PIPING THAT RECEIVES CONDENSATE DISCHARGE FROM AIR
CONDITIONING EQUIPMENT SHALL BE INSULATED WITH 1" THK. ARMAFLEX.
SHOCK
P.D.I. DESIGNATION
ARRESTOR SCHEDULE
MANUF. do MODEL FIXTURE UNITS CONNECTION
A
SIOUX CHIEF 652 -A
1 -11
1/2'
B
SIOUX CHIEF 653 -B
12 -32
3/4"
C
SIOUX CHIEF 654-C
33 -60
1"
ACCESS DOOR REQUIRED. CONFORMS CONFORMS TO ANSI /ASS INSTALLATION 1 N STANDARDS.
SLOPE OF HORIZ. DRAINAGE PIPE
SIZE (Inches) MINIMUM SLOPE (Inch per foot)
2 -1/2 or less
1/4
3 to 6
1/8
8 or larger
1/16
TABLE 704.1 OF THE FLORIDA PLUMBING CODE 2004
PLUMBING SHEET INDEX
SHEM
DEBC F&YrM
POA
PLUMBING NOTES, LEGENDS, AND DETAILS
PO.2
EQUIPMENT SCHEDULE do DETAILS
P2.1
SANITARY PLAN
P3.1
DOMESTIC WATER & GAS PLAN
P5.1
SANITARY ISOMETRICS
P6.1
I DOEMSTIC WATER do GAS ISOMETRICS
PLUMBING FIXTURE SCHEDULE
PLUMBING LEGEND
CO
CLEAN OUT
CARRIER RIER OR MOUNTING OF LAV. WADE MODEL / 5 0 -M36. SUPPLY P UMBER MEXMOODEL 44333ORT
SANITARY SEWER PIPING
FD
FLOOR DRAIN
S' - - - -S
VENT PIPING
CW
DOMESTIC COLD WATER
WADE MODEL / 520
DOMESTIC COLD WATER PIPING
HW
DOMESTIC HOT WATER
WATER CLOSET, FLUSH VALVE BOWL: FLOOR MOUNTED, SIPHON JET ACTION VITREOUS CHINA,
ELONGATED RIM AND 1 -1/2" TOP SPUD, AMERICAN STANDARD 2234.015 MADERA AQUAMETER, 1.6
HOT WATER PIPING (120')
GPF TOILET WITH A SLOAN ROYAL 0111 FLUSH VALVE AND A COMFORT SEAT MODEL / C106C OPEN
NOTES
S- - ---5
HOT WATER PIPING (140')
HB
HOSE BIBB
WITH ELONGATED RIM AND 1 -1/2' TOP SPUD. 18' HIGH AMERICAN STANDARD /3043.102 ELDERLY
NEW CADET AQUAMETER, 1.6 GPF TOILET WITH SLOAN ROYAL /111 FLUSH VALVE AND A COMFORT
SEAT MODEL IS C106C, OPEN FRONT SEAT LESS COVER.
PO 1
S- -CD-S
CONDENSATE PIPING
�Q
GATE VALVE
HEATE R SHALL BE 85 GAL. TURBOCHARGER GAS WATER HEATER.
LOCHINVAR MODEL EPN150 -085, 150,000 BTU/HR NAUTRAL GAS INPUT.
FGNHWATER
i
GAS COCK
�- G -S
GAS PIPING
SPECIFIED FAUCET AND PER ARCHITECTURAL FINISH SCHEDULE.
(4) - ALL FIXTURES SHALL BE ROUGHED IN PER MANUFACTURER CUT SHEET TO MAINTAIN UNIFORMITY.
WATER HAMMER ARRESTER (PDI No.)
S-o-S
PIPE RISE UP
S-} S
PIPE DOWN OR DROP
0 FD
FLOOR DRAIN
F--
CAPPED END OF PIPE
N
CHECK VALVE
�--
POINT OF CONNECTION
GAS SOLENOID VALVE
I
P -TRAP
PLUMBING FIXTURE SCHEDULE
SPECIFICATIONS WERE PREPARED UNDER MY
HANDICAP LAVATORY, AMERICAN STANDARD, DECLYN WALL HUNG LAVATORY MODEL 10321.075.
CONTRACTOR
#
HLAV
CARRIER RIER OR MOUNTING OF LAV. WADE MODEL / 5 0 -M36. SUPPLY P UMBER MEXMOODEL 44333ORT
KNOWLEDGE COMPLY WITH THE STATE BUILDING
INSULATION KIT. MUST MEET A.D.A. CODE.
AND ZONING ORDINANCES.
LAVATORY, AMERICAN STANDARD DECLYN WALL HUNG /0321.075 WHITE W/ SLOAN POLARIS SL -2711
LAV
FAUCET. CONTRACTOR TO SUPPLY CONCEALED ARM SUPPORT CARRIER FOR MOUNTING OF LAVATORY.
STATE REGISTRATION
WADE MODEL / 520
WCO
WALL CLEANOUT, WADE MODEL / 8590 TAPPED PLUG NTH 8480R.
PLUMBING
WATER CLOSET, FLUSH VALVE BOWL: FLOOR MOUNTED, SIPHON JET ACTION VITREOUS CHINA,
ELONGATED RIM AND 1 -1/2" TOP SPUD, AMERICAN STANDARD 2234.015 MADERA AQUAMETER, 1.6
WC
GPF TOILET WITH A SLOAN ROYAL 0111 FLUSH VALVE AND A COMFORT SEAT MODEL / C106C OPEN
NOTES
FRONT SEAT LESS COVER.
HANDICAP WATER CLOSET - FLUSH VALVE BOWL; FLOOR MOUNTED, SIPHON JET, VITEROUS CHINA
HW1C
WITH ELONGATED RIM AND 1 -1/2' TOP SPUD. 18' HIGH AMERICAN STANDARD /3043.102 ELDERLY
NEW CADET AQUAMETER, 1.6 GPF TOILET WITH SLOAN ROYAL /111 FLUSH VALVE AND A COMFORT
SEAT MODEL IS C106C, OPEN FRONT SEAT LESS COVER.
PO 1
URINAL AMERICAN STANDARD, WASHBROOK /8501.010, FLUSH VALVE SLOAN ROYAL /188 -1,
UR
WALL MOUNTED, WHITE URINAL. WALL CARRIER, WADE / 40OAM11.
Drawing No.
HEATE R SHALL BE 85 GAL. TURBOCHARGER GAS WATER HEATER.
LOCHINVAR MODEL EPN150 -085, 150,000 BTU/HR NAUTRAL GAS INPUT.
FGNHWATER
RECIRCULATING PUMP TACO MODEL / 007
L NOTES:
(2) - ALL FIXTURES SHALL COMPLY WITH TABLE 604.4 OF FBC 2004.
3 - ALL FIXTURE TRIM PACKAGES INCLUDING BUT NOT LIMITED TO TRAP, ANGLE STOP, FLUSH VALVE,
SUPPLY TUBES, AND CLEANOUT COVER PLATES SHALL BE OF THE SAME FINISH AS THE ABOVE
SPECIFIED FAUCET AND PER ARCHITECTURAL FINISH SCHEDULE.
(4) - ALL FIXTURES SHALL BE ROUGHED IN PER MANUFACTURER CUT SHEET TO MAINTAIN UNIFORMITY.
�GOQ`l
gG!lwo
O �
Nod yoo
i N
1.
t !ii j
■
rh
- _ MavF rick Architecture &
_ _ - _ .. - = _Design, Ilc.
6675 Westwood Blvd.
Suite 140
Orlando, Florida 32821
T: 407.351.8787
F: 407.351.9254
E:
Info @MaverickArchDes.com
AA. 26000903 AR.
91835
a conceptually
independent forum
M
r
O M
M
•C (6
D2
4-0 •L_
(D O
U) LL
6 •E
M •�
0
�_
rrO^
VJ
m
❑
c Q
o �
a Q
v U
m LL
m �
I HEREBY CERTIFY THAT THESE DRAWINGS AND
SPECIFICATIONS WERE PREPARED UNDER MY
DIRECT SUPERVISION AND TO THE BEST OF MY
KNOWLEDGE COMPLY WITH THE STATE BUILDING
AND ZONING ORDINANCES.
SIGNED
ISSUED FOR PERNIIT Oct O8, 2007
STATE REGISTRATION
ISSUED FOR CONSTRUCTION -
DATE
I{AMM CONSULTING PROJECT' #: 2007 -0307 �� I t , �,,
PLUMBING
PROJECT MANAGER: Nicholas Melisiotis, P.E. }' \ �' t� •�� " -`
1407 West VV<QL't C
Deerfield Sbaft Flonxit''ll,
*a M M
NOTES
Phone 954.949.2200 Fax 954.949.2201 ,
nsu engineer0g @kimmconsulting�.•��mm
Certific iron o£AutliOrita ' #T8189 `•.
l Dlycemb �i% Op7�. ;
RECTOR OF ELECTRICAL INGINEERING
in T. Carter Florida License •• r
PO 1
; RECTOR OF MECHANICAL ENGINEERING !� •• �� .
ircea Pella Florida License #48798 fir, . a ,C • ./
Drawing No.
�1
♦� `r �•I 1 l 11tV
1
I i