07-1661-069�k
w,
5
i
t
y
REFLECTED CEILING LEGEND
SYMBOL
DESCRIPTION
SPECIFICATION
LAMPS/FIXT.
CONTACT
IF A PROBLEM IS ENCOUNTERED IN COMPLYING WITH THIS REQUIREMENT, CONTRACTOR SHALL NOTIFY
RECESSED DISKUS PUCK LIGHT
ABQEE:_ DISKUS PUCK LIGHT
(1) 20W HOLOGEN LAMP
GENLYTE
1 PURPLE. GROUNDED (NEUTRAL) CONDUCTORS. GREY. GROUNDING CONDUCTORS SHALL BE GREEN.
TOTAL QTY.: VERIFY
DRRS 12V, 20W BI -PIN HALOGEN
THE CONTRACTOR SHALL VISIT THE JOB SITE PRIOR TO BID AND FAMILIARIZE HIMSELF WITH ALL
ROCHELLE LEWIS
A
PULL POINTS (EXCEPT LB'S OR LBD'S) USING COLOR MARKERS OR PLASTIC TAPE MANUFACTURED
THE COST THEREOF.
FOR THE PURPOSE.
(407) 629 -5644
B. WIRING METHODS
CYLINDER CAN LIGHT
JUNO: /TC920 -8258 6' DEEP BAFFLE
ALLOW 75W
JUNO LIGHTING
UTTUZED IN THIS PROJECT.
TOTAL QTY: VERIFY
PAR 38 W/150 WATT PAR 38 LAMP
RAIN TIGHT COMPRESSION TYPE OR ALL STEEL CONCRETE TIGHT SET SCREW TYPE.
847.827.9880
2. SCHEDULE 40 PVC CONDUIT, WITH FITTINGS AND COUPUNGS APPROPRIATE FOR THE USE, SHALL
3. STANDARD FOR THE INSTALLATION, MAINTENANCE AND USE OF LOCAL PROTECTIVE SIGNALING
CONTACT ROGER ANGELKORTE- JUNO
SYSTEMS (NFPA -72), 2007 EDITION
3. TYPE MC CABLE WITH ALUMINUM ARMOR AND INTERNAL GROUND IS ACCEPTABLE FOR
8
USE AS GENERAL BRANCH CIRCUIT WIRING FOR CIRCUITS 20 AMPERES OR LESS AND CONCEALED
LIGHTING (847)827 -9880
IN WALLS OR ABOVE SUSPENDED CEILING AND AS APPROVED BY THE AUTHORITY HAVING
6. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
JURISDICTION.
LYTECASTER RECESSED DOWNUGHT
LIGHTOLIER: LYTECASTER RECESSED
(1) 75W MR18
GENLYTE
9. FLORIDA BUILDING CODE. 2004 EDITION WITH 2006 REVISION
TOTAL QTY: VERIFY
DOWN LIGHT
WORKMANLIKE MANNER. THE COMPLETED SYSTEM SHALL BE FULLY OPERATIVE.
ROCHELLE LENS
O
C
12. ADDITIONALLY, DESIGNS, WORK PRACTICES AND CONDITIONS MUST CONFORM WITH THE
413MTX /4020MREX
OCCUPATIONAL SAFETY AND HEALTH ACT OF 1970 (OSHA)
(407) 629 -5644
DO NOT SCALE THE ELECTRICAL DRAWINGS. REFER TO ARCHITECTURAL PLANS AND ELEVATIONS
CUSTOM ACRYLIC LIGHT FIXTURE
TBD
ALLOW 4000W
2ND AVE
DEVICES, FOR ALL OUTLETS AS INDICATED.
TOTAL QTY: 1
H. MATERIALS, PRODUCTS, AND EQUIPMENT, INCLUDING ALL COMPONENTS THEREOF. SHALL BE NEW
AND PROVIDE ALL REQUIREMENTS NECESSARY FOR EQUIPMENT TO BE PLACED IN PROPER WORKING ORDER.
AND SUCH AS APPEAR ON THE UL UST OF APPROVED ITEMS AND SHALL MEET OR EXCEED THE
D
REQUIREMENTS OF NEC, NEMA, AND IECE.
PERIOD OF NOT LESS THAN ONE YEAR FROM DATE OF ACCEPTANCE.
I. CONTRACTOR SUBMITTALS:
800.843.1602
I, SUBMIT AT LEAST FIVE (5) SETS OF SHOP DRAWINGS OR CUT SHEETS OF LIGHTING
TRACK LIGHT
LIGHTOLIER, I RI R' TANGENT TRACK LIGHTING
50W MAX
GENLYTE
(D
TOTAL QTY: 4 LOCATIONS
SYSTEM
FX16S 12 V MR16 HALOGEN
FLORIDA BUILDING CODE. ARTICLE 13.413.1
ROCHELLE LENS
(407) 629 -5644
E
THE CONTRACTOR IS TO FURNISH, INSTALL AND CONNECT COMPLETE.
K. ALL LAY -IN LIGHTING FIXTURES SHALL BE SECURED TO THE SUSPENDED CEILING GRID AT EACH CORNER.
L CONTRACTOR SHALL COORDINATE WITH MECHANICAL DRAWINGS AND PROVIDE ALL NECESSARY CONTROL
PART 2 - PRODUCTS
DECORATIVE PENDANT
YLIGHTTNG: NELSON SAUCER LAMP
ALLOW 75W
YUGHTING
F
TOTAL QTY: VERIFY
MEDIUM 9.5'x25'DIA.
ELECTRICAL METALLIC TUBING (EMT) E
( T) SHALL B OF BEST QUALITY STEEL, SMOOTH INSIDE AND OUT
888.428.9289
AND SHALL BE HOT -DIPPED GALVANIZED.
DECORATIVE PENDANT
YL1GH11NG: NELSON CIGAR LAMP MEDIUM
"H01.5'DIA.
ALLOW 75W
YUGHTING
G
TOTAL QTY: VERIFY
21
PANELBOARDS:
866.428.9289
1. CURRENT CARRYING BUSES SHALL BE COPPER. GROUND BUS BARS SHALL BE COPPER.
DECORATIVE PENDANT
OXYGEN LIGHTING: MASSIMA/PENDANT
ALLOW 50OW
OXYGEN LIGHTING
• INCREASE WIRE BY 3 WIRE SIZES FOR RUNS FROM 150 FT. TO 230 FT.
TOTAL QTY: VERIFY
2- 615 -59
4. ALL CIRCUIT BREAKERS FEEDING MECHANICAL EQUIPMENT SHALL BE HACR TYPE.
877.607.0203
5. A.I.C. RATINGS SHALL BE AS INDICATED ON PANELBOARD SCHEDULES.
LUG SIZE RESTRICTIONS.
7"DIAM. x 17'H
P. THE CONTRACTOR SHALL SCHEDULE ALL REQUIRED DOWN TIME FOR THE OWNERS CONFIRMATION.
ENGRAVED LETTERING FOR PANEL IDENTIFICATION.
Q. ANY CONFLICTS AND DESCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER BEFORE
7. ALL PANELBOARDS SHALL BE PROVIDED WITH TYPE- WRITTEN DIRECTORY OF BRANCH CIRCUIT
FINISH: SILVER GRAPHITE, SATIN WHITE
DESIGNATIONS.
H
TRIPLEX GLASS
OVERLOAD RELAYS IN EACH PHASE. PROVIDE MAGNETIC STARTERS WITH 'H -O -A' SWITCH.
DECORATIVE PENDANT
AI 1 LMINARE: LARGE RECTANGULAR
ALLOW 50OW
ALLUMINARE
WIRING DEVICES (GENERAL PURPOSE RECEPTACLES AND WALL SWITCHES) SHALL BE WHITE COLOR UNLESS
TOTAL QTY: VERIFY
DINING PENDANT
U
WWW.ALLUMINARE.COM
SHADE: OFF -WHITE LINEN, SIZE: 26'W
866.526.7748
X 14 -D,
2
q
c
y
o
w-
9' ADJUSTABLE CORD, 15OW
BARTOP LAMP
'MENA LIGHTING: ALICE 2423
ALLOW 75W
SIENA LIGHTING
J
TOTAL QTY: VERIFY
13"H x 19 "W
408.573.7450
RECESSED DOWNLIGHT EXTERIOR RATED
BUILDING STANDARD EXTERIOR LIGHTING
ALLOW 75W
OK
TOTAL QTY: VERIFY
�
U
U
W
DECORATIVE PENDANT
SEGA/US. LIMBURG COLLECTION L4116,
ALLOW IDOW
SESCO LIGHTING
TOTAL QTY: 2
10OW
0
DAN SCHULMAN
L1
SIZE: 7 -7/8" X 77L
407.629.6100
DECORATIVE PENDANT
BEGA/USL UMBURG COLLECTION L4117,
ALLOW IOOW
SESCO LIGHTING
TOTAL QTY: 1
10OW
DAN SCHULMAN
L2
SIZE: 9 -7/8" X 79L
407.629.6100
DECORATIVE PENDANT
BEG S: UMBURG COLLECTION L4118,
ALLOW 100W
SESCO LIGHTING
TOTAL QTY: 2
100W
DAN SCHULMAN
L3
d
z
SIZE: 11 -3/4" X 79'L
407.629.6100
DECORATIVE PENDANT
BEGAQIS- UMBURG COLLECTION L4119,
ALLOW IOOW
SESCO LIGHTING
TOTAL QTY: 1
10OW
DAN SCHULMAN
L4
MY
SIZE: 13 -3/4" X 79 "L
KNOWLEDGE COMPLY WITH THE STATE BUILDING
407.629.6100
DECORATIVE PENDANT
BEGAa1S� UMBURG COLLECTION L4341,
ALLOW IOOW
SESCO LIGHTING
DATE
TOTAL QTY: 1
10OW
DAN SCHULMAN
L5
EOO 1
SIZE: 15 -3/4' X 81L
Drawing No.
407.629.6100
DECORATIVE PENDANT
LUMETTA: 48' DRUM PENDANT
ALLOW 50OW
LUMETTA
M
TOTAL QTY: 3
LUMENATE COLOR: D4 GOLD
40 &573.7450
DECORATIVE PENDANT
YLIGHTTNG: Eaay Pendant Light -W1 Gray
ALLOW 2OW
YUGHTING
TOTAL QTY; 40
866.428.9289
2' X 4' FLUORESCENT
L IGHTOUER: DEEPCEL DPA2G18LS332
(3) 32W T8 TUBES
GENLYTE
IL
OFFICE AREAS
FLUORESCENT
ROCHELLE LENS
VERIFY QTY
W/ PARABOLIC LOUVER
(407) 629 -5644
2' X 4' FLUORESCENT
LIGHTOLIER XPXA 2'X4' LENS RECESSED
(3) 32W T8 TUBES
GENLYTE
MTCHYN, STORAGE. HALL AREAS
ROCHELLE LEWIS
�
VERIFY QTY
XP /XA 32
XP/XA332
(407) 6
(407) 829 -5844
2' X 4' FLUORESCENT
LIGHTOLIER XPXA 2'X4' LENS RECESSED
(3) 32W T8 TUBES
GENLYTE
STORAGE. AREAS WITH
ROCHELLE LEWIS
L999FU
EMERGENCY BA PACK
XP/XA332
(407) 629-5644
(1400 LUMENS OUTPUT)
COVE UGH71NG / BACK UGH71NG FOR
CELESTIAL LIGHTING: FESTOON
5 WATTS / BULB
GENLYTE
MIRRORS
STANDARD 5W LAMPS SPACED 2.4' O.C.
LOW VOLTAGE
ROCHELLE LEWIS
5 LAMPS PER FOOT
(407) 629 -5544
EXTERIOR GRADE PADDLE FANS
DESIGN WITHIN REACH: EXTERIOR
DESIGN WITHIN REACH
TOTAL QTY: 3
CEILING FAN - LAPA
305.604.0037
MODEL: LAP -BN 42 NK NL 003
DUAL FACE THERMOPLASTIC EXIT
SIGN/UGHT WITH WHITE HOUSING AND
RED LETTERS. PROVIDE DIRECTIONAL
®X1
ARROWS AS INDICATED. PROVIDE
FIXTURE WITH 90 MINUTE BATTERY
BACKUP.
DUAL FACE THERMOPLASTIC EXIT
SIGN/LIGHT WITH WHITE HOUSING AND
RED LETTERS PROVIDE DIRECTIONAL
ARROWS AS INDICATED. PROVIDE
FIXTURE WITH 90 MINUTE BATTERY
BACKUP.
REFLECTED CEILING PLAN NOTES:
1. ALL QUANTITIES ARE AS SHOWN ON PLAN, CONTRACTOR MAY WANT TO ORDER
ADDITIONAL AMOUNTS OF SOME FIXTURES.
2. TRACK LIGHTING AND HEADS NEED TO BE VERIFIED AS PER SITE FOR PLACEMENT
AND ADJUSTMENT.
3. ALL DOWN AND TRACK LIGHTS ARE TO BE ON SLIDE DIMMERS.
4. DJ BOOTH EQUIPMENT AND AMP RACKS MUST BE GROUNDED TOGETHER AND
ISOLATED FROM ALL OTHER POWERED EQUIPMENT.
ELECTRICAL SPECIFICATIONS
0 -O4"07
SHEM
PART 1 - GENERAL
THE CONTRACTOR SHALL SUPPLY AND INSTALL ALL NEW ELECTRICAL WORK INDICATED.
PART 3 - EXECUTION
A. COLOR CODING OF CONDUCTORS SHALL BE AS FOLLOWS:
CONSTRUCTION SHALL BE IN ACCORDANCE WITH DRAWINGS AND APPLICABLE SPECIFICATIONS.
1. 208/120 VOLTS, 3 PHASE, 4-WIRE SYSTEM: UNGROUNDED CONDUCTORS: 1 BLACK, 1 RED AND 1
IF A PROBLEM IS ENCOUNTERED IN COMPLYING WITH THIS REQUIREMENT, CONTRACTOR SHALL NOTIFY
BLUE. GROUNDED (NEUTRAL) CONDUCTOR: WHITE. GROUNDING CONDUCTORS SHALL BE GREEN.
THE ARCHITECT/ENGINEER AS SOON AS POSSIBLE AFTER DISCOVERY OF THE PROBLEM AND
2. 480/277 VOLT. 3- PHASE, 4 -WIRE SYSTEM: UNGROUNDED CONDUCTORS: 1 BROWN, 1 YELLOW, AND
SHALL NOT PROCEED WITH THAT PORTION OF THE WORK UNTIL ARCHITECT/ENGINEER HAS DIRECTED
1 PURPLE. GROUNDED (NEUTRAL) CONDUCTORS. GREY. GROUNDING CONDUCTORS SHALL BE GREEN.
CORRECTIVE ACTION TO BE TAKEN.
3. BRANCH CIRCUIT WIRING (/6 AND SMALLER) SHALL BE COLOR CODED BY CONTINUOUS INSULATION
THE CONTRACTOR SHALL VISIT THE JOB SITE PRIOR TO BID AND FAMILIARIZE HIMSELF WITH ALL
COLOR AND FEEDERS AND SERVICES (/4 AND LARGER) SHALL BE CODED AT ALL JUNCTION OR
CONDITIONS AFFECTING ELECTRICAL AND COMMUNICATIONS INSTALLATION AND MAKE PROVISIONS AS TO
PULL POINTS (EXCEPT LB'S OR LBD'S) USING COLOR MARKERS OR PLASTIC TAPE MANUFACTURED
THE COST THEREOF.
FOR THE PURPOSE.
ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRIC
B. WIRING METHODS
CODE (AS ADOPTED BY THE AUTHORITY HAVING JURISDICTION) AND ALL CODES AND ORDINANCES OF THE
1. ALL CONDUCTORS SHALL BE INSTALLED IN ELECTRICAL METALLIC TUBING (EMT) UNLESS
AUTHORITY HAVING JURISDICTION. THE SPECIFICATION, CODES AND STANDARDS LISTED BELOW ARE
OTHERWISE NOTED, SPECIFIED OR AS SPECIFICALLY PROHIBITED BY THE AUTHORITY HAVING
UTTUZED IN THIS PROJECT.
JURISDICTION. ALL FITTINGS AND COUPLINGS FOR EMT CONDUIT SHALL BE ALL STEEL
1. NATIONAL ELECTRICAL CODE (NFPA -70), 2005 EDITION
RAIN TIGHT COMPRESSION TYPE OR ALL STEEL CONCRETE TIGHT SET SCREW TYPE.
2. CODE FOR SAFETY TO LIFE (NFPA -101), 2006 EDITION
2. SCHEDULE 40 PVC CONDUIT, WITH FITTINGS AND COUPUNGS APPROPRIATE FOR THE USE, SHALL
3. STANDARD FOR THE INSTALLATION, MAINTENANCE AND USE OF LOCAL PROTECTIVE SIGNALING
BE INSTALLED UNDERGROUND OR BELOW SLABS ON GRADE.
SYSTEMS (NFPA -72), 2007 EDITION
3. TYPE MC CABLE WITH ALUMINUM ARMOR AND INTERNAL GROUND IS ACCEPTABLE FOR
4. UNDERWRITERS' LABORATORIES (UL)
USE AS GENERAL BRANCH CIRCUIT WIRING FOR CIRCUITS 20 AMPERES OR LESS AND CONCEALED
5. NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
IN WALLS OR ABOVE SUSPENDED CEILING AND AS APPROVED BY THE AUTHORITY HAVING
6. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
JURISDICTION.
7. FEDERAL SPECIFICATION (FED. SPEC.)
C. ELECTRICAL SYSTEM SHALL BE COMPLETE AND EFFECTIVELY GROUNDED AS REQUIRED BY THE LATEST
& INSULATED POWER CABLE ENGINEERS ASSOCIATION (IPCEA)
EDITION OF THE WELECTRICAL CONTRACTOR AND LOCAL CODES.
9. FLORIDA BUILDING CODE. 2004 EDITION WITH 2006 REVISION
D. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST CLASS
10. INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS (IEEE)
WORKMANLIKE MANNER. THE COMPLETED SYSTEM SHALL BE FULLY OPERATIVE.
11. CITY OF SOUTH MIAMI BUILDING CODE. (2006 AMENDMENTS TO 2004 FLORIDA BUILDING CODE)
E. ALL WORK SHALL BE COORDINATED NTH OTHER TRADES TO AVOID INTERFERENCE WITH THE PROGRESS
12. ADDITIONALLY, DESIGNS, WORK PRACTICES AND CONDITIONS MUST CONFORM WITH THE
OF CONSTRUCTION.
OCCUPATIONAL SAFETY AND HEALTH ACT OF 1970 (OSHA)
F. THE ELECTRICAL INSTALLATION SHALL MEET ALL STANDARD REQUIREMENTS OF POWER AND TELEPHONE
DO NOT SCALE THE ELECTRICAL DRAWINGS. REFER TO ARCHITECTURAL PLANS AND ELEVATIONS
COMPANIES, AND SHALL BE FULLY COORDINATED WITH THEM PRIOR TO COMMENCEMENT OF WORK.
FOR EXACT LOCATION OF ALL EQUIPMENT. CONFIRM WITH OWNER'S REPRESENTATIVE.
G. PROVIDE AND INSTALL CONDUIT, CONDUCTORS, PULL WIRES, BOXES, COVER PLATES, AND HARING
IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. THE
DEVICES, FOR ALL OUTLETS AS INDICATED.
CONTRACTOR IS EXPECTED TO FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL SYSTEM
H. MATERIALS, PRODUCTS, AND EQUIPMENT, INCLUDING ALL COMPONENTS THEREOF. SHALL BE NEW
AND PROVIDE ALL REQUIREMENTS NECESSARY FOR EQUIPMENT TO BE PLACED IN PROPER WORKING ORDER.
AND SUCH AS APPEAR ON THE UL UST OF APPROVED ITEMS AND SHALL MEET OR EXCEED THE
CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS FROM A
REQUIREMENTS OF NEC, NEMA, AND IECE.
PERIOD OF NOT LESS THAN ONE YEAR FROM DATE OF ACCEPTANCE.
I. CONTRACTOR SUBMITTALS:
CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE AND SHALL INCLUDE
I, SUBMIT AT LEAST FIVE (5) SETS OF SHOP DRAWINGS OR CUT SHEETS OF LIGHTING
REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED
FIXTURES, SWITCHES. AND OTHER ELECTRICAL ITEMS FOR APPROVAL BY ENGINEER /ARCHITECT.
THERE BY.
ALL REQUIRED INSURANCE SHALL BE PROVIDED FOR PROTECTION AGAINST PUBLIC LIABILITY AND
2, AS -BUILT ELECTRICAL DRAWINGS SHALL BE PROVIDED TO THE OWNER AS REQUIRED BY FLORIDA
BUILDING CODE. ARTICLE 13.413.1
PROPERTY DAMAGE FOR THE DURATION OF THE WORK.
CONTRACTOR SHALL PAY FOR ALL PERMITS, FEES, INSPECTIONS AND TESTING. CONTRACTOR
3. OPERATING AND MAINTENANCE MANUALS SHALL BE PROVIDED TO THE OWNER AS REQUIRED BY
TO OBTAIN PERMIT AND APPROVED SUBMITTALS PRIOR TO BEGINNING WORK OR ORDERING EQUIPMENT.
FLORIDA BUILDING CODE. ARTICLE 13.413.1
THE TERM 'PROVIDE' USED IN THE CONSTRUCTION DOCUMENTS AND SPECIFICATIONS SHALL MEAN THAT
J. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING REQUIRED OF HIS WORK.
THE CONTRACTOR IS TO FURNISH, INSTALL AND CONNECT COMPLETE.
K. ALL LAY -IN LIGHTING FIXTURES SHALL BE SECURED TO THE SUSPENDED CEILING GRID AT EACH CORNER.
L CONTRACTOR SHALL COORDINATE WITH MECHANICAL DRAWINGS AND PROVIDE ALL NECESSARY CONTROL
PART 2 - PRODUCTS
WIRING.
MINIMUM WIRE SIZE SHALL BE f12 A.W.G. (EXCEPT AS NOTED OTHERWISE FOR CONTROL WIRING). ALL
M. ALL ELECTRICAL POWER WIRING FOR THE HVAC SYSTEM INCLUDING WIRING THRU LINE VOLTAGE CONTROL
CONDUCTORS SHALL BE 98X CONDUCTIVITY, COPPER WITH - THHN- THWIN- INSULATION UNLESS OTHERWISE
DEVICES SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR.
NOTED.
N. VOLTAGE DROP
ELECTRICAL METALLIC TUBING (EMT) E
( T) SHALL B OF BEST QUALITY STEEL, SMOOTH INSIDE AND OUT
1. CONDUCTORS FOR ALL FEEDERS SHALL BE INCREASED FROM SIZES INDICATED ON DRAWINGS TO
AND SHALL BE HOT -DIPPED GALVANIZED.
PREVENT VOLTAGE DROP EXCEEDING 2%.
RIGID NONMETALLIC CONDUIT SHALL BE SCHEDULE 40 PVC.
2. CONDUCTORS FOR ALL BRANCH CIRCUITS SHALL BE INCREASED FROM SIZES INDICATED ON
OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS, CAST ALLOY WITH THREADED HUBS
DRAWINGS TO PREVENT VOLTAGE DROP EXCEEDING 3%. FROM THE FURTHEST DEVICE.
IN WET OR DAMP LOCATIONS AND SPECIAL ENCLOSURES FOR OTHER CLASSIFIED AREAS.
ALL MATERIALS SHALL BE NEW AND BEAR UNDERWRITERS' LABELS WHERE APPLICABLE.
3
. DETERMINING CONDUCTOR SIZES SHALL BE BASED ON 80X OF THE BREAKER RATING
PANELBOARDS:
4. FOR DETERMINATION OF WIRE SIZE FOR BID PURPOSES.
1. CURRENT CARRYING BUSES SHALL BE COPPER. GROUND BUS BARS SHALL BE COPPER.
• INCREASE MARE BY 1 WIRE SIZE FOR RUNS 60 FT. TO 100 FT.
2. ALL CIRCUIT BREAKERS SHALL BE BOLT ON. PLUG -IN BREAKERS ARE NOT ACCEPTABLE.
INCREASE WIRE BY 2 WIRE SIZES FOR RUNS 100 FT. TO 150 FT.
& CIRCUIT BREAKERS USED AS SWITCHES IN FLUORESCENT OR HID LIGHTING CIRCUITS SHALL
• INCREASE WIRE BY 3 WIRE SIZES FOR RUNS FROM 150 FT. TO 230 FT.
BE LISTED AND MARKED "SWD' OR 'HID' AS REQUIRED.
0. THE CONTRACTOR SHALL CONFIRM WITH THE ELECTRICAL UTILITY COMPANY ANY AND ALL
4. ALL CIRCUIT BREAKERS FEEDING MECHANICAL EQUIPMENT SHALL BE HACR TYPE.
REQUIREMENTS SUCH AS: TRANSFORMER SIZE AND LOCATION OR SERVICE POINT, CONDUIT ENTRY AND
5. A.I.C. RATINGS SHALL BE AS INDICATED ON PANELBOARD SCHEDULES.
LUG SIZE RESTRICTIONS.
S. ALL PANELBOARDS SHALL BE FURNISHED WITH PLASTIC LAMINATE NAMEPLATES WITH 1/4"
P. THE CONTRACTOR SHALL SCHEDULE ALL REQUIRED DOWN TIME FOR THE OWNERS CONFIRMATION.
ENGRAVED LETTERING FOR PANEL IDENTIFICATION.
Q. ANY CONFLICTS AND DESCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER BEFORE
7. ALL PANELBOARDS SHALL BE PROVIDED WITH TYPE- WRITTEN DIRECTORY OF BRANCH CIRCUIT
PROCEEDING WITH ANY WORK.
DESIGNATIONS.
DISCONNECT SWATCHES SHALL BE H.P. RATED, HEAVY DUTY, QUICK -MAKE, QUICK- BREAK.
MOTOR STARTERS SHALL BE MANUAL OR MAGNETIC AS INDICATED ON THE ELECTRICAL DRAWINGS, WITH
OVERLOAD RELAYS IN EACH PHASE. PROVIDE MAGNETIC STARTERS WITH 'H -O -A' SWITCH.
ENCLOSURES SHALL BE NEMA -1 FOR INDOOR LOCATIONS. NEMA 3R FOR OUTDOOR LOCATIONS
OR AS OTHERWISE NOTED.
WIRING DEVICES (GENERAL PURPOSE RECEPTACLES AND WALL SWITCHES) SHALL BE WHITE COLOR UNLESS
OTHERWISE NOTED. FACEPLATES SHALL BE SMOOTH, WHITE NYLON UNLESS OTHERWISE NOTED.
U
TELEPHONE WOOD BACKBOARD
4'Wx8'Hx3 /4" BC PLYWOOD
PAINT WITH TWO COATS OF
FIRE RETARDANT WHITE PAINT
TO BRANCH
CIRCUIT PANEL
MOUNT RECEPTACLE -
DIRECTLY TO TELEPHONE
BOARD
GROUND BAR, SEE DETAIL -
THIS SHEET.
1 /2 GROUND
TO NEAREST EFFECTIVELY
GROUNDED BUILDING
STRUCTURAL STEEL MEMBER.
EEO
1 -2" CONDUIT WITH PULL
STRING TO MAIN
TELEPHONE BOARD ON
THE FIRST FLOOR -RM 115
TERMINATE CONDUIT WITH
INSULATED BUSHING
10"
!EQUIPMENT GROUN
/2' 0 0 0
0 1110.
-MOUNTED AT BASE OF
PLYWOOD BACKBOARD
3' -0' A.F.F.
1/4" COPPER BAR
GLAS11C INSULATOR
PLYWOOD BACKBOARD
SIDE VIEW
TELEPHONED GROUNDING BAR
N TO SCALE
3/8" HILTI INSERT HDI -3/8 '. (TYPICAL OF 4)
a a
PRIMARY 3/8'
FEEDER THREADED ROD
FUSED DISCONNECT
FLEXIBLE METAL SWITCH. MOUNT ON
CONDUIT STEEL CHANNEL ON
SIDE OF TRANSFORMER.
RIBBED
RUBBER
VIBRATION FLEXIBLE METAL
ISOLATER CONDUIT
3x5 / CHANNEL
SECONDARY
FEEDER
FRONT VIEW SIDE VIEW
TRANSFORMER MOUNTING DETAIL
NOT TO SCALE
ELECTRICAL SHEET INDEX
SHEM
DEBCRPTION
EO.1
ELECTRICAL NOTES, LEGEND do INDEX
E2.1
ELECTRICAL LIGHTING PLAN
E3.1
ELECTRICAL POWER PLAN
E3.2
EQUIPMENT SCHEDULE
E3.3
ROOF POWER PLAN
E4.1
PART POWER PLAN
E4.2
PART POWER PLAN
E4.3
PART POWER PLAN
E5.1
ELECTRICAL RISER DIAGRAM
EGA
ELECTRICAL PANEL SCHEDULES
E6.2
ELECTRICAL PANEL SCHEDULES
ELECTRICAL SYMBOLS
0 TELEPHONE OUTLET WITH 3/4" CONDUIT STUBBED OUT FROM WALL 6- ABOVE CEILING.
MOUNT 18' A.F.F. TO CENTER LINE OF OUTLET UNLESS OTHERWISE NOTED.
TELEPHONE/DATA OUTLET WITH 3/4' CONDUIT STUBBED OUT FROM WALL 6" ABOVE CEILING.
0 MOUNT 18" A.F.F. TO CENTER LINE OF OUTLET UNLESS OTHERWISE NOTED.
® TELEPHONE/DATA OUTLET, RECESSED FLOOR MOUNTED, WITH 3/4' CONDUIT RUN TO THE
NEAREST STUD WALL AND STUBBED OUT FROM WALL 6" ABOVE CEILING. PROVIDE BRASS
COVER PLATE AND CARPET FLANGE.
TELEVISION OUTLET WITH 3/4' CONDUIT STUBBED OUT FROM WALL 6- ABOVE CEILING.
MOUNT AT 18' A.F.F. TO CENTER LINE OF OUTLET UNLESS OTHERWISE NOTED.
(f1) 20 AMP DUPLEX RECEPTACLE (NEMA 5 -20R) MOUNTED AT 18" A.F.F. TO CENTER LINE OF
Ott OUTLET UNLESS NOTED OTHERWISE.
20 AMP QUADRUPLEX RECEPTACLE (NEMA 5 -20R) MOUNTED AT 18" A.F.F. TO CENTER LINE
OF OUTLET UNLESS NOTED OTHERWISE.
gpGFI 20 AMP DUPLEX RECEPTACLE (NEMA 5 -20R) WITH GROUND FAULT CIRCUIT INTERRUPTER.
T�TT MOUNT AT 18" A.F.F. TO CENTER LINE OF OUTLET. UNLESS NOTED OTHERWISE.
{ 20 AMP DUPLEX RECEPTACLE (NEMA 5 -20R) MOUNTED ABOVE COUNTER
TT SEE ARCHITECTUAL DRAWINGS FOR SPECIFIC REQUIREMENTS.
(n 20 AMP DUPLEX RECEPTACLE (NEMA 5 -20R) MATH DEDICATED GROUND, MOUNT AT 18' A.F.F.
Tiff TO CENTERLINE OF OUTLET UNLESS OTHERWISE NOTED.
20 AMP DUPLEX RECEPTACLE (NEMA 5 -20R) WITH ISOLATED GROUND, MOUNT AT 18- A.F.F.
TO CENTERLINE OF OUTLET UNLESS OTHERWISE NOTED.
20 AMP QUADRUPLEX RECEPTACLE (NEMA 5 -20R) WITH ISOLATED GROUND, MOUNT AT 18-
A.F.F. TO CENTERLINE OF OUTLET UNLESS OTHERWISE NOTED.
® 20 AMP DUPLEX RECEPTACLE (NEMA 5 -20R). RECESSED FLOOR MOUNTED. PROVIDE BRASS
COVER PLATE AND CARPET FLANGE.
20 AMP DUPLEX RECEPTACLE (NEMA 5 -20R), CEILING MOUNTED.
SPECIAL- PURPOSE RECEPTACLE
JUNCTION BOX FLOOR MOUNTED
d0 JUNCTION BOX
® SPECIAL PURPOSE RECEPTACLE MOUNTED BELOW RAISE FLOOR.
4 EXHAUST FAN. SEE MECHANICAL DRAWINGS FOR SPECIFICATIONS.
SINGLE POLE, 20 AMP. SWITCH. MOUNT 42' A.F.F. TO CENTERLINE OF SWITCH UNLESS
OTHERWISE NOTED.
$3 3 -WAY, 20 AMP, SWITCH. MOUNT 42' A.F.F. TO CENTERLINE OF SWITCH UNLESS
OTHERWISE NOTED.
$0 SINGLE POLE. 20 AMP, SWITCH WITH DIMMER. MOUNT 42" A.F.F. TO CENTERLINE OF SWITCH
UNLESS OTHERWISE NOTED.
$y MOTOR RATED SWITCH
TWO POLE, 30 AMP SWITCH. MOUNT ADJACENT EQUIPMENT TO BE CONTROLLED.
® FACTORY MOUNTED DISCONNECT/STARTER (SEE MECHANICAL SCHEDULE)
Wfl Ag FUSIBLE DISCONNECT SWITCH A - POLES, B= FRAME SIZE, C- FUSE RATING
J- GROUNDING ELECTRODE & CONDUCTOR SYSTEM
IMTRANSFORMER
D ELECTRICAL PANELBOARD
0- TELEPHONE WOOD BACKBOARD
WP WEATHERPROOF
T/C TIME CLOCK
A.F.F. ABOVE FINISH FLOOR
® OUTLET STRIPS.
Q ,gyp $G Op7
00
-C 2
1 1.
6� to C�/
ISSUED FOR PERMIT Oct. 08, 2007
ISSUED FOR CONSTRUCTION -
KAMM CONSULTING PROJECTM 2007 -0307 •• ►�' • ' �' ��i�
PROJECT MANAGER: Nicholas Melisiotis, P.E. ��� CAR
M M 1407 West et '1m.
Deerfield Bis ci,Fo� 4`
Phone 954 -449.2200 54.949221, _
�u engineering@ka qty
Certification of �►� 1$9
DIRECTOR OFELECTRICALINGINEERING Die Ur4 90oy�
Lon T. Carter Florida License #35249 �f - ^ .t au ,,r•. �A
DIRECTOR OF MECHANICAL
ENGINEERING " , s •• �r V- • ��
Mircea Pella Florida License #48798 , . �. r. ir
Maverick Architecture &
Design, Ilc.
6675 Westwood Blvd.
Suite 140
Orlando, Florida 32821
T: 407.351.8787
F: 407.351.9254
E:
Info @MaverickArchDes.com
AA. 26000903 AR.
91835
a conceptually
independent forum
M
-y
r
M
>
M
.L
CU
_
O
10
U-
"E
6
cn
A2
O
�
M LO
O
0
m
fV
m
0
Z
W
O
U
2
q
c
y
o
w-
Q
n
O
�
(n
WW
�
U
U
W
0
0
�
0
d
z
I HEREBY CERTIFY THAT THESE DRAWINGS AND
SPECIFICATIONS WERE PREPARED UNDER
MY
DIRECT SUPERVISION AND TO THE BEST OF MY
KNOWLEDGE COMPLY WITH THE STATE BUILDING
AND ZONING ORDINANCES.
SKIED
STATE REGISTRATION
DATE
ELECTRICAL
NOTES
EOO 1
Drawing No.