07-1661-068(A)
GI 1%2"
60"
MINIMUM X 1 -1/2- X 0.054 (16 GA.)
SEE ARCH.
RETAINING ANGLES MUST OVERLAP STRUCTURE OPENING
100-
1" MINIMUM AND COVER CORNERS OF OPENINGS AS SHOWN.
FIRE RESISTIVE MATERIAL
(B) CLEARANCE: 1/8" PER LINEAR FOOT
140-
BOTH DIMENSIONS
DUCT SHALL ATTACH
(C) STEEL SLEEVE: TO SLEEVE (STYLE "B -) (B)
(D) APPROVED FIRE DAMPER, CURTAIN BLADE TYPE
e
WITH 212• FUSIBLE LINK
91835
(E) SECURE RETAINING ANGLES TO SLEEVE
a conceptually
NO. 10 STEEL SCREWS
independent forum
(F) SECURE DAMPER TO SLEEVE ON 8- CENTERS WITH
WOOD STUD
NO. 10 STEEL SCREWS
I SEE ARCH. I
(H) I
(F)
(G) CONNECT DUCT TO SLEEVE WITH BREAKAWAY
CONNECTION
(H) FULLY GASKETED HINGED CAM LOCK FIRE DAMPER
>
ACCESS DOOR. LABEL "FIRE DAMPER ACCESS ".
'i
NOTE
•, •0
ALL SMOKE AND FIRE DAMPERS (G)
co
(UNDER 16- IN HEIGHT) SHALL BE (A)
r
OVERSIZED BY 2" AND TRANSITIONED (E)
t• "a
DOWN TO DUCT SIZE TO MAXIMIZE
co
FREE AREA.
_ O
(D)
OPENING TO BE LINED WITH FIRE
60"
RESISTIVE MATERIAL OF RATING
SEE ARCH.
EQUAL TO THAT OF THE WALL
100-
205 -330 CFM
FIRE RESISTIVE MATERIAL
335 -450 CFM
140-
FIRE DAMPER SLEEVE
F: 407.351.9254
BREAK —AWAY CONNECTION
Info @MaverickArchDes.com
AA. 26000903 AR.
DUCT
1Y
91835
,,
a conceptually
(C)
independent forum
WOOD STUD
I SEE ARCH. I
DUCT
(A)
FIRE RESISTIVE MATERIAL
METAL STUD AROUND
PERIMETER OPENING
I STYLE 'B" DYNAMIC FIRE SCALE DETAIL
NOT TO
MAIN DUCT
N.
\
\
D= \\\
TM -CfF \
9mUm SUPPLY GRalJ'
DOUBLE M=nm WH OPPOSED
BLADE DAMPER
SIDEWALL GRILLE DETAIL a
NOT TO SCALE M7
LOCKING QUADRANT GALV. STEEL ROD OR NYLON DRAWBAND AND
TO BE EXPOSED STRAP SUPPORTS PER MASTIC AT EACH CONNECTION
SMACNA STANDARDS
FLEXIBLE DUCT WITH SIDE TAKE —OFF FITTING
INSULATION do WITH DAMPER, BELL MOUTH
VAPOR BARRIER OR SHOETAP TYPE SQUARE TO
ROUND
MAIN SUPPLY AIR ADAPTER
TIE TO DUCT, SEE PLANS FOR
STRUCTURAL TYPE AND INSULATION
SUPPORTS -- ----- -- = --- -- GYPSUM BOARD
/ CEILING
2" WIDE METAL BAND / __ :: .::
SUPPORT
ILOUVERED FACE CEIUN DIFFUSER
ROUNDE TO I 1 -1/2" X 1 -1/2" X 1/8- GALV.
ADAPTER ANGLE OR STRAP PER SMACNA
II CONNECT INNER DUCT WITH DRAWBAND AND SEAL
WITH TAPE/MASTIC OUTERDUCT AT NECK CONNECTION
PROVIDE THERMAL INSULATION BLANKET
IF INSTALLED IN UNCONDITIONED SPACE
SUSPENDED TYPE LOUVERED FACE CEILING DIFFUSER
CEILING SYSTEM WITH 2' X 2' LAY —IN ALUM. PANEL
TYPICAL DIFFUSER DETAIL 8
NOT TO SCALE M7
UNISTRUT CONNECI
To FLOOR SLABS.
UNISTRUT 1-1/2- TAPCONS.
BRACKET
CHASE FU
GALVANIZED PIPE CLAMP W/ELASTOMERIC
UNISTRUT CONNECTION ISOLATOR, GALV. NUT do WASHER
TO FLOOR SLABS. GALVANIZED PIPE CLAMP
SEE ELEVATION DETIAL W/ GALV. NUT & WASHER
1 "x1 "x1 -1 /2"
FU
(TYP-)
�TYP. UNINSULATED L— TYP. SUCTION LINE WITH
LIQUID LINE EXTERNAL INSULATION REF
NOTE:
1. PIPE SIZES INDICATED ON PLANS FLC
2. SEE AR04ITECTIJAL DRAWINGS FOR CHASE CONSTRUCTION.
1
COMMON CORRUGATED METAL
DUCT, SEE PLAN FOR SIZE
SHEETMETAL ROUND CONN
SEE PLAN FOR END SIZES
l •
CORRUGATED METAL SEE PLAN FOR SIZE DUCT ( �— PANDUIT STRAP (TYP)
CEILING INSERT WEER SAME
THICKNESS AS
TRANSFERSE DUCT
CEILING SLAB
1 1/2 "SHEET METAL SLEEVE. LLU 5/8" 1/2 STEEL ROD SCREWED
RIVET TO DUCT AT TOP AND INTO INSERT IN CEILING SLAB.
BOTTOM. SLEEVE TO BE PROVIDE THREADED COUPLING
OF SHEET METAL
SAME GAUGE AS DUCT. L AT BOTTOM OF DUCT PULLED
WASHER UP TIGHT TO SUPPORT DUCT
MANUAL VOLUME DAMPER
BUCKLEY BELLMOUTH —
AIRTITE "BM" FITTING.
MAIN DUCT
CEILING DIFUSER
REFER TO ARCHITECTURAL
DRAWINGS FOR CEILING TYPE
SUPPORT TO STRUCTURE ABOVE.
INSULATED FLEXIBLE DUCT
4' -0" MAX. LENGTH IF N.O.I.
METAL CLAMP AROUND FLEX
DUCT do COLLAR. CONNECTION
TO BE DRAWN TIGHT do TAPED.
FLEX BCFEDWF
60"
50 -125 CFM
80"
130 -200 CFM
100-
205 -330 CFM
120'
335 -450 CFM
140-
455 -7GD CFM
v
I FLEX DUCT CONNECTION DETAIL �
NOT TO SCALE M7
SHAFT EXTENSION
(LOCKING HARDWA
EXTENDED TO SUII
INSULATION THICK!
2" x 1/2" x 8" STRUCTURAL
FORMED CHANNEL FRAME —
WIDTH SHALL NOT EXCEED 48"
i
ALL BRANCH DUCTS SHALL
HAVE VOLUME DAMPERS.
1/2" x 1/2" ANGLE
STOP BAR (TYP.)
OPPOSED BLADE VOLUME DAMPER Z
NOT TO SCALE M7
ELBOW
CC
TURNING
HANGING
HANG ALL DUCT PER SMACNA STANDARDS
CHANNEL STRAP do SADDLE
TURNING
TEE
SPUTTER DAMPER CONTROL
ROD W/ LOCK
M7
MAIN DUCT
SPUTTER DAMPER
CLINCH EDGES
I
BRANCH DUCT
/
/
/
SPACER REO'D ON INSULATED DUCT
SET SCREW
GALV. STEEL ROD
TYPICAL DUCT TAP -OFF 110
NOT TO SCALE M7
"RUSKIN" MODEL CDBOVG2 WITH
12OV -10 MOTORIZED ACTUATOR. DAMPER
SHALL BE CLOSED WHEN POWER IS OFF.
DAMPER SHALL BE INTERLOCKED WITH
A/C UNIT CONTROL SO THAT WHEN DAMPER
IS IN CLOSED POSITION A/C UNIT SHALL
NOT OPERATE.
0
• BOLT DAMPER TO
c WALL WITH 5/16"
0 BOLTS TO METAL WALL
wool STUD FRAME.
O ® 0
BOLT FLANGE TO
EXISTING DUCT. 0
PROVIDE FLANGE FOR c
EXISTING DUCT.
MOTORIZEDDDAMPER DETAIL 3
7
TURNING VANES
(TYPICAL)
THROAT SIZE AS
INDICATED ON PLANS —
LENGTH -WI OR W2
WHICH EVER IS LARGER
CLOSED
L HEM EDGE
PIVOT
FLOW ►
VENTILGCK #603
BALL JOINT
1/4 "0 CLERANCE
SUP SLEEVE
1/4 "0 PUSH
PULL ROD
1/4" SET
SCREW
LOCK
tail•
BRANCH
DUCT
3
z
a�
W2
RECTANGULAR TEE SUPPLY DUCT DETAIL
NOT TO SCALE M7
12 GAUGE WIRE
OR 1/4" ROD TO
UNDERSIDE OF
rROOF DECK
HANG FLEXIBLE DUCTS
WITH 1.5- WIDE 26 GA.
STEEL STRAPS WRAPPING
UNDER DUCT EVERY 4 FT.
MAXIMUM.
1" WIDE 22 GAUGE
STRAP WRAPPING UNDER
DUCT AND ATTACHED TO
JOISTS OR UNDERSIDE
OF ROOF DECK /SLAB-7
DUCT DUCT
1"
8' MAX 8' MAX
' I 22 GAUGE
1 "X2 "X1- ANGLE
CHANNEL 4 4 "X2 "X2" 4"
HANG ALL DUCT PER SMACNA STANDARDS
DUCT SUPPORT DETAIL n
NOT TO SCALE M7
CITY OF SOUTH MIAMI
BUILDING DEPT.
MECHANICAL SECTION
APPROVED BY:
DATE: U '
ISSUED FOR PERMIT Oct 08, 2007
ISSUED FOR CONSTRUCTION
GK;AMM CONSULTING PROJECTM 2007 -0307
PROJECT MANAGER Nicholas Melisiotis, P.E. * `' % F l�• , a , l , ►�" tN i�
i
1407 West N CL� • • • '•'
Deerfield Beach, ldrhk'33442''- "�'•
Phone 954.5L49,2290 Fax 9 01
0 A', �V engineerinkammcaul
Certificati on off, utho
8
DIRECTOR OF ELECTRICAL ING � O y
14; -
Lon T. Carter Florida License #35249
DIRECTOR OF MECHANICAL ENGINEERING t l 1 0 Fi`O ' •`(�
Mircea Pella Florida License #48798 .�
Maverick Architecture 8L
Design, Ilc.
6675 Westwood Blvd.
Suite 140
Orlando, Florida 32821
T: 407.351.8787
F: 407.351.9254
E:
Info @MaverickArchDes.com
AA. 26000903 AR.
91835
a conceptually
independent forum
CO
M
>
M
'i
CU
0
0
co
LL
r
•E
Y` c
co
.R1
_ O
�
LO
r-
---
0
U)
co
O
C
o
Q
n
Q
m
U
LU
m
O
0
It
I HEREBY CERTIFY THAT THESE DRAWINGS AND
SPECIFICATIONS WERE PREPARED UNDER
MY
DIRECT SUPERVISION AND TO THE BEST OF MY
KNOWLEDGE COMPLY MATH THE STATE BUILDING
AND ZONING ORDINANCES.
SIGNED
STATE REGISTRATION
DATE
MECHANICAL
DETAILS
■
Drawing No.