07-1661-066� AIR DISTRIBUTION SCHEDULE Design, Ilc. 6675 Westwood Blvd. FAN SCHEDULE CHILLED WATER AIR HANDLING UNIT SCHEDULE SELECTION DATA FAN DATA FRAME MOTOR DATA DAMPER THROW NC GENERAL DATA SELECTION DATA SERVICE AREA MANUF.(•) MODEL FAN DATA CFM COIL DATA SONES HP RPM DRIVE VOLTAGE WEIGHT (LBS) INTENSION L "xW xH" OPENING L'xW CONTROL GEN. DATA EF -1 RESTROOMS GREENHECK BCF- 110 -15 INUNE UNIT TAG MANUFACTURER(**) MODEL NO. TYPE S/A CFM 0/A CFM TYPE ESP (" WG) HP FLA MCA/MOCP VOLTAGE WPD ('WG) ROWS" EAT DB T DB EWT/LWT GPM TOTAL MBH SENS. MBH PIPE CONN. FILTER HEAT KW VIBRATION MIN. STAT. OPERATING DIMENSION NOTES /ACCESSORIES 2,5,11,14 KEF -1 HOOD 1 E/A CAPTIVEAIRE 6112CARM UPBLASST 1150 1.4 - 0.75 1745 BELT 480/31 200 33X33X30 - SWITCHED VIA VIA 1,2,3,5,6,9,10,12,15,16 KEF -2 HOOD 2 E/A CAPTIVEAIRE B118CARM UPBLUAST 3750 ISOLATION DEFLECT. WEIGH LB LXWxH IN BELT 460/34 AC -1(•) CARRIER 4ORMS008 HORZ 2400 EE BALLANCE FC 1.2 2.4 - 25.8/30 460/3/80 8.0' - 79/70 55.5/55.0 45/57 13 72.0 57.6 SEE PLANS - 15 SPRING 1' - - 1 THRU 16 0.65 AH -1(•) CARRIER 39LA10 HORZ 4200 SEE ANCE FC 2' 5.0 - - 480/3/60 6.3' 6/11 79/87 55.6/54.5 45/57 27.0 157.2 103.2 SEE PLANS - 15 SPRING 1" 710 125X58X32 1 THRU 16 HOOD 2 M/A -1 AH -2(•) CARRIER 39LA10 HORZ 4200 AIR ISSAULANCE FC 2' 5.0 - - 480/3/60 8.3' 8/11 79/87 55.8/54.5 45/57 27.0 157.2 103.2 SEE PLANS - 15 SPRING 1" 710 125X58X32 1 THRU 18 36X4OX35 AH -3(•) CARRIER 39LA10 HORZ 4200 9ALLLAN AIR FC 2' 5.0 - - 480/3/80 8.3' 8/11 79/87 55.8/54.5 45/57 27.0 157.2 103.2 SEE PLANS - 15 SPRING 1' 710 125X58X32 1 THRU 18 NORMAL POWER WRING BY ELEC. ' AH -4(•) CARRIER 39LA08 HORZ 3900 BALANCE FC 2.2" 3.0 - - 480/3/60 1.6 6/14 76/64 58.7/56.4 45/57 24.0 144.2 95.32 SEE PLANS - 15 SPRING 1' 710 125X58X32 1 THRU 18 AH -5(•) MCQUAY LSL 111C HORZ 4200 91 ANCE FC 0.6" 3.0 - - 480/3/60 12.0' 4/12 76/64 57.0/56.5 45/57 1 27.0 128.4 100.0 SEE PLANS - 15 SPRING 1" 950 - 1 THRU 16 PH -6(N) CARRIER 42BHC162 HORZ 1700 EE 9AI NCE FC 0.6" 0.5 - - 277/1/60 5.3' 6/4.1 76/65 54.7/54.2 45/57 9.0 57.5 38.4 SEE PLANS - 3.0 SPRING 1" 500 38X48X21 1 THRU 16 AH -7(N) CARRIER 42BHC162 HORZ 1700 BAELEANCE FC 0.6" 0.5 - - 277/1/80 5.3' 6/4.1 76/65 54.7/54.2 45/57 9.0 57.5 38.4 SEE PLANS - 3.0 SPRING 1" 500 38X48X21 1 THRU 16 AH -8(N) CARRIER 42BHC162 HORZ 1700 BALANCE FC 0.6" 0.5 - - 277/1/60 5.3' 6/4.1 76/65 54.7/54.2 45/57 9.0 57.5 38.4 SEE PLANS - 3.0 SPRING 1" 500 38X48X21 1 THRU 16 AH -9(N) CARRIER 42BHC162 HORZ 1700 EE BALANCE FC 0.6' 0.5 - - 277/1/60 5.3' 6/4.1 76/65 54.7/54.2 45/57 9.0 57.5 3&4 ISEE PLANS - 3.0 SPRING 1' 500 38X48X2t 1 THRU 16 AH -10(N) CARRIER 42BHC162 HORZ 1700 BALANCE FC 0.6" 0.5 - - 277/1/60 5.3' 6/4.1 76/85 54.7/54.2 45/57 9.0 57.5 3&4 SEE PLANS - 3.0 SPRING 1" 500 38X48X21 1 THRU 16 OAU -1(N) CARRIER 39MC14 HORZ 5000 BALANCE FC 1.0' 3.0 - - 460/3/60 6.3' 8/11 76/64 54.9/54.4 45/57 69.4 416.5 199.7 SEE PLANS - 25 SPRING 1" 2300 114X79X49 1 THRU 17 (•) EXISTING UNITS. (••) EQUIVALENT MANUFACTURER: TRANE. MCQUAY. YORK AHU NOTES: 10. FACE VELOCITY SHALL NOT EXCEED 450 FPM 1. PROVIDE 3 -WAY MODULATING CONTROL VALVES. 11. PROVIDE SLOPED STAINLESS STEEL DRAIN PAN. 2. PROVIDE MINIMUM 30% EFF. 2" FILTERS. 12. PROVIDE ANTi- MICROBIAL COATING FOR FILTERS AND DRAIN 3. PROVIDE INTERFACE CONTROL COMPATIBLE WITH BAC SYSTEM (SEE CONTROL DIAGRAMS) PAN ASSEMBLY. 4. PROVIDE EXTENDED GREASE LINES TO MOTOR SIDE OF AHU. 13. PROVIDE 3" AUXILLARY DRAIN PAN WITH AUTOMATIC SHUT OFF FLOAT SWITCH. 5. PROVIDE SPRING VIBRATION ISOLATORS AS PER MANUFACTURER'S RECOMMENDATION. 14. PROVIDE 3 -PHASE PROTECTION FOR EACH LEG OF ELEC. MOTOR 6. PROVIDE PLENUM BOX FILTER SECTION. 15. MOTOR STARTERS. DISCONNECTS AND ALL EQUIPMENT 7. COILS SHALL NOT EXCEED 8 ROWS OR 120 FINS PER FOOT. POWER WRING BY ELEC. CONTRACTOR; COORDINATE PRIOR TO ANY WORK/PURCHASING 8. PROVIDE AHU'n WITH EITHER RIGHT OR LEFT HAND COIL AND MOTOR CONNECTIONS 16. INTERLOCK THE FAN WITH OUTSIDE AIR MOTORIZED AIR DAMPER AS INDICATED ON PLANS. 17. PROVIDE CO2, RELATIVE HUMIDITY AND THERMOSTAT COMBINATION SENSOR. 9. PROVIDE SOLID DOUBLE WALL CASING, WITH 1'/3 LB. INSULATION UNEXPOSED TO AIRSTREAM 18. PROIDE VFD DRIVE FOR FAN AND INTERLOCK WiTH COMBINATION SENSOR. � AIR DISTRIBUTION SCHEDULE Design, Ilc. 6675 Westwood Blvd. FAN SCHEDULE FACE SIZE SELECTION DATA FAN DATA FRAME MOTOR DATA DAMPER THROW NC GENERAL DATA TAG SERVICE AREA MANUF.(•) MODEL CONFIG. CFM ESP ( "WG) SONES HP RPM DRIVE VOLTAGE WEIGHT (LBS) INTENSION L "xW xH" OPENING L'xW CONTROL ACCESSORIES EF -1 RESTROOMS GREENHECK BCF- 110 -15 INUNE 2000 1.0 12.5 1.5 1262 BELT 460/30 300 36X32X19 2012 SWITCHED 2,5,11,14 EF -2 OUTDOOR SMOKING GREENHECK BCF -106 INUNE 500 1.0 13.2 0.25 1667 BELT 450/30 100 29X23X13 15X8 SWITCHED 2,5,11,14 KEF -1 HOOD 1 E/A CAPTIVEAIRE 6112CARM UPBLASST 1150 1.4 - 0.75 1745 BELT 480/31 200 33X33X30 - SWITCHED VIA VIA 1,2,3,5,6,9,10,12,15,16 KEF -2 HOOD 2 E/A CAPTIVEAIRE B118CARM UPBLUAST 3750 1.9 - 3.0 1478 BELT 460/34 220 38X38X36 - SWITCHED VIA VIA 1,2,3.5,6,9,10,12,15,16 KEF -3 HOOD 3 E/A CAPTiVEAIRE B124CARM UPBLAST 4000 2.0 - 3.0 972 BELT 460/30 500 52X52X50 - SW HOOD VIA 1,2,3,5,6,9,10,12,15,16 DEF -3 DISHWASHER CAPTiVEAIRE B113CARM UTILITY 800 0.65 - 1.0 772 BELT 115/10 - _ - SWITCHED VIA DISHWASHER 1 2.3,5,6,9,11,12,1315 KSF -1 HOOD 1 M/A CAPTIVENRE NSAU1 -G10 CABINET 920 0.825" - 0.5 774 BELT 480/30 210 28X32X28 24X24 SWI CHEDD VIA 2,3.4.5,7,8,9 KSF -2 HOOD 2 M/A -1 CAPTiVEAURE NSAU1 -G12 1 CABINET 2812 0.650" - 1.0 772 BELT 460/30 3DO 36X4OX35 34X34 SWI CHEDD VIA 2,3.4,5.7,8,9 KSF -3 HOOD 3 M/A CAPTIVEAIRE NSAU1 -G12 CABINET 3200 0.650" - 1.5 810 BELT 460/30 3DO 36X4OX35 34X34 SWITCHED VIA 2,3,4,5,7,8,9 (•) APPROVED EQUAL MANUFACTURER: COOK, TWIN -CITY, ACME, PENN ACCESSORIES NOTES: 1. PROVIDE SPIN -IN COLLAR WITH VOLUME DAMPER AT TRUNK TO FLEX DUCT CONNECTION (SEE DETAIL). 2. PROVIDE TYPICAL 4 -WAY DIFFUSION, 2 -WAY OR 3 -WAY ONLY WHERE INDICATED ON PLANS. 1. PROVIDE MOTOR OUT OF AIR STREAM 3. REFER TO ARCHITECT PLANS FOR CEILING TYPE. 4. FINAL COLOR SELECTION SUBJECT TO ARCHITECT APPROVAL GENERAL FAN NOTES: 2. PROVIDE BACK DRAFT DAMPER 6. PROVIDE INSULATION ON THE BACK OF DIFFUSER IF IN UNCONDITIONED SPACE S/A FLEX SCHEDULE a. MOTOR STARTERS, DISCONNECTS (CONTRACTOR IF NOT FACTORY PROVIDED) AND ALL EQUIPMENT 3. PROVIDE FACTORY MOUNTED DISCONNECT SWITCH AND INTEGRAL THERMAL OVERLOAD PROTECTION, 8. PROVIDE INTERNAL CABLE CONTROL FOR UNEARS IN HARD CEILINGS. 64' 50 -125 CFM NORMAL POWER WRING BY ELEC. ' COORDINATE WITH ELECTRICAL CONTRACTOR PRIOR TO ANY PURCHASING. 130 -200 CFM CONTRACTOR SHALL VERIFY WITH ARCHITECT AND TENANT /OWNER, 104' 205 -330 CFM b. ALL CONTINUOUS -DUTY MOTORS SHALL BE PROVIDED WITH OVERLOAD PROTECTION 4. PROVIDE ROOF CURB STANDARD HAS TO BE FOLLOWED REGARDING A SPECIFIC MODEL 124" 335 -450 CFM OR MANUFACTURER AND SHALL BRING ANY DISCREPANCY TO ACCORDING TO NATIONAL ELECTRICAL CODE PAR. 430 -32. 5. PROVIDE MINIMUM TWO BELTS . 144' 455 -700 CFM 8. VIBRATION ISOLATORS C. FIELD ADJUST OPENINGS WITH STRUCTURE. 7. PROVIDE COMPLETE WITH FILTERS 8. PROVIDE BIRD SCREEN d. ALL OUTDOOR EQUIPMENT SHALL COMPLY WITH LOCAL ZONING NOISE 9. PROVIDE RHOOD DRAIN AND CORROSION COATING. ORDINANCE OR NOT EXCEED A NOISE LEVEL OF 65dB AS MEASURED 10. PROVIDE G GREASE GREASE TRAP RADIALLY 30 FT. FROM THE EQUIPMENT IN ALL DIRECTIONS. 11. SUPPORT FROM STRUCTURE COMPLETE WITH VIBRATION ISOLATORS e. COORDINATE WITH ELECTRICAL CONTRACTOR BEFORE BIDDING OR 12. PROVIDE UPBLAST CONFIGURATION. ORDERING ANY EQUIPMENT. 13. PROVIDE ALUMINUM CONSTRUCTION AND SNATCH AT DISHWASHER. 14. PROVIDE TIME DELAY RELAY TO ALLOW OPERATION OF MOTORIZED DAMPERS t. SEE PROJECT PLANS AND SPECIFICATIONS FOR OTHER FIELD SUPPLIED ITEMS 15. HEAT SLINGER AND ADDITIONAL INFORMATION. 16. SHAFT SEAL g. ALL FANS ON ROOF SHALL BE PAINTED AS PER ARCHITECTURAL SPECS. h. FINAL SELECTION COORDINATED WITH HOOD/KITCHEN EQUIPMENT SUPPLIER � AIR DISTRIBUTION SCHEDULE Design, Ilc. 6675 Westwood Blvd. TAG MANUF. & MODEL FACE SIZE NECK SIZE MATERIAL FRAME FINISH DAMPER THROW NC CFM RANGE NOTES A 71TUS TDCA -AA 24X24 SE SCH ALUM. NOTE 3 NOTE 4 NOTE 1 NOTE 2 MAX. 30 SEE SCH. 5,6,8 B TITUS TDCA -AA 12X12 SCH ALUM. NOTE 3 NOTE 4 NOTE 1 NOTE 2 MAX. 30 SEE SCH. 5,6,8 C TITUS 30ORS 20X14 18X12 ALUM. NOTE 3 NOTE 4 NOTE 1 NOTE 2 MAX. 30 SEE SCH. 5,6,8 E TITUS TMRA -AA 300 104 ALUM. NOTE 3 NOTE 4 NOTE 1 NOTE 2 MAX. 30 SEE SCH. 5,6,8 G TITUS PAR 24X24 SEES ALUM. NOTE 3 NOTE 4 NOTE 1 NOTE 2 MAX. 30 SEE SCH. 5,6,8 I TITUS 272FS 50X8 48X6 ALUM. NOTE 3 NOTE 4 NOTE 1 NOTE 2 MAX. 30 SEE SCH. 5,6,8 m � 0 0 Z I HEREBY CERTIFY THAT THESE DRAWINGS AND SPECIFICATIONS WERE PREPARED UNDER MY DIRECT SUPERVISION AND TO THE BEST OF MY KNOWLEDGE COMPLY WITH THE STATE BUILDING AND ZONING ORDINANCES. SIGNED STATE REGISTRATION DATE MECHANICAL AA 71TUS 4FL 24X24 22X22 ALUM. NOTE 3 NOTE 4 - - MAX. 30 • 6,7 BB TiTUS 4FL 12X12 10X10 ALUM. NOTE 3 NOTE 4 - - MAX. 30 • 6,7 CC TITUS 4FL 2048 22X48 ALUM. NOTE 3 NOTE 4 - - MAX. 30 • 6,7 (•) EQUIVALENT -MANUFACTURER. TITUS, METALAIRE, CARNES, T & B, NAILOR GENERAL NOTES• 1. PROVIDE SPIN -IN COLLAR WITH VOLUME DAMPER AT TRUNK TO FLEX DUCT CONNECTION (SEE DETAIL). 2. PROVIDE TYPICAL 4 -WAY DIFFUSION, 2 -WAY OR 3 -WAY ONLY WHERE INDICATED ON PLANS. 3. REFER TO ARCHITECT PLANS FOR CEILING TYPE. 4. FINAL COLOR SELECTION SUBJECT TO ARCHITECT APPROVAL 5. FLEX DUCT SIZE TO BE SAME AS DIFFUSER NECK SIZE. 6. PROVIDE INSULATION ON THE BACK OF DIFFUSER IF IN UNCONDITIONED SPACE S/A FLEX SCHEDULE 7. PROVIDE VOLUME CONTROL DAMPERS FOR ALL RETURN GRILLES OR REGISTERS FOR BALANCED AIRFLOW. 8. PROVIDE INTERNAL CABLE CONTROL FOR UNEARS IN HARD CEILINGS. 64' 50 -125 CFM 84' 130 -200 CFM CONTRACTOR SHALL VERIFY WITH ARCHITECT AND TENANT /OWNER, 104' 205 -330 CFM PRIOR TO ANY PURCHASING OR INSTALLATION, IF A BUILDING STANDARD HAS TO BE FOLLOWED REGARDING A SPECIFIC MODEL 124" 335 -450 CFM OR MANUFACTURER AND SHALL BRING ANY DISCREPANCY TO THE ATTENTION OF ENGINEER. . 144' 455 -700 CFM 24H 4G r w W FAN STARTER RIBll1 4VDC RELAY 1 Cum SENSOR EXHWIST FAN EF -1 OUTSIDE NR N.C. OUTSIDE NR DAMPER BY M.C. MODULATING CHILLED WATER VALVE _ _ q 0-100% DAMPER ACTUATOR BY CONTROL MFG RIBU1 w24WCREL�►Y, FM STARTER 1 I OAU -1 SUPPLY FAN � E H D.P. SNATCH m LJFM CH WS SUPPLY NR DUCT TEMPERATURE SENSOR SUPPLY AIR ELECTRIC DUCT HEATER ® COMBINATION SENSOR: 1. 002 SENSOR 2. RELATNE HUMIDITY 3. REMOTE TEMP. SEQUENCE OF OPERATION- CV AIR HANDLING UNIT CONTROL 1. The air handling unit shall be started from the building automation yetem (BITS) based on a programmed time schedule or by the timed override pushbutton located at the local thermostat. 2. On a start command, the fan shall run and the fan status switch shall prove flow. if after an adjustable time delay. the fan faile to start, a fan failure alarm shall be sent to the BAS computer. 3. The outside air damper shale open to the set dm requirements. 4. Exhaust fan hF -1 shall be tnterlodad to start whwwar WW -1 Is In the men pled mode. 4. A supply air sensor shall modulate the chilled water valve to mantatn set temperature at 551 ( adjustable). The space thermostat will modulate the duct heater to maintain pprice temperature. & Provide graphic display @croons at the BAS computer for all points used for manta tfq. control and diagnostics of the air handlkq unit controller. 120VAC POWER BY EC. r; mli L,a 100% OA OAU -1 CONTROL COMA BUS RETURN NR FIRE ALARM DDC FICU CONTROLLER DUCT 117 S.D SENSOR TEMPERATURE xe rtTATUS E H MTER ELECTRIC DUCT HEATER SUPPLY NR MODULATING CHILLED WATER 24V VALVE CHWR CHINS 5 COND 18 SH. NR HANDLING UNiT LOW FM COIL UNiT CONTROL WIRING ONLY THE FAN COIL UNIT SHALL BE STARTED BASED ON THE MODE OF THE ROOM OCCUPANCY SENSOR OR BY THE OVERRIDE TIME PUSHBUTTON SWITCH LOCATED ON THE THERMOSTAT. THE FAN COIL UNIT SHALL BE INDEXED FROM THE OCCUPIED SETPOINT TO THE UNOCCUPIED SETPOINT FROM THE OCCUPANCY SENSOR. ON A START COMMAND, THE FAN SHALL START. THE PUSH BUTTON FM SWITCH LOCATED ON THE THERMOSTAT SHALL ACTIVATED THE 'AUTO, OFF. LOW, MED, AND HIGH' FAN MODE. WHEN THE SWITCH IS IN THE 'AUTO' POSMON, THE FAN CONTROLLER WILL USE iTS AL.GORiiHMS TO SELECT THE OPTIMUM SPEED. WHEN THE SWITCH IS IN THE 'OFF' POSITION, ALL FAN SPEEDS Will BE DISABLED. IF THE FAN SPEED IS MAKMLLY SELECTED, THE SPEED T59 DIGITAL DISPLAY ALGORITHM WILL BE DISABLED AND THE FAN SPUD WILL RUN AT THE COMMANDED SPEED WHEN THERMOSTAT W/SE REQUIRED. ON A RISE IN SPACE TEMPERATURE ABONE COOLING SETPOINT, THE CHILLED WATER A DUST AND OVER VALVE SWILL MODULATE OPEN. ON A FALL IN TEMPERATURE BELOW COOLING SEiPOINT, THE VALVE %IALL MODULATE CLOSED. ON A FURTHER DROP IN TEMPERATURE BELOW HEATING SETPOINT. THE ELECTRIC HEAT SWA I BE ENERGIZED AS REQUIRED 70 MAINTAIN SPACE TEMPERATURE. ON A SIGNAL FROM THE FIRE ALARM SYSTEM, THE FM SHALL STOP AND THE CONTROL SYSTEM DE- ENERGIZED. AIR HANDLING UNITS CONTROL CONTROL NOTE CONTROLS ARE FOR REFERENCE ONLY. CONTRACTOR TO COORDINATE CONTROLS AND METHOD OF CONTROL WITH OWNER AND CONTROL MANUFACTURE. VN Ctn' OF SOUTH MIAMI BUILDING DEPT. MECHANiCAL SECTION APPROVED BY: // ­' DATE: Q c ze ISSUED FOR PERMIT Oct. 08, 2007 ISSUED FOR CONSTRUCTION - KAMM CONSULTING PROJECT #: 2007 -0307 , t 4 s PROJECT MANAGER: Nicholas Melisiotis, P s� !, C. �� •� 0%mm 140* •e� ve Dee el eaL� 44 Pholker95 .A4Qr Olt Fax 54.949:21281 nsV en eering@kamm g. DIRECTOR OF ELECTRICAL ENGINEERIN fiCatiOn pA�Iltb n 89 Lon T. Carter Florida License #3 � 91k , •! ?= : e ; i DIRECTOR OF MECHANICAL INGINEEEtING ` Macea Pella Florida License #4879 (J "fig Maverick Architecture & Design, Ilc. 6675 Westwood Blvd. Suite 140 Orlando, Florida 32821 T: 407.351.8787 F: 407.351.9254 E: Info @MaverickArchDes.com AA. 26000903 AR. 91835 a conceptually independent forum M M M .L CU O _ - u- .E vJ M "M O t a rI L 0 m 0 o o n Q � U m W m � 0 0 Z I HEREBY CERTIFY THAT THESE DRAWINGS AND SPECIFICATIONS WERE PREPARED UNDER MY DIRECT SUPERVISION AND TO THE BEST OF MY KNOWLEDGE COMPLY WITH THE STATE BUILDING AND ZONING ORDINANCES. SIGNED STATE REGISTRATION DATE MECHANICAL SCHEDULES M61 • Drawing No.