07-1661-059OUTSIDE AIR CALCULATIONS
(BASED ON ASHRAE 82 -04, TABLE 6.1)
AREA
SERVED
AREA SERVED
OR UNIT TAG
NET OCCUPIABLE
AREA SQ.FT.
TOTAL NO.
OF PEOPLE
VENTILATION RATE
CFM
VENTILATION RATE
CFM SF
TOTAL CFM
0 A REQUIRED
TOTAL CFM
O A PROVIDED
NOTES
VENTILATION REQ'D
AC /HR OR CFM
BAR 113
2900.0
250.0
7.5
0.18
2397
2400
3210
50/WC
STOR.121
145
-
-
0.12
17.0
20
-
50/WC
BAR 108,110
3450.0
350.0
7.5
0.18
3248
3250
-
-
8900
-
STORAGE 2
183
-
-
0,12
19
20
-
"CC�
ENTRANCE AREA
3750
200
5
0.06
1225
1225
-
r
MGR OFF 103A
300
3
5
0.05
33
35
-
KITCHEN 117
1335
20
390.0
390
-
STATI
STATION 1
900
23
7.5
0.18
344
350
-
STORAGE 1
921
-
-
0.12
111
115
-
OFFICE
91
1
5
0.08
10
10
-
CORRIDOR
207
-
Q
0.08
12
15
-
v
m
V
LU
m
0
d
�
NOTES- TOTAL 7830.0
1. CALCULATIONS ARE BASED ON ESTIMATED MAX. OCCUPANCY RATES PER ARCHITECTURAL. PLANS AND ASHRAE 62 -04
VENTILATION RATES PER ASHRAE 62 -04
2. FOR OFFICE AND OTHER SIMILAR AREAS CALCULATIONS ARE BASED ON CONTINUOUS OCCUPANCY
AIR BALANCE SCHEDULE
AREA
SERVED
EXHAUST AIR
CALCULATIONS
OUTSIDE AIR
CFM
MAKE -UP AIR
CFM
SPACE SERVED
OR UNIT TAG
SPACE AREA
SQ.FT. )
SPACE HEIGHT
(FT)
SPACE VOLUME
(CU.FT.
VENTILATION REQ'D
AC /HR OR CFM
TOTAL CFM
REQUIRED
TOTAL CFM
PROVIDED
NOTES
MECHANICAL ROOF PLAN
MENS RESTROOM
321
10
3210
50/WC
500
700
X
ENTRANCE AREA
RpESTR00M
614
10
61140
50/WC
650
1300
X
KITCHEN 117
AH -4
KSF/KEF
AC -1
3900
-
3000
440
-
440
-
7000
-
-
8900
-
SERVICE STATION 1
STORAGE 1
LL
NOTES:
1. CALCULATIONS ARE BASED ON LOCAL CODE REQUIREMENTS, FLORIDA BUILDING CODE 2004 (TABLE 403.3) AND ASHRAE 52 -01.
AIR BALANCE SCHEDULE
AREA
SERVED
EQUIPMENT
TAG
SUPPLY AIR
CFM
OUTSIDE AIR
CFM
MAKE -UP AIR
CFM
EXHAUST AIR
CFM
BAR 113
AH -1
OAU -1
4500
2000
420
2000
-
-
-
-
STORAGE 121
MECHANICAL ROOF PLAN
BAR 108,110
AH -2
OAU -1
4500
2740
530
2740
-
-
-
-
STORAGE 2
MECHANICAL DETAILS
ENTRANCE AREA
AH -5
AH -3
OAU -1
EF -1
4500
4500
260
-
500
500
260
-
-
-
-
-
-
-
-
2000
MGR OFF 103A
RESTROOMS
KITCHEN 117
AH -4
KSF/KEF
AC -1
3900
-
3000
440
-
440
-
7000
-
-
8900
-
SERVICE STATION 1
STORAGE 1
LL
OFFICE 1
CORRIDOR
BALANCE DAMPER
BM -1
M
"CC�
0
2700
TOTAL 7830.0 7000 13600.0
NOTES'
1. AREA IS 7,830 +7,000 - 13,6001,230 POSITIVE WHEN ALL EXHAUST FANS OPERATING
MECHANICAL NOTES
1. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, AND EQUIPMENT NECESSARY
FOR THE INSTALLATION OF A COMPLETE SYSTEM IN ACCORDANCE WITH THESE
DRAWINGS, THE FLORIDA BUILDING CODE 2004 AND ALL OTHER APPLICABLE STATE,
COUNTY AND LOCAL ORDINANCES AND THE LATEST ADDITION OF THE FOLLOWING
PUBLICATIONS; SMACNA -85, 92, 95; ASHRAE 15-01, 34-01, 62 -01; NFPA 70-02, 72 -02,
9OA -02, 9OB -02, 91 -99, 96 -01; ANSI Z10.1 -98, Z10.3 -98, Z21.8 -94, Z21.83 -98.
2. THE OWNER SHALL PAY ALL COSTS OF PERMIT, INSPECTIONS AND ALL OTHER
COSTS INCIDENTAL TO THE COMPLETION AND TESTING OF THIS WORK.
3. THE CONTRACTOR SHALL VISIT THE SITE AND COORDINATE WORK WITH OTHER TRADES.
4. THE CONTRACTOR SHALL SUPPLY THE ARCHITECT WITH "AS- BUILT' DRAWINGS.
5. CONTRACTOR SHALL SUBMIT, FOR APPROVAL FIVE [5] COPIES OF MANUFACTURER'S
DRAWINGS FOR EACH PIECE OF EQUIPMENT AND CONTROLS INCLUDED IN CONTRACT.
6. ALL MATERIAL SHALL BE NEW OF U.S. MANUFACTURER OF GOOD QUALITY. ALL WORK SHALL
BE PERFORMED AT INDUSTRY STANDARD QUALITY LEVEL BY CERTIFIED PROFESSIONALS.
ALL EQUIPMENT SHALL BE UL OR ETL LISTED.
7. DUCTWORK:
& ALL (UNEXPOSED) AIR CONDITIONING DUCT WORK SHALL BE OF 1" (R -4.2) SPECIAL
DUTY FSK FOIL REINFORCED FIBERGLASS WITH MANUFACTURER'S LOGO PRINTED ON VAPOR
BARRIER, WITH A HIGH - TENSILE, RESISTANT MAT COATING, EQUAL TO "SUPERDUCT" BY
MANVILLE OR "TOUGHGARD" BY CERTAINTEED, AND ANTI- MICROBIAL PROPERTIES.
ALL FLEXIBLE DUCT TO BE R -4.2 WITH A MAX. TOTAL LENGTH NOT TO EXCEED 15 FT.
INSTALL UL LISTED FOR PLENUM, FLEXIBLE DUCTWORK ELBOW SUPPORTS AT EACH DIFFUSER,
GRILLE, AND REGISTER EQUAL TO "FLEXFLOW ELBOW AS MANUFACTURED BY "THERMAFLEX".
LL ALL EXPOSED DUCTWORK SHALL BE GALVANIZED UNINSULATED SHEETMETAL THE CONTRACTOR
SHALL PROVIDE ALL SHEETMETAL DUCTWORK, HANGERS, AUX. SUPPORT STEEL, ETC., ALL METAL
DUCTS SHALL BE FABRICATED IN ACCORDANCE WITH LATEST EDITION OF S.M.A.C.N.A. ARCHITECT
TO VERIFY FINAL COLOR OF EXPOSED DUCTWORK. REFER TO DEMOUTIN SHEET MD2.1 FOR EXISTING
DUCTWORK INFORMATION.
SMACNA DUCT PRESSURE CLASSES BASED ON OPERATING PRESSURE ARE: 1/2", 1 ", 2 ", 3 4",
6% AND 10 ". EACH DUCT SYSTEM SHALL BE CONSTRUCTED FOR THE SPECIFIC DUCT PRESSURE
CLASS SHOWN ON PLANS.
WHERE NO PRESSURE CLASS IS SPECIFIED FOR CONSTANT VOLUME SYSTEMS, 1" W.G. PRESSURE
CLASS IS THE BASIS OF COMPLIANCE WITH THE SMACNA STANDARDS REGARDLESS OF VELOCITY.
ALL DUCTWORK SHALL BE SEALED TO SMACNA "HVAC DUCT CONSTRUCTION STANDARDS' FOR
ITS PRESSURE CLASS SEALING METHODS.
8. ALL EXHAUST DUCTS, SMOKE MAKE UP, AND OUTSIDE AIR DUCTS SHALL BE
GALVANIZED SHEET METAL WITH SEALED SEAMS AND JOINTS. ALL OUTSIDE AIR DUCT SHALL BE
INSULATED WITH EXTERNAL BLANKET INSULATION R -6 MIN.
ALL METAL EXHAUST, MAKE -UP OR OTHERWISE DUCTS INSTALLED IN LOCATIONS WHERE DEWPOINT
CONDITIONS CAN OCCUR INSIDE THE DUCT SHALL BE EXTERNALLY INSULATED WITH R -6 MIN. ALL
METAL DUCTS SHALL BE FABRICATED IN ACCORDANCE WITH LATEST EDITION OF S.M.A.C.N.A.
9. OUTSIDE AIR INTAKES SHALL BE SCREENED WITH A CORROSION RESISTANT MATERIAL NOT LARGER
THAN 1/2" MESH. 0/A INTAKES SHALL NOT BE TAKEN FROM A LOCATION CLOSER THAN 10 FT.
FROM ANY CHIMNEY, VENT OUTLET OR SANITARY SEWER VENT OUTLET, UNLESS SUCH VENT
IS NOT LESS THAN 24 INCHES ABOVE THE OUTSIDE AIR VENT.
OUTSIDE NR INTAKE VENTS LOCATED ON ROOFS WILL BE PROPERLY MARKED WITH A UNIVERSAL
MARKING "INTAKE% PERMANENTLY ATTACHED PER FMC 2004, SEC. 401.5.1. COORDINATE WITH
BASE BUILDING PLANS FOR LABELS AND MATERIALS
10. DUCT SIZES SHOWN ARE INSIDE DIMENSIONS.
11. ALL NR DEVICES (DIFFUSERS, REGISTERS AND GRILLES) SHALL BE ALL ALUMINUM
CONSTRUCTION WITH EXPOSED SURFACE OFF WHITE BAKED ENAMEL FINISH OR AS
SPECIFIED BY ARCHITECT. DEVICES SHALL BE AS SPECIFIED OR EQUAL TO TITUS OR METALAIRE.
PROVIDE OPPOSED BLADE DAMPERS AT ALL DIFFUSERS AND REGISTERS AS INDICATED ON
PLANS. PROVIDE BALANCING DAMPERS FOR ALL SUPPLY AND RETURN DIFFUSERS AND REGISTERS
TO ENSURE COMPLAINCE WITH FMC 2004, PAR. 801.4 AND PAR. 803.15 FOR BALANCED AIR FLOW.
12. THERMOSTAT
A. SHALL BE COMBINATION COOUNG/HEATING, WITH SYSTEM "COOL -AUTO-
HEAT -OFF" AND FAN "ON -AUTO" SELECTOR SWITCHES. PROVIDE PROGRAMMABLE TYPE AS
RECOMMENDED BY MANUFACTURER, HONEYWELL OR EQUAL PROVIDE TAMPER PROOF COVERS.
13. THERMOSTAT LOCATION SHALL BE APPROVED BY OWNER AND ENGINEER BEFORE INSTALLATION.
INSTALL THERMOSTAT 48" TO 54" A.F.F. PER A.D.A REQUIREMENTS WHERE APPLICABLE.
MECHANICAL CONTRACTOR SHALL COORDINATE WITH ELECTRICAL CONTRACTOR ALL REQUIREMENTS
FOR JUNCTION BOXES, CONDUITS, CONTROL WIRING, POWER, ETC. AND DEFINE RESPONSIBILITIES
AND SCOPE OF WORK FOR EACH TRADE PRIOR TO ANY PURCHASING OR INSTALLATION.
14. ALL BRANCH TAKE -OFFS TO BE PROVIDED W/ MANUAL VOLUME DAMPERS. PROVIDE RADIUS ELBOWS
WHERE FEASIBLE, SQUARE ELBOWS AND TEE'S SHALL BE FURNISHED W /SINGLE FOIL TURNING VANES.
PROVIDE MANUAL VOLUME DAMPERS WITH EXTRACTOR AT ALL FLEX TAKE -OFFS.
PROVIDE REMOTE, CABLE OPERATED VOLUME DAMPERS IN INACCESIBLE AND HARD CEILING AREAS,
"YOUNG REGULATOR" OR EQUAL.
15. PROVIDE NEW FILTERS FOR ALL AIR CONDITIONING EQUIPMENT BEFORE START -UP,
REPLACE PRIOR To FINAL ACCEPTANCE BY OWNER.
16. PROVIDE SMOKE DETECTORS WITH SERVICE ACCESS DOORS IN ALL SUPPLY AIR DUCTS
FOR FANS AND AHU'S SERVING A COMMON PLENUM OF 2000 CFM OR ABOVE.
FOR SMOKE DETECTORS NOT VISIBLE, IN CONCEALED SPACES, PROVIDE REMOTE ANNUNCIATION /TEST
STATION AS REQUIRED BY AUTHORITY HAVING JURISDICTION, COORDINATE PRIOR TO INSTALLATION.
DETECTORS SHALL BE BY ONE MANUFACTURER, COORDINATE VOLTAGE ETC. WITH
ELECTRICAL CONTRACTOR AND FIRE ALARM SYSTEM BEFORE ORDERING. UPON
DETECTION, SMOKE DETECTORS SHUT DOWN ASSOCIATED AIR MOVING EQUIPMENT AND
ALL AIR MOVING EQUIPMENT SERVING THAT COMMON PLENUM.
17. PROVIDE TYPE "B" DYNAMIC FIRE DAMPERS WITH SERVICE ACCESS DOORS IN ALL DUCTS AND
OPENINGS PENETRATING FIRE RATED WALLS, MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS,
TENANT SEPARATION, PARTITIONS, FLOOR OR ROOF SLABS AND AT OUTSIDE AIR INTAKES AS
REQUIRED. PROVIDE RADIATION DAMPERS IN RATED CEILINGS FOR ALL CEILING OPENINGS, CEILING
FANS, DIFFUSERS OR GRILLES RATED FOR USE IN THE CEILING ASSEMBLY.
PROVIDE LOW- LEAKAGE CLASS DAMPERS FOR ALL SITUATIONS WHERE THE AIRFLOW CFM
HAS TO BE CONTROLLED. VERIFY AND REPLACE AS REQUIRED FOR EXISTING SYSTEMS.
18. HVAC CONTRACTOR SHALL PROVIDE A T & B REPORT PER F.B.C. 2004, CH. 13, 410.1.ABCD.4
(THE T & B REPORT SHALL BE INDEPENDENT FOR SYSTEMS OVER 15 TONS)
FOR ALL MECHANICAL EQUIPMENT, AIR DEVICES, DAMPERS, AHU'S AND FANS.
THE TEST AND BALANCE REPORT SHALL BE IN ACCORDANCE WITH THE AIR BALANCE COUNCIL
STANDARDS AND SHALL INCLUDE AIR QUANTITIES FOR ALL SUPPLY GRILLES, RETURN GRILLES
AND EXHAUST GRILLES AND THE LEAVING AND ENTERING AIR TEMPERATURE (T) FROM
SUPPLY GRILLES AND EVAPORATORS.
19. RUN INSULATED FIRE RATED CONDENSATE DRAINS AS REQUIRED.
20. ALL INSULATION WILL HAVE FIRE /SMOKE RATING LESS THAN 25/50.
21. MECHANICAL EQUIPMENT ON ROOF OR ELEVATED STRUCTURES SHALL COMPLY WITH FBC 2004
PAR. 306.5 IF INSTALLED HIGHER THAN 16 FEET A.F.F.
MECHANICAL EQUIPMENT INSTALLED IN ATTICS SHALL MEET THE REQUIREMENTS OF FBC 2004
PAR. 306.3 IF THE EQUIPMENT CAN NOT BE SERVICED/REMOVED THROUGH REQUIRED OPENING.
MECHANICAL EQUIPMENT SHALL BE PROTECTED WITH MECHANICAL BARRIERS IF EXPOSED TO
MECH. DAMAGE. ALL EQUIPMENT SHALL BE INSTALLED ON 6" CONCRETE PAD AT GRADE LEVEL .
SPECIAL NOTE•
ALL WIND LOAD AND OTHER COMPLIANCE CALCULATIONS AND /OR INSTALLATION DETAILS
FOR ROOF MOUNTED EQUIPMENT AS REQUIRED BY FBC 2004, SEC. 1509, 1522 AND CHAPTER 16,
SHALL BE PROVIDED BY STRUCTURAL ENGINEER / ARCHITECT.
22. PROVIDE A MIN. OF 36" CLEARANCE IN FRONT OF ALL 120 -208 VOLT PANELS AND MIN. 42"
CLEARANCE IN FRONT OF ANY 240 -480 VOLT PANEL PROVIDE ADEQUATE SIDE CLEARANCE
PER NEC.
23. MECHANICAL PLANS IN GENERAL, ARE DIAGRAMMATIC IN NATURE, AND ARE TO BE READ
IN CONJUNCTION WITH ARCHITECTURAL, PLUMBING, ELECTRICAL, FIRE SPRINKLER, AND
STRUCTURAL PLANS AND SHALL BE CONSIDERED AS ONE SET OF DOCUMENTS.
DUCT AND PIPING OFFSETS, BENDS AND TRANS171ONS SHALL BE REQUIRED TO PROVIDE AND
INSTALL A COMPLETE FUNCTIONAL SYSTEM AND SHALL BE PROVIDED BY THE CONTRACTOR
AT NO ADDITIONAL COST TO THE OWNER. CHANGES IN DUCTWORK SIZE AND ROUTE
WILL BE REQUIRED TO AVOID STRUCTURAL, PLUMBING, FIRE SPRINKLER AND ARCHITECTURAL
BUILDING FEATURES. DUCTWORK CHANGES MAY BE MADE BY CONTRACTOR USING
EQUIVALENT SIZED DUCT. CONTACT ENGINEER IF DUCT AREA WILL NOT FIT.
24. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS PRIOR TO BIDDING, ORDERING,
FABRICATION OR INSTALLATION OF MATERIALS OR EQUIPMENT.
25. NO COMBUSTIBLE MATERIALS ARE ALLOWED IN RETURN AIR PLENUMS OR ABOVE
CEILINGS USED AS RETURN AIR PLENUM. IF SPACE WITH RETURN AIR PLENUM
HAS ANY DECK TO DECK PARTITIONS, AIR TRANSFER DUCTS MUST BE INSTALLED.
WHEN CPVC PIPING IS USED FOR FIRE SPRINKLER SYSTEMS, THE R/A GRILLES LAYOUT SHALL
BE (FIELD) COORDINATED WITH SUCH PIPING SO THAT NO PORTION OF THE GRILLES WILL BE
DIRECTLY BELOW THE CPVC PIPING.
26. CONDENSATE DRAIN PIPING TO BE AS SPECIFIED PER PLUMBING PLANS, IF NOT SPECIFIED
TO BE TYPE "L" COPPER OR PVC WHERE ALLOWED BY CODE WITH 1/2" ARMAFLEX INSULATION.
PROVIDE APPROVED WATER LEVEL DETECTOR OR FLOAT SWITCH TO AUTOMATICALLY SHUT DOWN
THE AIR COND. UNIT, AS A SECONDARY DRAIN SYSTEM TO COMPLY WITH FMC 2004, SEC. 307
SUPPLY CONDENSATE PUMP WHERE NECESSARY AS IMPOSED BY FIELD CONDITIONS OR INSTALLATION
CHANGES AND PIPE TO CONDENSATE DRAIN PER PLUMBING PLANS.
27. MANUFACTURER'S WARRANTY: CONTRACTOR SHALL PROVIDE WARRANTY FOR A PERIOD OF
(1) ONE YEAR AFTER BUILDING C.O. FOR ALL MECHANICAL SYSTEMS, DUCTWORK, CONTROLS
ACCESSORIES AND ALL OTHER EQUIPMENT, PARTS AND LABOR UNDER THESE DRAWINGS AND
AND SPECIFICATIONS. CONTRACTOR SHALL PROVIDE WARRANTY FOR COMPRESSORS FOR
(5) FIVE YEARS. ANY REPAIRS REQUIRING SYSTEM SHUTDOWN WILL BE DONE DURING
NON - OPERATIONAL PERIODS OR AS AGREED WITH OWNER.
28. THIS IS A REMODEL OF AN EXISTING SPACE. CONTRACTOR TO VISIT SITE PRIOR TO BID.
CONTRACTOR SHALL INSPECT ALL EXISTING AND NEW COMPONENTS OF THE MECHANICAL SYSTEMS
AND ENSURE THAT ALL ARE OPERATIONAL AND WORKING AS SHOWN ON THE APPROVED CD PLANS
AT THE TIME OF C.O.
29. AUXILARY DRAIN PANS SHALL. BE INSTALLED UNDER ALL COILS ON WHICH CONDENSATION CAN
OCCUR AND UNDER ALL UNITS IN CONCEALED SPACES OR ANY AREA WHERE BLDG. DAMAGE
CAN OCCUR AS A RESULT OF AN OVERFLOW, TO COMPLY WITH FBC 2004, PAR. 307.2.
31. CHILLED WATER PIPING SHALL BE BLACK STEEL SCHAO OR TYPE "L" COPPER WITH 2 LB.
DENSITY IN CLOSED CELL FOAMGLASS, WITH FIRE RESISTING FLAME PROOF
ALUMINUM FOIL VAPOR SEAL JACKET AND IT MUST CONFORM TO NFPA 90 -A.
32. INTEGRATE ALL SMOKE CONTROL EQUIPMENT OPERATION (I.E. SUPPLY, RETURN, MAKE -UP, EXHAUST
FAN(S), MOTORIZED DAMPERS AND ETC.) WITH EXISTING SHELL SMOKE EXHAUST SYSTEM OPERATION,
SMOKE MANAGEMENT SYSTEM CONTROL PANEL AND EMERGENCY POWER.
MECHANICAL SHEET INDEX
SHEET#
DESCRIPTION
MOA
MECHANICAL NOTES, LEGEND do INDEX
M2.1
MECHANICAL PLAN
M2.2
MECHANICAL HYDRONIC PLAN
MD2.1
MECHANICAL DEMOU71ON PLAN
MD2.2
MECHANICAL DEMOU71ON PLAN
M3.1
MECHANICAL ROOF PLAN
M4.1
ENLARGED PLANS do SECTIONS
M6.1
MECHANICAL SCHEDULES
M7.1
MECHANICAL DETAILS
M7.2
MECHANICAL DETAILS
independent forum
MECHANICAL LEGEND
®
NEW S/A CEILING DIFFUSER
«1-U/1C
NEW R/A CEIUNG GRILLE
®
EXISTING S/A CEILING DIFFUSER
®
EXISTING R/A CEILING GRILLE
®�
SLOT / LINEAR DIFFUSER
f J
WALL LOUVER / WALL DIFFUSER.
OT
VOLUME CONTROL DAMPER
►
REDUCER OR INCREASER
NEW FLEX DUCT
EXISTING FLEX DUCT
1•� NEW DUCTWORK
EXISTING DUCTWORK
DEMO DUCTWORK
"Z" BOOT TRANSFER DUCT
O ROUND UP
BELLMOUTH TAP
SHOE TAP DAMPER
FIRE DAMPER
`F � FIRE SMOKE DAMPER
RETURN AIR FIRE SMOKE DAMPER
®� DUCT SMOKE DETECTOR
4 CEIUNG EXHAUST: FAN
Fal INUNE EXHAUST FAN
0 ROOF EXHAUST FAN
m
VARIABLE FREQ. DRIVE CONTROL PANEL
«1-U/1C
SUPPLY AIR
®
DIFFUSER OR GRILLE DESIGNATION
®
AIR
®�
DIFFUSER GRILLE
DIFFUSER OR GRILLE DESIGNATION
gyp_ X
EQUIPMENT TAG
OT
THERMOSTAT
OH
HUMIDISTAT
®
WALL SWITCH
-(�
POC- POINT OF CONNECTION
SUPPLY AIR
''I'
RETURN AIR
«1-U/1C
DOOR UNDER CUT
B.O.D.
AP - ACCESS PANEL
-�
SECTION MARK
®�
SMOKE DAMPER
SMOKE DAMPER(S)
FIRE -SMOKE DAMPER
•
MOTORIZED DAMPER
G GATE VALVE
BUTTERFLY VALVE
N CHECK VALVE
BALANCING VALVE
RE
RELOCATED EXISTING
N
NEW
B.O.D.
BOTTOM OF DECK
AFF
ABOVE FINISHED FLOOR
NOT ALL SYMBOLS MAY
APPLY TO THESE PLANS
HVAC DESIGN REQUIRES
YES
NO
DUCT SMOKE DETECTOR
•
Suite 140
FIRE DAMPER(S)
•
SMOKE DAMPER(S)
•
FIRE RATED ENCLOSURE
E:
•
FIRE RATED ROOF / FLOOR CEILING ASSEMBLY
AA. 26000903 AR.
•
FIRE STOPPING
•
SMOKE CONTROL
independent forum
•
000� 00,0<1
00 1
0111111 .0001,
.0(0 11111100,00
0000 10 -
J
CITY Cyr ;)t)UTH MIAMI
SECTION
�>
ISSUED FOR PERMIT Oct 08, 2007
ISSUED FOR CONSTRUCTION - -I
K AMM CONSULTING PROJECT #: 2007 -0307
PROJECT MANAGER: Nicholas Melisiotis, P E
ffff 1407 West N e ac , M Deerfield BC2•�•y "
Phone 954.949 C ' F ' �'•y �,' '
-
Fax954.949.220L
OIISY engineering@katbm '
Certificativn'ofAuth 619 '
DIRECTOR OF ELECTRICAL ENGINEERING D„ fete ; Y' 7r,9.00.7-:-'
Lon T. Carter Florida License #35249 "
DIRECTOR OF MECHANICAL ENGINEERING '-
Mircea Pella Florida License #48798 �F�fr sig�rC ..• ��
004,8#80604 Its%%
,,, �•
Maverick Architecture &
Design, Ilc.
6675 Westwood Blvd.
Suite 140
Orlando, Florida 32821
T: 407.351.8787
F: 407.351.9254
E:
Info @MaverickArchDes.com
AA. 26000903 AR.
91835
a conceptually
independent forum
M
M
>
M
.a
CU
�
sL
0
Cl)
LL
p
•E
/: h
c
M
"CC�
0
G
I -_ LID
r
0
m
O
c
o
Q
x
n
Q
v
m
V
LU
m
0
d
�
I HEREBY CERTIFY THAT THESE DRAWINGS AND
SPECIFICATIONS WERE PREPARED UNDER MY
DIRECT SUPERVISION AND TO THE BEST OF MY
KNOWLEDGE COMPLY WITH THE STATE BUILDING
AND ZONING ORDINANCES.
SIGNED
STATE REGISTRATION
DATE
MECHANICAL
NOTES
mom
Drawing No.