07-1661-008CONSTRUCTION NOTES: 1. DIMENSIONS TO AND BETWEEN PARTITIONS TO FACE OF GYPSUM BOARD SURFACES — NOT INCLUDING FINISHES UNLESS OTHERWISE NOTED. DIMENSIONS MARKED AS HOLD SHALL TAKE PRECEDENT OVER OTHER DIMENSIONS SHOWN IN THE DIMENSION STRING. THE G.C. SHALL VERIFY ALL DIMENSIONS DURING THE LAYOUT PROCESS AND SHALL REPORT ANY DISCREPANCIES TO THE ARCHITECT IMMEDIATELY. 2. THE G.C. SHALL FIELD VERIFY ALL CLEARANCES REQUIRED FOR EQUIPMENT AND FURNISHINGS. REFER TO EQUIPMENT AND FURNISHING DRAWINGS FOR LOCATIONS AND DIMENSIONS PRIOR TO INSTALLATION. 3. REFER TO THE PARTITION TYPE SCHEDULE FOR THE TYPICAL WALL CONSTRUCTION. MATERIAL FINISHES ARE DESCRIBED IN THE FINISH SCHEDULE AND INTERIOR ELEVATIONS. 4. MILLWORK DIMENSIONS ARE OVERALL DIMENSIONS — REFER TO DETAILS. 5. VERIFY ROUGHED -IN OPENINGS PRIOR TO FABRICATING MILLWORK, DOOR AND WINDOW FRAMES. 6. SEE MECHANICAL, PLUMBING, ELECTRICAL AND KITCHEN DRAWINGS FOR LOCATIONS OF FLOOR PENETRATIONS. 7. G.C. TO COORDINATE LOCATION OF REFRIGERATION /SODA/P.O.S. SYSTEM(S) LINES WITH APPROPRIATE SUBCONTRACTOR(S) PRIOR TO FINISHING SURFACES. 8. REFER TO INTERIOR ELEVATIONS, DETAILS AND ROOM FINISH SCHEDULE FOR FINISHES. 9. ALL KITCHEN, SERVICE STATION, AND RESTROOM WALLS SHALL BE SHEATHED WITH MOISTURE RESISTANT GYPSUM BOARD. 10. ALL EXIT DOORS TO SWING IN DIRECTION AS PER CODE AND TO BE OPERABLE WITH A MAXIMUM OF (15) POUNDS OF PRESSURE. 11. ALL WASHROOM WALLS ADJACENT TO PUBLIC AREA SHALL BE FURNISHED WITH SOUND INSULATION BATTS, INCLUSIVE. 12. ALL WOOD USED FOR FRAMING AND BLOCKING SHALL BE TREATED WITH A FIRE RETARDANT TO COMPLY WITH THE REQUIREMENT FOR A FLAME SPREAD RATING OF 26 TO 75, CLASS II OR BETTER, WITH NO SIGNIFICANT EVIDENCE OF PROGRESSIVE COMBUSTION WHEN TESTED FOR A TIME OF 30 MINUTES UNDER STANDARD TEST METHOD FOR FIRE HAZARD CLASSIFICATION OF BUILDING MATERIALS (ASTM E-84). EACH PIECE OF WOOD SHALL BEAR THE U.L. LABEL INDICATING COMPLIANCE WITH THE FIRE HAZARD CLASSIFICATION. 13. ALL MATERIAL USED FOR INTERIOR WALL AND CEILING FINISH SHALL BE NOT GREATER THAN A FLAME SPREAD RATING OF 76-200 CLASS III, EXCEPT TEXTILE WALL COVERINGS AND AT REQUIRED VERTICAL EXITWAYS /PASSEGEWAYS /CORRIDORS PROVIDING EXITWAY ACCESS, WHEREBY SUCH MATERIAL SHALL HAVE A FLAME SPREAD RATING OF 26 TO 75, CLASS 11. 14. G.C. TO COORDINATE LOCATION OF ALL BLOCKING REQUIRED FOR KITCHEN EQUIPMENT WITH KITCHEN EQUIPMENT CONTRACTOR. ALL BLOCKING SHALL BE INSTALLED DIRECTLY TO ROUGH METAL STUDS. G.C. TO FURNISH ALL BLOCKING REQUIRED AND VERIFY INSTALLATION IN FIELD. 15. VERTICAL PIPING LOCATED WITHIN THE STUD SPACE OF PARTITIONS SHALL BE COMPLETELY ENCLOSED WITH FULL THICKNESS OF DRYWALL ON EACH SIDE. 16. JOINTS OCCURRING IN RATED DRYWALL PARTITIONS SHALL BE STAGGERED BOTH HORIZONTALLY AND VERTICALLY. 17. STOREFRONT GLASS SHALL MEET FLORIDA IMPACT HURRICAN CODE. 18. ENSURE THAT ALL EXISTING WALLS TO REMAIN HAVE BEEN PATCHED, REPAIRED AND PRIMED AS NECESSARY PRIOR TO THE APPLICATION OF ALL NEW FINISH TREATMENTS. 19. KITCHEN WALLS SHALL UTILIZE HEAVY DUTY STEEL STUDS- 16 GAUGE @ALL STAINLESS STEEL WALL SHELVING LOCATIONS (SEE KITCHEN DRAWINGS). 20. CUSTOMER ENTRANCE AIR CURTAINS TO BE WALLMOUNTED G.C. TO PROVIDE ADDITIONAL BACKING REQUIRED. SECTION 1 10 PLAN 3 %* STUD CHANNEL 20 GA. UNLESS SPECIFIED ----FRP OVER GYP. BRD. ON WET SIDE OF WALL ' GYP BRD. TERMINATE 6' ABOVE CEILING HE3GHT 11 WALL BATT INSULATION 18' FIBER CEMENT BOARD ON WET SIDE OF WALL 3 96' STUD CHANNEL 20 GA. UNLESS SPECIFIED CON SLAB 1 WAIL BATT INSULATION 3 9C MTL STUDS 0 GA. 0 16' O.C. UNLESS SPECIFIED %' GYP BOARD BOTH SIDES, TAPED, SANDED AND SEALED. FRP OVER GYP. BRD. ON WET SIDE OF WALL FAI ' 4, A ARTITION WALL - NOT RATED SCALE: 1"=1'-0" 6 ARTITION WALL - NR TO B.O. DECK LE:1 " =1' -0" 1' X 8' WOOD CAP, PAINTED (SEE ELEVATIONS) 1/2' X 1 1/2' WOOD TRIM, PAINTED (SEE ELEVATIONS) 5 1/Y X 3' WOOD TRIM, PAINTED (SEE ELEVATIONS) 1/2' X 4 1/2' WOOD TRIM, PAINTED (SEE ELEVATIONS) .f 3-518' MTL STUDS (20 GA.) 016' O.C. MAX. SECTION (1) LAYER 518' TYPE 'X" GYPSUM BOARD EACH SIDE W/ JOINTS STAGGARED (PROVIDE WATER RESISTANT GYP. BD. IN WET AREAS) 5/8' MTL STUD TRACK (0 GA.) NYL BASE (SEE FLOOR FINISH PLAN) OOR PERIMETER CAULKED E ASTING CONCRETE SLAB PLAN �-4' OR If MTL STUDS 0 GA. 16' O.C. UNLESS SPECIFIED 9C TYPE 'X' GYP BOARD BOTH SIDES, TAPED, SANDED AND SEALED TO STRUCTURE ABOVE PER 1 HR FIRE RATING. RE U419 THIS SHEET. PARTIAL HEIGHT WALL - NOT RATED SCALE: 1"=1'-0" �L-' r t• 4� SWIFT TO PUNCTURE THROUGH EXISTING DECK rol"m ROOF DECK 7 SECTION WITH SEALANT (ALL SIDES) 11 WALL BAIT INSULATION 1' SWIFT LINER PANEL sHAFT 2) LAYERS W TYPE 'X' GYP BOARD, TAPED, SANDED AND SEALED TO STRUCTURE ABOVE PER 2NR FIRE RATING. RE U438. 2 1/2' GA. METAL 'C -H' STUDS 0 24' O.C. CONCRETE SLAB LJ LSH SIDE PLAN 1' SWIFT LINER PANEL �IN 2 1/2' GA. METAL 'C -H' STUD 0 24' O.C. (2) LAYERS %' TYPE 'x' GYP BOARD, TAPED, SANDED AND SEALED TO STRUCTURE ABOVE PER 2HR FIRE RATING. RE U438. SHAFT WALL - 2 HOUR RATED SCALE: 1"=I'-O" EXISTING ROOF DECK CAULK WITH APPROVED SEA ANT ( SIDE) SECTION 4' OR 6" STUD CHANNEL 0 GA. UNLESS SPECIFIED R11 WALL BATT INSULATION NON LOAD BEARING PARTITION WALL SKI TERMINATE AT ROOF DECK ABOVE W TYPE X GYP BOARD BOTH SIDES. TAPED, SANDED AND SEALED TO STRUCTURE ABOVE PER 1HR FIRE RATING. RE U419 THIS SHEET 4' OR 6' STUD CHANNEL 0 GA. UNLESS SPECIFIED NG CONCRETE SLAB [OW-11 1 WALL BATT INSULATION I �-4' OR 6' MTL STUDS 20 GA. I 16' O.C. UNLESS SPECIFIED %' TYPE 'X' GYP BOARD BOTH SIDES, TAPED, SANDED AND SEALED TO STRUCTURE ABOVE PER 1HR FIRE RATING. RE 0419 THIS SHEET. 2 PARTITION WALL - 1 HOUR RATED SCALE: 1"=1'-0" NOTE: ALL WET LOCATIONS (KITCHEN, RESTROOMS, BARS, STORAGE ROOMS 119 AND 121 AND EMPLOYEE RESTROOMS) SHALL BE PROTECTED BY THE LATICRETE 254 PLATINUM (SKIM COAT), LATICRETE 9235 (WATERPROOFING MEMBRANE), SPECTRALOCK PRO GROUT AND 1776 GROUT ENHANCER, TO COMPLETE THE WATER PROOFING SYSTEM. ALL WET LOCATIONS (KITCHEN, RESTROOMS, BARS, STORAGE ROOMS 119 AND 121 AND EMPLOYEE RESTROOMS) SHALL HAVE CEMENT BOARD 18' ABOVE EASTING SLAB OR FROM TOP OF CONSTRUCTED PLATFORMS. i9° SECTION V EXISTING CMU 1 )!' METAL Z- FURRING CHANNELS WITH RIGID INSULATION 96' GYP. BOARD APPLIED TO THE RETAIL SIDE THAT SHALL TERMINATE 6' ABOVE CE]UNG. -OWNG CONCRETE SLAB PLAN EXISTING CMU 9%' GYP. BOARD OVER 1)f MIL Z- FURRING CHANNELS, TAPED AND SANDED CMU W/ FURRING CHANNELS SCALE: 1"=l'-O" SECTION PLAN 3 96' STUD CHANNEL 20 GA. UNLESS SPECIFIED FINISH CEILING '--9c GYP BRD. TERMINATE 6' ABOVE CEILING HEIGHT ,,,—Rll WALL BATT INSULATION 396' SAID CHANNEL 20 GA. UNLESS SPECIFIED NG CONCRETE SLAB 1 WALL BATT INSULATION 3 96' MTL STUDS 20 GA. 0 16' O.C. UNLESS SPECIFIED 96' GYP BOARD BOTH SIDES, TAPED, AND SEALED PARTITION WALL - NOT RATED SCALE: 1'=l'-O" PARTITION WALL - MR) TO B.O. DECK n G E asiyn, 11" 6675 Westivrood vSul- B�lI. Sue 40 Orlando, Porida 52821 40/.351.8/8/ II�: 1- IO /.SSI.Q2b4 1=_: I n f o@ Maveric�A—ch Des.com Ai--i• 26000Q03 Q'835 a conceptual ,{ it eperJert forum i r co dj r- � M > co 0:9 N 0 C LL c "E co N p LO CC0 M co 0 0 m �OWr F- = O o W n O D- - U 0_ N W O 0 OW o (n W W I Q U N r' Z y J j '��: / J .1 ��'I1 , � ,•hip Interior Wall Ty 1 and Construction N i i ■ Drawing No.