B. PROVIDE SAFETY AND DISCONNECT SWITCHES. FUSED OR NONFUSED,
AS CALLED FOR ON DRAWINGS AND AS REQUIRED BY CODE. (FUSES
AS MANUFACTURED BY BUSSMAN, CHASE SHAWMUT, WESTINGHOUSE,
ECONOMY FUSE CO.. OR LITTLE FUSE CO. ARE ACCEPTABLE).
DISCONNECT SWITCHES THAT ARE INSTALLED AT AIR CONDITIONING
EQUIPMENT, HEAT PUMPS, ETC SHALL BE FUSED IN ACCORDANCE
WITH THE EQUIPMENT'S NAME PLATE REQUIREMENTS PER N.E.C.
440-21 do 110 -3B.
SWITCHES SHALL BE HEAVY DUTY, QUICK MAKE /QUICK BREAK TYPE,
FUSIBLE OR NON — FUSIBLE, WEATHERPROOF AS INDICATED ON THE
DRAWINGS, OR AS REQUIRED BY LOCAL CODES. LOAD AND
HORSEPOWER RATED AS MANUFACTURED BY SQUARE D. GOULD ITE,
CHALLENGER, CUTLER HAMMER, WESTINGHOUSE. FEDERAL PACIFIC,
OR GENERAL ELECTRIC (OR APPROVED EQUAL).
C. MANUAL MOTOR STARTERS WITH OVERLOAD PROTECTION MAY BE USED
FOR FRACTIONAL HORSEPOWER MOTORS THAT DO NOT REQUIRE
AUXILIARY CONTROL SINGLE PHASE STARTERS SHALL BE SQUARE
D OR EQUAL THREE PHASE STARTERS SHALL BE PROVIDED WITH
OVERLOAD DEVICE IN EACH PHASE MATCHED TO MOTOR NAMEPLATE
RATING. MAGNETIC MOTOR STARTERS (MINIMUM SIZE #1) SHALL
BE USED FOR ALL SINGLE PHASE AND THREE PHASE MOTORS RATED
ABOVE 1/2 HP OR THAT REQUIRE AUXILIARY CONTROL PROVIDE
CONTROL DEVICES (CONTACTS, TRANSFORMERS. ETC.) IN STARTERS
AS REQUIRED FOR INTERLOCKS, COORDINATE WITH MECHANICAL
AND /OR TEMPERATURE CONTROL CONTRACTORS. COMBINATION
STARTERS, WHEN USED, SHALL CONTAIN FUSIBLE SWITCHES.
BOXES:
A. OUTLET BOXES AND COVERS SHALL BE GALVANIZED, ONE —PIECE
PRESSED STEEL KNOCKOUT.
B. JUNCTION. PULL BOXES AND COVERS SHALL BE GALVANIZED STEEL,
CODE GAUGE SIZE.
C. INSTALL BOXES RIGIDLY ON BUILDING STRUCTURE AND SUPPORT
INDEPENDENTLY OF THE CONDUIT SYSTEM. ALSO PROVIDE
SUITABLE/PROPER BOX EXTENSIONS TO EXTEND BOXES TO FINISHED
FACES OF WALLS ETC. ALL OUTLET BOXES TO HAVE SUITABLE
BLOCKING BEHIND THEM TO MINIMIZE THE DEFLECTION THAT
OCCURS WHEN PLUGGING/UNPLUGGING INTO THESE DEVICES.
D. WHERE A 277 VOLT LIGHT SWITCH IS GANGED WITH A 120 VOLT
RECEPTACLE PROVIDE A SUITABLE DIVIDER OR SEPARATE JUNCTION
BOXES IN ACCORDANCE WITH NEC AND LOCAL CODES.
SERVICES:
A. ELECTRICAL CONTRACTOR SHALL PROVIDE TEMPORARY SERVICE FROM
LANDLORD'S DESIGNATED LOCATION AND PROVIDE LIGHTING, POWER
AND WIRING AS REQUIRED TO FACILITATE APPLICABLE TEMPORARY
NEEDS, AND FURNISH EXTENSION CORDS. ANY TEMPORARY
WIRING, FUSES, ETC., SHALL BE REMOVED UPON
COMPLETION OF THE PROJECT. PROVIDE GROUND FAULT
PROTECTION AS REQUIRED BY N.E.C. AND LOCAL CODES.
B. PROVIDE ELECTRICAL SERVICE AS SHOWN ON THE DRAWINGS, FIELD
VERIFY EXACT REQUIREMENTS PRIOR TO BIDS. ALL WORK NOT
SPECIFICALLY NOTED AS BEING BY THE LANDLORD OR POWER
COMPANY SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR.
CLOSELY COORDINATE ENTIRE INSTALLATION WITH LANDLORD AND
POWER COMPANY AS REQUIRED. (PROVIDE EQUIPMENT THAT IS
COMPATIBLE WITH AVAILABLE FAULT CURRENT LEVELS, PROVIDE
"CABLE LIMITERS" IF NECESSARY FOR SYSTEM COORDINATION).
FIELD VERIFY EXACT TYPE, SIZE, LOCATION, REQUIREMENTS,
ETC. OF EXISTING POWER AND TELEPHONE FACIU71ES PRIOR TO
BIDDING PROJECT.
C. MAKE PROVISIONS FOR NEW TELEPHONE SERVICE AS REQUIRED, AND
AS INDICATED ON THE DRAWINGS.
D. CONDUIT SYSTEM FOR TELEPHONE DISTRIBUTION WITHIN TENANT'S
PREMISES SHALL BE PROVIDED AS REQUIRED FOR A COMPLETE
TELEPHONE SYSTEM. OUTLET BOXES SHALL BE a SQUARE
MINIMUM WITH SINGLE DEVICE COVER AND TELEPHONE PLATE.
CLOSELY FIELD COORDINATE WITH TENANTS CONSTRUCTION MANAGER
TO AVOID CONFLICTS.
STEP —DOWN TRANSFORMER:
A. PROVIDE A DRY —TYPE TRANSFORMER OF THE ENCLOSED VENTILATED
TYPE WITH KVA AND VOLTAGE RATINGS AS CALLED FOR ON THE
DRAWINGS AND WITH COILS DESIGNED FOR 150 DEGREES C. RISE
ABOVE A 40 DEGREE C. AMBIENT WITH 100X OF RATED LOAD
CONNECTED TO THE SECONDARY, CLASS H INSULATION AND MINIMUM
OF SIX STANDARD FULL CAPACITY TAPS. (TWO ABOVE AND FOUR
BELOW NORMAL) SOUND LEVEL/bECIBELS SHALL BE IN ACCORDANCE
WITH "NEMA" STANDARDS. AND INSTALLATION SHALL INCLUDE
KORFOUND OR EQUAL VIBRATION— DAMPENING MOUNTS AND FLEXIBLE
STEEL CONDUIT FOR PRIMARY AND SECONDARY CONNECTIONS TO
MINIMIZE SOUND TRANSMISSION. (MOUNT TRANSFORMER ON
SEPARATE VIBRATION ISOLATORS, THESE ARE ADDITIONAL
VIBRATION ISOLATORS AND ARE USED IN CONJUNCTION WITH ANY
INTEGRAL FACTORY INSTALLED VIBRATION ISOLATORS.) AS
MANUFACTURED BY SQUARE D, HEAVY DUTY, ACME, GENERAL
ELECTRIC OR WESTINGHOUSE.
LIGHTING CONTACTOR AND TIME SWITCH:
A. CONTACTORS FOR CONTROL OF LIGHTING SHALL BE ASCO BULLETIN,
917 SERIES IN A NEMA 1 ENCLOSURE, OR EQUAL BY SQUARE "D",
CUTLER HAMMER. GENERAL ELECTRIC OR WESTINGHOUSE, ENCLOSED,
ELECTRICALLY OPERATED, MECHANICALLY HELD. TIME SWITCHES FOR
CONTROL OF LIGHTING SHALL BE 7 DAY TYPE WITH RESERVE POWER.
"TORK% SERIES DWZ100A, WITH ASTRONOMIC OPTION, OR EQUAL BY
SANGAMO OR PARAGON.
INSTALLATION:
A. ALL ELECTRIC WORK SHALL BE INSTALLED SO AS TO BE READILY
ACCESSIBLE FOR OPERATING, SERVICING. MAINTAINING AND
REPAIRING. HANGERS SHALL INCLUDE ALL MISCELLANEOUS STEEL
SUCH AS CHANNELS, RODS, ETC., NECESSARY FOR THE
INSTALLATION OF WORK AND SHALL BE FASTENED TO BUILDING
STEEL, CONCRETE OR MASONRY, BUT NOT PIPING OR DUCTWORK.
ALL CONDUIT SHALL BE CONCEALED WHEREVER POSSIBLE. EXPOSED
CONDUITS SHALL BE IN STRAIGHT LINES PARALLEL WITH OR AT
RIGHT ANGLES TO COLUMN LINES OR BEAMS AND SEPARATED AT
LEAST 3 INCHES FROM WATER LINES WHEREVER THEY RUN
ALONGSIDE OR ACROSS SUCH LINES. ALL CONDUCTORS SHALL BE
IN CONDUIT, DUCTS OR OTHER CODE APPROVED RACEWAYS.
11 1 12 1 13 1 14
B.
1 2 3
4
5 6 7
r
= :
Electrical Specifications
ELECTRICAL CONTRACTOR. (ALL LINE VOLTAGE WIRING, CONDUIT,
N
AND FINAL CONNECTIONS FROM THE POWER SOURCE THRU THE
STARTER/DISCONNECT ETC. TO THE MOTOR OR EQUIPMENT IS THE
RESPONSIBILITY OR THE ELECTRICAL CONTRACTOR. ALL HVAC
ELECTRICAL SPECIFICATIONS
CONNECTIONS IS THE RESPONSIBILITY OF THE
GENERAL CONDITIONS:
OTHERWISE NOTED ON THE PLANS).
C.
A.
THE REQUIREMENTS AS SET FORTH UNDER GENERAL CONDITIONS,
F.
SECURE ALL RACEWAYS TO THE BUILDING STRUCTURE IN A RIGID
ELECTRICAL DIVISION, ANY CUTTING SHALL HAVE PRIOR APPROVAL
INSTRUCTIONS TO BIDDERS AND GENERAL REQUIREMENTS ARE A
AND SECURE MANNER, USING FASTENERS SUCH AS "CADDY CUPS"
ETC., THROUGH FIRE RATED WALLS AND FLOORS SHALL BE FIRE
PART OF THIS CONTRACT.
SEALED WITH CALCIUM SILICATE. SILICONE "RTV" FOAM. "3M"
OR EQUAL
FIRE RATED SEALANTS OR EQUAL BY HILTI AFTER CONDUIT /CABLES
B.
BIDS SHALL BE BASED ON A COMPLETE/FULL SET OF DRAWINGS.
G.
FLASH AND COUNTERFLASH ALL RACEWAYS WHICH PENETRATE THE
CONCERNED, SHALL AT ALL TIMES KEEP THE PREMISES IN A NEAT
AND ORDERLY CONDITION AND. AT THE COMPLETION OF THE WORK,
ROOF OR USE PITCH POCKETS. INSURE THAT PENETRATIONS ARE
M
C.
CONTRACTOR MUST READ THE ENTIRE SPE FIC,AlIMS- COrERING
E.
COMPLETELY WEATHERPROOF. ALL RACEWAY SYSTEMS EXPOSED TO
BAKELITE NAMEPLATES AS TO NAME AND /OR FUNCTION;
OTHER BRANCHES OF WORK AND'IS RESPdN5IBL:E ftR t
DISTRIBUTION PANELS, LIGHTING PANELS, MOTOR STARTERS AND
THE WEATHER SHALL BE WEATHERPROOF. PRIOR APPROVAL BY
DISCONNECT SWITCHES. NAMEPLATES TO BE APPROXIMATELY 1" X
COORDINATION OF THE WORK WITH WORK PFRFORMEP BY
F.
LANDLORD IS REQUIRED TO ADD ADDITIONAL EQUIPMENT LOADS TO
DRAWINGS ARE APPROXIMATE AND THE ARCHITECT/TENANT
,OTHER TRADES. ••'
CONSTRUCTION MANAGER SHALL HAVE THE RIGHT TO RELOCATE ANY
STRUCTURE OR TO MAKE HOLES IN EXISTING ROOF. NOTIFY
OUTLETS OR FIXTURES BEFORE THEY ARE INSTALLED WITHOUT
-
"""°
G.
LANDLORD'S ROOFING CONTRACTOR AT LEAST 72 HOURS PRIOR TO
SCOPE' OF WORK: , ,�,
ANY REQUIRED ROOF WORK.
A.
CONTRACTOR SHALL VISIT SITE PRIOR TO BIDDING.'- 'BIDS SHALL
WIRE:
AGAINST DAMAGE FROM LEAKS, ABUSE. ETC., AND PAY COST OF
SERVE AS EVIDENCE OF KNOWLEDGE OR EXISTING CONDITIONS.
NECESSARY BY FAILURE TO PROVIDE SUITABLE SAFEGUARDS OR
PROTECTION.
ALL REQUIREMENTS INCLUDING MODIFICATIONS WHICH ARE
A.
WIRE SHALL BE SINGLE CONDUCTOR COPPER WITH 600 VOLT
'
REQUIRED TO MEET THE INTENT OF-,THE DRAWINGS : AMA, ,
INSULATION. MINIMUM WIRE SIZE SHALL BE #12 AWG, ALL WIRE
L
THIS WORK .JUST PRIOR TO COMPLETION OF PROJECT.
SPECIFICATIONS ARE TO BE OBTAI BY ELECTRICAL CONTRACTOR
THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ANY /ALL
AND CABLE SHALL BE NEW AND SHALL BE BROUGHT TO THE S17E IN
NECESSARY ELECTRICAL DEMOLITION WORK THAT IS REQUIRED TO
PRIOR TO AND INCLUDED IN BID PRICE. FIELD, VERIFY ALL
UNBROKEN PACKAGES. ALL WIRING OF ANY TYPE SHALL BE IN
`
FOR A COMPLETE INSTALLATION. ANY EQUIPMENT OR DEVICE
EXISTING ELECTRICAL AND TELEPHONE' EQUIPMENT, -LOCATIONS,
REMAINING IN USE AFTER PART OF THE EQUIPMENT OR DEVICES
CONDUIT. NO STRANDED WIRE ALLOWED FOR #10 AND #12 AWG
HAVE BEEN-REMOVED ARE TO BE RECONNECTED TO EXISTING OR NEW
`CIRCUITSkkD
CONDITIONS ETC. FAILURE TO. VISIT THE SITE SHALL NOT,
-
SIZES. (INCREASE CONDUCTOR BY ONE SIZE FOR EVERY 150'
-
AREAS. COORDINATE ANY DISRUPTION OF ELECTRICAL
RELIEVE THE CONTRACTOR FROM ANY RESPONSIBILITY IN THE
OR TELEPHONE SERVICES WITH LANDLORD AND TENANT
INCREMENT OF DISTANCE FROM THE PANEL BOARD FOR 120 VOLT
CONSTRUCTION MANAGER TO AVOID CONFLICTS.
GUARANTEE:
PERFORMANCE OF THE ELECTRICAL WORK.,
A.
CIRCUITS.)
B.
FURNISH ALL LABOR, MATERIALS, TESTING, EQUIPMENT, '.;
DEFECTS WHICH APPEAR DURING THAT PERIOD SHALL BE CORRECTED
1. GENERAL WIRING SHALL BE THW OR THHN. (ALUMINUM
AT THE ELECTRICAL CONTRACTOR'S EXPENSE.
B.
INCIDENTALS AND TOOLS TO PERFORM ELECTRICAL - WORK SHOWN,
CONDUCTORS ARE NOT PERMITTED.)
IN WORKMANSHIP OR IN THE WORK OR EQUIPMENT FURNISHED
NOTED OR SCHEDULED FOR A COMPLETE AND FINISHED
AND /OR INSTALLED BY THE ELECTRICAL CONTRACTOR.
FINALLY:
A.
IT IS THE INTENT THAT THE FOREGOING WORK SHALL BE COMPLETE
INSTALLATION.
IN EVERY RESPECT AND THAT ANY MATERIAL OR WORK NOT
K
;�'
B.
WIRE CONNECTORS SHALL BE EQUAL TO SCOTCHLOCK FOR #8 AND
1. MATERIALS, PRODUCTS AND EQUIPMENT, INCLUDING ALL
SMALLER, AND EQUAL TO T do B "LOCK —TITS" FOR #6 AND LARGER.
COMPONENTS THEREOF, SHALL BE NEW AND AS SUCti APPEAR ON
;-
THE UNDERWRITERS LABORATORIES LIST OF APPROVED ITEMS
C.
THE USE OF SHARED NEUTRALS IS ACCEPTABLE FOR LIGHTING AND
AND SHALL BE SIZED IN CONFORMITY WITH REQUIREMENTS OF
RECEPTACLE CIRCUITS IF INSTALLED IN ACCORDANCE WITH N.E.C.
THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND
#310, AND LOCAL CODES.
OTHER APPLICABLE CODES, WHICHEVER ARE' MORE STRINGENT.
C.
THE WORK IS TO BE IN ACCORDANCE WITH THE LATEST EDITION OF
LIGHTING:
THE NEC AND ALL APPLICABLE FEDERAL, STATE AND LOCAL CODES.
A.
LIGHTING FIXTURES AND LAMPS SHALL BE FURNISHED AS
J
D.
INCLUDE ANY LABOR AND MATERIALS NOT SPECIFICALLY
SCHEDULED ON THE LIGHTING FIXTURE SCHEDULE. (THE MAJORITY
OR THE FIXTURES AND LAMPS ARE FURNISHED BY THE TENANT)
MENTIONED, BUT NECESSARY TO PROVIDE A COMPLETE AND FULLY
ELECTRICAL CONTRACTOR SHALL INSTALL ALL FIXTURES AND
OPERATIVE ELECTRICAL SYSTEMS: ,, i. „: �;. ,
LAMPS. FLUORESCENT FIXTURES SHALL HAVE HPF BALLASTS WITH
-
PERMITS:
EFFICIENCY FACTORS IN ACCORDANCE WITH "NATIONAL APPLIANCE
ENERGY CONSERVATION ACT OF 1987. AMENDMENTS OF 1988."
A.
SECURE AND PAY FOR ALL REQUIRED PERMITS, FEES, ASSESSMENTS
B.
LIGHT FIXTURES SHALL BE SUPPORTED FROM THE BUILDING
.AND INSPECTION CERTIFICATES THAT RELATE TO THE ELECTRICAL
STRUCTURAL VIA ALL THREAD AND UNI— STRUT, AND NOT SUPPORTED BY
CONTRACT.
CEILING SYSTEM.
H
B.
FURNISH APPROVED CERTIFICATE OF FINAL INSPECTION, AND TURN
WIRED
GROUND SYSTEM:
OVER TO OWNER AT COMPLETION OF PROJECT.
A.
FURNISH AND INSTALL A COMPLETE WIRED GROUNDING SYSTEM FOR
DRAWINGS
AND SPECIFICATIONS:
ELECTRICAL EQUIPMENT AND CIRCUITS AS SHOWN ON THE DRAWINGS
AND DESCRIBED GENERALLY BELOW.
A.
THIS ELECTRICAL PLANS ARE DIAGRAMMATIC, NOT SHOWING EVERY
ITEM IN EXACT LOCATION OR DETAIL MEASUREMENTS AND
B.
ALL GROUNDING CONDUCTORS SHALL BE GREEN, WHERE EXPOSED IN
LOCATIONS MUST BE FIELD VERIFIED AND COORDINATED WITH
PANEL, SWITCHBOARD, OUTLET, BOXES, ETC.
ARCHITECTURAL, PLUMBING, HVAC, FIRE PROTECTION,
STRUCTURAL AND OTHER BUILDING DRAWINGS.
C.
ALL ENCLOSURES AND NON— CURRENT CARRYING METALS TO BE
G
GROUNDED. CONDUIT SYSTEM TO BE ELECTRICALLY CONTINUOUS.
SHOP
DRAWINGS:
ALL LOCK NUTS MUST CUT THROUGH ENAMELED OR PAINTED
_
SURFACES ON ENCLOSURES. WHERE ENCLOSURES AND NON— CURRENT
-
A.
SUBMIT FIVE COPIES OF MATERIAL LISTS AND SHOP DRAWINGS FOR
CARRYING METALS ARE ISOLATED FROM THE CONDUIT SYSTEM, USE
MAJOR EQUIPMENT TO THE OWNER'S CONSTRUCTION MANAGER FOR
BONDING JUMPERS WITH APPROVED CLAMPS.
'
APPROVAL PRIOR TO ORDERING EQUIPMENT. CONTRACTOR SHALL
SUBMIT SHOP DRAWINGS EARLY ENOUGH IN PROJECT TO ALLOW
D
RUN A SEPARATE GROUNDING CONDUCTOR IN EACH CONDUIT #12
AMPLE TIME FOR OWNER'S REVIEW WITHOUT CAUSING TIME DELAYS
MINIMUM, OR AS SHOWN ON DRAWINGS. FOR PANEL FEEDERS BOND
OR CONFLICTS IN THE JOB PROGRESS. SUBMITTALS SHALL BE IN
THE GROUNDING CONDUCTOR TO THE CONDUIT, WHERE ENTERING AND
ACCORDANCE WITH GENERAL CONDITIONS AND THE MANUFACTURERS
LEAVING THE CONDUIT. ALL GROUND CLAMPS SHALL BE PENN—
LISTED ON THE DRAWINGS AND SHALL BEAR THE STAMP OF THE
UNION OR EQUAL. SIMILAR TO "GPL" TYPE. CONDUIT GROUND
F
CONTRACTOR SHOWING THAT HE HAS REVIEWED AND APPROVED THEM
BUSHINGS SHALL BE THOMAS do BETTS OR EQUAL, SIMILAR TO
AND THAT THEY ARE IN CONFORMANCE WITH THE CONTRACT
#3800 SERIES WITH NYLON INSULATED THROAT.
DRAWINGS. LACK OF SUCH CONTRACTOR'S APPROVAL WILL BE
CAUSE FOR REJECTION WITHOUT REVIEW BY THE OWNER.
E.
ALL DEVICES SHALL BE BONDED TO THE CONDUIT SYSTEM. USE A
BONDING JUMPER BETWEEN THE OUTLET BOX AND THE DEVICE
-
B.
WHERE TRADE NAMES, BRANDS OF MANUFACTURERS OF EQUIPMENT OR
GROUNDING TERMINAL METAL —TO —METAL CONTACT BETWEEN THE
MATERIALS ARE SHOWN ON THE DRAWINGS OR SPECIFICATIONS THE
DEVICE YOKE AND THE OUTLET BOX IS NOT ACCEPTABLE AS A BOND
EXACT EQUIPMENT SHALL BE USED ON THE PROJECT. THE USE OF
FOR EITHER SURFACE MOUNTED BOXES OR FLUSH TYPE BOXES. ALL
-
ANY UNAUTHORIZED EQUIPMENT SHALL BE SUBJECT TO
JUNCTION BOXES, OUTLET BOXES AND PULL BOXES SHALL BE
REMOVAL/REPLACEMENT AT THE REQUEST OF THE OWNER'S
BONDED TO THE CONDUIT SYSTEM. ALL FLEXIBLE CONDUIT SHALL
CONSTRUCTION MANAGER (AT THE ELECTRICAL CONTRACTORS
BE JUMPERED WITH A GROUND CONDUCTOR.
E
EXPENSE).
WIRE
DEVICES:
CONDUITS:
A.
CONDUIT SHALL BE STANDARD STEEL RIGID, AMC OR EMT THIN
(
A.
COLOR OF WIRING DEVICES AND COVERPLATES SHALL BE SELECTED
BY ARCHITECT. (SEE PLAN NOTES FOR ADDITIONAL
WALL) ACCORDING TO LOCAL CODE AND LANDLORD REQUIREMENTS.
INFORMATION).
CONDUIT SHALL BE CONCEALED IN FINISHED 'AREAS, EXCEPT AS
OTHERWISE APPROVED BY ARCHITECT. EMT CONNECTIONS SHALL BE
1. RECEPTACLES SHALL BE 20 AMP, 3 —WIRE GROUNDING TYPE
COMPRESSION OR SET SCREW TYPE.
EQUAL TO HUBBELL 5362.
-
B.
FLEXIBLE CONDUIT OR TYPE MC CABLE SHALL BE USED FOR FINAL
2. SWITCHES SHALL BE 20 AMP SPECIFICATION GRADE, RATED AT
CONNECTIONS TO LIGHT FIXTURES, MOTORS AND VIBRATING
120 OR 277 VOLT, AS REQUIRED.
-
EQUIPMENT ONLY; AND WHERE SO USED TO BE GROUNDED WITH A
SEPARATE FULL SIZED GREEN GROUNDING CONDUCTOR. FINAL TYPE
3. SPECIAL DEVICES SHALL BE A SPECIFICATION GRADE.
MC/FLEX CONNECTIONS SHALL BE LIMITED TO 8' -0" IN LENGTH.
(ARRANGE CIRCUITS SO AS TO AVOID THE USE OF JUNCTION BOXES
4. ALL DEVICE COVERPLATES SHALL BE STAINLESS STEEL
ABOVE DRYWALL CEILING AREAS, JUNCTION BOXES LOCATED ABOVE
LAY —IN CEILINGS ARE ACCEPTABLE.)
5. FLOOR BOXES TO BE HUBBELL #B- 2527/29 WITH S -3925 BRASS
1. MINIMUM SIZES OF CONDUITS SHALL BE 3/4* FOR STANDARD
COVER (OR EQUAL BY "STEEL CITY") AND HUBBELL 5362
RECEPTACLE (UNLESS OTHERWISE NOTED)
CONDUIT, AND 1/2" FOR FLEX CONDUIT 1/2" STANDARD
C
CONDUIT; AND 3/8" MC CABLE MAY-'BE-'USED'--AS- SPECIFIED
6. EQUAL BY ARROW —HART, GENERAL ELECTRIC, BRYANT. PASS &
ABOVE, IF ACCEPTABLE WITH LANDLORD AND LOCAL CODES,
SEYMOUR, OR SIERRA.
ELECTRICAL CONTRACTOR SHALL FIELD COORDINATE WITH
LANDLORD do INSPECTION AGENCIES PRIOR TO INSTALLATION).
ELECTRIC METALLIC TUBING (EMT) SHALL BE GALVANIZED OR
ELECTRO= GALVANIZED: FITTINGS SHALL BE SET SCREW OR
PANELBOARDS AND SAFETY SWITCHES:
COMPRESSION TYPE, FITTING SHALL BE • AS MANUFACTURED BY
REGEL. STEEL CITY, RACO, T do B, EFCOR OR EQUAL EMT
A.
PROVIDE BRANCH CIRCUIT PANELS WHICH SHALL BE OF THE BOLTED
SHALL BE USED FOR FEEDERS AND BRANCH CIRCUITS RUN
CIRCUIT BREAKER TYPE WITH SOLID COPPER BUSSING FULL SIZED
ABOVE SUSPENDED CEILINGS OR CONCEALED IN INTERIOR
NEUTRAL. 25X GROUND BUSSING, OVERALL HINGED/LOCKABLE DOOR,
TYPEWRITTEN DIRECTORY ALL SERVICE
.a
t
ENTRANCE EQUIPMENT SHLL BEAR THE MANUFACTURER'S S LABEL
2. PAINTING OF ELECTRICAL CONDUITS. ETC.. IF REQUIRED.
WHICH SHALL STATE THAT THE EQUIPMENT IS RATED FOR SERVICE
'
WILL BE BY GENERAL CONTRACTOR.
ENTRANCE APPLICATION IN ACCORDANCE WITH N.E.C. #230 -70.
LOAD BALANCE ALL ELECTRICAL PHASES AT PANELS AND
_
C.
THE USE OF ROMEX OR BX IS NOT PERMITTED.
SWITCHBOARDS. TWO AND THREE POLE BREAKERS SHALL BE COMMON
TRIP TYPE. WHEN USED AS SWITCHES IN 120V. AND 277V.
D.
MAXIMUM CONDUIT HANGER SPACING SHALL BE 8' -0" FOR 3/4"
LIGHTING CIRCUITS, FURNISH TYPE "SWD" BREAKERS IN
j
THRU 1 1/4" AND 10' -0" FOR 1 1/2" THRU 4" CONDUITS. DO
ACCORDANCE WITH N.E.C. #240 -836. SQUARE D OR EQUAL BY
�
NOT SUPPORT CONDUIT FROM THE CEILING SYSTEM.
GOULD ATE, CUTLER — HAMMER, WESTINGHOUSE, CHALLENGER,
FEDERAL PACIFIC, OR GENERAL ELECTRIC (OR APPROVED EQUAL).
E
E.
LEAVE A #10 AWG PULL WIRE OR NYLON PULL STRING IN ALL
- A
EMPTY CONDUITS.
3 I 4
E -?
9
10
B. PROVIDE SAFETY AND DISCONNECT SWITCHES. FUSED OR NONFUSED,
AS CALLED FOR ON DRAWINGS AND AS REQUIRED BY CODE. (FUSES
AS MANUFACTURED BY BUSSMAN, CHASE SHAWMUT, WESTINGHOUSE,
ECONOMY FUSE CO.. OR LITTLE FUSE CO. ARE ACCEPTABLE).
DISCONNECT SWITCHES THAT ARE INSTALLED AT AIR CONDITIONING
EQUIPMENT, HEAT PUMPS, ETC SHALL BE FUSED IN ACCORDANCE
WITH THE EQUIPMENT'S NAME PLATE REQUIREMENTS PER N.E.C.
440-21 do 110 -3B.
SWITCHES SHALL BE HEAVY DUTY, QUICK MAKE /QUICK BREAK TYPE,
FUSIBLE OR NON — FUSIBLE, WEATHERPROOF AS INDICATED ON THE
DRAWINGS, OR AS REQUIRED BY LOCAL CODES. LOAD AND
HORSEPOWER RATED AS MANUFACTURED BY SQUARE D. GOULD ITE,
CHALLENGER, CUTLER HAMMER, WESTINGHOUSE. FEDERAL PACIFIC,
OR GENERAL ELECTRIC (OR APPROVED EQUAL).
C. MANUAL MOTOR STARTERS WITH OVERLOAD PROTECTION MAY BE USED
FOR FRACTIONAL HORSEPOWER MOTORS THAT DO NOT REQUIRE
AUXILIARY CONTROL SINGLE PHASE STARTERS SHALL BE SQUARE
D OR EQUAL THREE PHASE STARTERS SHALL BE PROVIDED WITH
OVERLOAD DEVICE IN EACH PHASE MATCHED TO MOTOR NAMEPLATE
RATING. MAGNETIC MOTOR STARTERS (MINIMUM SIZE #1) SHALL
BE USED FOR ALL SINGLE PHASE AND THREE PHASE MOTORS RATED
ABOVE 1/2 HP OR THAT REQUIRE AUXILIARY CONTROL PROVIDE
CONTROL DEVICES (CONTACTS, TRANSFORMERS. ETC.) IN STARTERS
AS REQUIRED FOR INTERLOCKS, COORDINATE WITH MECHANICAL
AND /OR TEMPERATURE CONTROL CONTRACTORS. COMBINATION
STARTERS, WHEN USED, SHALL CONTAIN FUSIBLE SWITCHES.
BOXES:
A. OUTLET BOXES AND COVERS SHALL BE GALVANIZED, ONE —PIECE
PRESSED STEEL KNOCKOUT.
B. JUNCTION. PULL BOXES AND COVERS SHALL BE GALVANIZED STEEL,
CODE GAUGE SIZE.
C. INSTALL BOXES RIGIDLY ON BUILDING STRUCTURE AND SUPPORT
INDEPENDENTLY OF THE CONDUIT SYSTEM. ALSO PROVIDE
SUITABLE/PROPER BOX EXTENSIONS TO EXTEND BOXES TO FINISHED
FACES OF WALLS ETC. ALL OUTLET BOXES TO HAVE SUITABLE
BLOCKING BEHIND THEM TO MINIMIZE THE DEFLECTION THAT
OCCURS WHEN PLUGGING/UNPLUGGING INTO THESE DEVICES.
D. WHERE A 277 VOLT LIGHT SWITCH IS GANGED WITH A 120 VOLT
RECEPTACLE PROVIDE A SUITABLE DIVIDER OR SEPARATE JUNCTION
BOXES IN ACCORDANCE WITH NEC AND LOCAL CODES.
SERVICES:
A. ELECTRICAL CONTRACTOR SHALL PROVIDE TEMPORARY SERVICE FROM
LANDLORD'S DESIGNATED LOCATION AND PROVIDE LIGHTING, POWER
AND WIRING AS REQUIRED TO FACILITATE APPLICABLE TEMPORARY
NEEDS, AND FURNISH EXTENSION CORDS. ANY TEMPORARY
WIRING, FUSES, ETC., SHALL BE REMOVED UPON
COMPLETION OF THE PROJECT. PROVIDE GROUND FAULT
PROTECTION AS REQUIRED BY N.E.C. AND LOCAL CODES.
B. PROVIDE ELECTRICAL SERVICE AS SHOWN ON THE DRAWINGS, FIELD
VERIFY EXACT REQUIREMENTS PRIOR TO BIDS. ALL WORK NOT
SPECIFICALLY NOTED AS BEING BY THE LANDLORD OR POWER
COMPANY SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR.
CLOSELY COORDINATE ENTIRE INSTALLATION WITH LANDLORD AND
POWER COMPANY AS REQUIRED. (PROVIDE EQUIPMENT THAT IS
COMPATIBLE WITH AVAILABLE FAULT CURRENT LEVELS, PROVIDE
"CABLE LIMITERS" IF NECESSARY FOR SYSTEM COORDINATION).
FIELD VERIFY EXACT TYPE, SIZE, LOCATION, REQUIREMENTS,
ETC. OF EXISTING POWER AND TELEPHONE FACIU71ES PRIOR TO
BIDDING PROJECT.
C. MAKE PROVISIONS FOR NEW TELEPHONE SERVICE AS REQUIRED, AND
AS INDICATED ON THE DRAWINGS.
D. CONDUIT SYSTEM FOR TELEPHONE DISTRIBUTION WITHIN TENANT'S
PREMISES SHALL BE PROVIDED AS REQUIRED FOR A COMPLETE
TELEPHONE SYSTEM. OUTLET BOXES SHALL BE a SQUARE
MINIMUM WITH SINGLE DEVICE COVER AND TELEPHONE PLATE.
CLOSELY FIELD COORDINATE WITH TENANTS CONSTRUCTION MANAGER
TO AVOID CONFLICTS.
STEP —DOWN TRANSFORMER:
A. PROVIDE A DRY —TYPE TRANSFORMER OF THE ENCLOSED VENTILATED
TYPE WITH KVA AND VOLTAGE RATINGS AS CALLED FOR ON THE
DRAWINGS AND WITH COILS DESIGNED FOR 150 DEGREES C. RISE
ABOVE A 40 DEGREE C. AMBIENT WITH 100X OF RATED LOAD
CONNECTED TO THE SECONDARY, CLASS H INSULATION AND MINIMUM
OF SIX STANDARD FULL CAPACITY TAPS. (TWO ABOVE AND FOUR
BELOW NORMAL) SOUND LEVEL/bECIBELS SHALL BE IN ACCORDANCE
WITH "NEMA" STANDARDS. AND INSTALLATION SHALL INCLUDE
KORFOUND OR EQUAL VIBRATION— DAMPENING MOUNTS AND FLEXIBLE
STEEL CONDUIT FOR PRIMARY AND SECONDARY CONNECTIONS TO
MINIMIZE SOUND TRANSMISSION. (MOUNT TRANSFORMER ON
SEPARATE VIBRATION ISOLATORS, THESE ARE ADDITIONAL
VIBRATION ISOLATORS AND ARE USED IN CONJUNCTION WITH ANY
INTEGRAL FACTORY INSTALLED VIBRATION ISOLATORS.) AS
MANUFACTURED BY SQUARE D, HEAVY DUTY, ACME, GENERAL
ELECTRIC OR WESTINGHOUSE.
LIGHTING CONTACTOR AND TIME SWITCH:
A. CONTACTORS FOR CONTROL OF LIGHTING SHALL BE ASCO BULLETIN,
917 SERIES IN A NEMA 1 ENCLOSURE, OR EQUAL BY SQUARE "D",
CUTLER HAMMER. GENERAL ELECTRIC OR WESTINGHOUSE, ENCLOSED,
ELECTRICALLY OPERATED, MECHANICALLY HELD. TIME SWITCHES FOR
CONTROL OF LIGHTING SHALL BE 7 DAY TYPE WITH RESERVE POWER.
"TORK% SERIES DWZ100A, WITH ASTRONOMIC OPTION, OR EQUAL BY
SANGAMO OR PARAGON.
INSTALLATION:
A. ALL ELECTRIC WORK SHALL BE INSTALLED SO AS TO BE READILY
ACCESSIBLE FOR OPERATING, SERVICING. MAINTAINING AND
REPAIRING. HANGERS SHALL INCLUDE ALL MISCELLANEOUS STEEL
SUCH AS CHANNELS, RODS, ETC., NECESSARY FOR THE
INSTALLATION OF WORK AND SHALL BE FASTENED TO BUILDING
STEEL, CONCRETE OR MASONRY, BUT NOT PIPING OR DUCTWORK.
ALL CONDUIT SHALL BE CONCEALED WHEREVER POSSIBLE. EXPOSED
CONDUITS SHALL BE IN STRAIGHT LINES PARALLEL WITH OR AT
RIGHT ANGLES TO COLUMN LINES OR BEAMS AND SEPARATED AT
LEAST 3 INCHES FROM WATER LINES WHEREVER THEY RUN
ALONGSIDE OR ACROSS SUCH LINES. ALL CONDUCTORS SHALL BE
IN CONDUIT, DUCTS OR OTHER CODE APPROVED RACEWAYS.
11 1 12 1 13 1 14
B.
ALL LINE AND LOW VOLTAGE POWER AND CONTROL WIRING (EXCEPT
HVAC LOW VOLTAGE WIRING) INCLUDING CONNECTIONS TO MOTORS,
DAMPERS, INTERLOCKING. ETC., SHALL BE PROVIDED BY THE
ELECTRICAL CONTRACTOR. (ALL LINE VOLTAGE WIRING, CONDUIT,
AND FINAL CONNECTIONS FROM THE POWER SOURCE THRU THE
STARTER/DISCONNECT ETC. TO THE MOTOR OR EQUIPMENT IS THE
RESPONSIBILITY OR THE ELECTRICAL CONTRACTOR. ALL HVAC
RELATED LOW VOLTAGE CONTROL WIRING. CONDUIT AND FINAL
CONNECTIONS IS THE RESPONSIBILITY OF THE
MECHANICAL/TEMPERATURE CONTROL CONTRACTOR, UNLESS
OTHERWISE NOTED ON THE PLANS).
C.
THE ELECTRICAL CONTRACTOR SHALL DO ALL CUTTING, CHASING OR
CHANNELING AND PATCHING REQUIRED FOR ANY WORK UNDER THE
ELECTRICAL DIVISION, ANY CUTTING SHALL HAVE PRIOR APPROVAL
OF THE LANDLORD. SLEEVES SHALL EXTEND AT LEAST TWO (2 ")
INCHES ABOVE FINISHED FLOOR AND ALL SLEEVES, OPENINGS.
ETC., THROUGH FIRE RATED WALLS AND FLOORS SHALL BE FIRE
SEALED WITH CALCIUM SILICATE. SILICONE "RTV" FOAM. "3M"
FIRE RATED SEALANTS OR EQUAL BY HILTI AFTER CONDUIT /CABLES
INSTALLATION SO AS TO RETAIN THE FIRE RATING.
D.
THE ELECTRICAL CONTRACTORS, INSOFAR AS THE WORK IS
CONCERNED, SHALL AT ALL TIMES KEEP THE PREMISES IN A NEAT
AND ORDERLY CONDITION AND. AT THE COMPLETION OF THE WORK,
SHALL PROPERLY CLEAN UP AND CART AWAY ANY DEBRIS AND
EXCESS MATERIAL
E.
THE FOLLOWING EQUIPMENT SHALL BE IDENTIFIED WITH ENGRAVED
BAKELITE NAMEPLATES AS TO NAME AND /OR FUNCTION;
DISTRIBUTION PANELS, LIGHTING PANELS, MOTOR STARTERS AND
DISCONNECT SWITCHES. NAMEPLATES TO BE APPROXIMATELY 1" X
2" IN SIZE AND BE FASTENED WITH POP RIVETS OR SCREWS.
F.
THE LOCATION OF OUTLETS AND EQUIPMENT SHOWN ON THE
DRAWINGS ARE APPROXIMATE AND THE ARCHITECT/TENANT
CONSTRUCTION MANAGER SHALL HAVE THE RIGHT TO RELOCATE ANY
OUTLETS OR FIXTURES BEFORE THEY ARE INSTALLED WITHOUT
ADDITIONAL COST.
G.
ELECTRICAL CONTRACTOR SHALL RECORD ALL FIELD CHANGES IN
THE WORK AS THE JOB PROGRESSES, AND TURN THIS "AS BUILT"
INFORMATION OVER TO THE OWNER AT THE COMPLETION OF THE
PROJECT.
H.
ELECTRICAL CONTRACTOR SHALL PROTECT ALL FIXTURES/EQUIPMENT
AGAINST DAMAGE FROM LEAKS, ABUSE. ETC., AND PAY COST OF
REPAIR OR REPLACEMENT OF FIXTURES OR EQUIPMENT MADE
NECESSARY BY FAILURE TO PROVIDE SUITABLE SAFEGUARDS OR
PROTECTION.
I.
ELECTRICAL CONTRACTOR SHALL MAKE ALL FINAL ELECTRICAL
CONNECTIONS 'AS REQUIRED FOR A COMPLETE AND OPERATING
SYSTEM. , -AFTER ",ALL EQUIPMENT HAS BEEN INSPECTED AND
:APPROVED.' THOROUGHLY CLEAN ALL EQUIPMENT PROVIDED UNDER
THIS WORK .JUST PRIOR TO COMPLETION OF PROJECT.
THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ANY /ALL
NECESSARY ELECTRICAL DEMOLITION WORK THAT IS REQUIRED TO
FACILITATE THE NEW INSTALLATION, FIELD COORDINATE PRIOR TO
BIDS. REMOVE AND /OR MODIFY EQUIPMENT. ETC. AS REQUIRED
`
FOR A COMPLETE INSTALLATION. ANY EQUIPMENT OR DEVICE
REMAINING IN USE AFTER PART OF THE EQUIPMENT OR DEVICES
-''
HAVE BEEN-REMOVED ARE TO BE RECONNECTED TO EXISTING OR NEW
`CIRCUITSkkD
LEFT IN WORKING ORDER. FEEDERS TO PANELS AND
-
� -- WIRING TO OTHER EQUIPMENT TO BE ROUTED CONCEALED IN
AREAS. COORDINATE ANY DISRUPTION OF ELECTRICAL
OR TELEPHONE SERVICES WITH LANDLORD AND TENANT
CONSTRUCTION MANAGER TO AVOID CONFLICTS.
GUARANTEE:
A.
MATERIALS, EQUIPMENT AND INSTALLATION SHALL BE GUARANTEED
FOR A PERIOD OF ONE (1) YEAR FROM DATE OF ACCEPTANCE.
DEFECTS WHICH APPEAR DURING THAT PERIOD SHALL BE CORRECTED
AT THE ELECTRICAL CONTRACTOR'S EXPENSE.
B.
FOR THE SAME PERIOD, ELECTRICAL CONTRACTOR SHALL BE
RESPONSIBLE FOR ANY DAMAGE TO PREMISES CAUSED BY DEFECTS
IN WORKMANSHIP OR IN THE WORK OR EQUIPMENT FURNISHED
AND /OR INSTALLED BY THE ELECTRICAL CONTRACTOR.
FINALLY:
A.
IT IS THE INTENT THAT THE FOREGOING WORK SHALL BE COMPLETE
IN EVERY RESPECT AND THAT ANY MATERIAL OR WORK NOT
SPECIFICALLY MENTIONED OR SHOWN ON THE DRAWINGS, BUT
NECESSARY TO FULLY COMPLETE THE WORK SHALL BE FURNISHED.
FIELD VERIFY ALL CONDITIONS
DESIGN DRAWINGS ARE SCHEMATIC. THIS CONTRACTOR SHALL VISIT THE
SITE PRIOR TO BIDDING OR AWARD OF CONTRACT TO INSPECT EXISTING
FIELD CONDITIONS. THIS CONTRACT SHALL INCLUDE ALL LABOR AND
MATERIALS NECESSARY FOR FIELD MODIFICATIONS DUE TO EXISTING
CONDITIONS.
THE CONTRACTOR SHALL CONTACT THE ARCHITECT, ENGINEER OR OWNER
PRIOR TO BIDDING FOR INTERPRETATIONS AND CLARIFICATIONS OF THE
DESIGN AND INCLUDE IN HIS BID ALL COSTS TO MEET THE DESIGN
INTENT. CLARIFICATIONS MADE BY THE ARCHITECT, ENGINEER OR OWNER
AFTER BIDDING WILL BE FINAL AND SHALL BE IMPLEMENTED AT
CONTRACTORS COST.
BIDDING CONTRACTORS SHALL HAVE A WORKING KNOWLEDGE OF LOCAL
CODES AND ORDINANCES AND SHALL INCLUDE IN THEIR BIDS THE
COSTS FOR ALL WORK INSTALLED IN STRICT ACCORDANCE WITH
GOVERNING CODES, THE PLANS AND SPECIFICATIONS NOT WITHSTANDING.
THE CONTRACTOR SHALL ALERT ARCHITECT. ENGINEER OR OWNER OF
ANY APPARENT DISCREPANCIES BETWEEN GOVERNING CODES AND DESIGN
INTENT.
5 I 6 I 7 I 8 9 10 11 12 13
14
17
N
1524 Delance Street -
Phladelphia. P 1
m 9102
www.Vg&co, Yom;
IL 215.735.1524 1� M
f. 215.735.4949 .
M— Retail Engineering, Inc.
MPE Systems Engineering
750 Brooksedge Blvd.
Westerville, OH 43081
614.818.2323 Fax: 614.818.2337
eoldenburg®m— corporation s.com ,� ;ts�•k
L
•
;H
G
a
•
4; r. '
�r f
E
� y .Y Jrl• r +1
f ✓, r `yD•
APR 1 9 2005
04.19.05 ISSUED FOR TENANT AND BUILDING DEPARTMENT N/A
REVIEW C
Date Issue Rev. Na
AA4.
Up Against T he Wall
•A
Space No. A -10 +:.
The Shops at Sunset Place B
South Miami, FL
ELECTRICA P"°I "a� °
SPECI FI CA I ON S'
D
/ A
.oa
k
•d
15 16