05-893-015N M L" K J H G F E D C A rn N L;..I H LO 0 0 N tri N Q Q D v� 3 v co LO 0 Rd- in 0 6 of Q O i a� rn Z 0 In Q U 1 2 3 4 5 6 7 8 9 10 11 12 13 14 1� -- 1 N1 THE EXISTING SPRINKLER SYSTEM AND HEAD LOCATIONS SHALL BE MODIFIED PER TENANT'S NEW FIXTURES, PARTITIONS, SOFFITS, DROPS, CEILING HEIGHTS, ETC. THE SPRINKLER SYSTEM SHALL BE DESIGNED AND INSTALLED IN STRICT ACCORDANCE WITH THE REQUIREMENTS OF THE LANDLORD, LANDLORD'S FIRE INSURANCE UNDERWRITER, AND ALL GOVERNMENTAL AGENCIES AND AUTHORITIES HAVING JURISDICTION OVER THE PREMISES. COMPREHENSIVE SHOP DRAWINGS AND CALCULATIONS SHALL BE SUBMITTED BY THE CONTRACTOR FOR THE APPROVAL BY THE OWNER, LANDLORD, LANDLORD'S FIRE INSURANCE UNDERWRITER, AND THE FIRE RATING INSPECTION BUREAU. TENANT'S FIRE PROTECTION CONTRACTOR SHALL DISCONNECT EXISTING SYSTEM FROM MAIN SYSTEM... PERFORM HIS WORK, TEST, THEN RECONNECT TO MAIN SYSTEM ... ALL COSTS RELATED TO DRAIN DOWN AND FILLS ARE TO BE BORNE BY TENANT'S FIRE PROTECTION CONTRACTOR. SPRINKLER SHOP DRAWINGS SHALL BE SUBMITTED TO THE LANDLORD AND LANDLORDS INSURANCE COMPANY AND RECEIVE THEIR APPROVAL BEFORE ANY INSTALLATION CAN BEGIN. APPROVED DRAWINGS MUST BE AT THE JOB SITE DURING CONSTRUCTION. TENANTS SPRINKLER SYSTEM DESIGN SHALL BE BASED UPON A SINGLE SOURCE OF SUPPLY, ORDINARY HAZARD PIPE SCHEDULE SYSTEM AS OUTLINED IN NFPA PAMPHLET #13 AND THE LANDLORDS INSURANCE CARRIERS REQUIREMENTS. TENANT SPRINKLER SYSTEM MAY BE VALVED AT CONNECTION TO LANDLORD MAINS. IF SYSTEM IS EXISTING, TENANT SHALL ATTACH A TAMPER SWITCH AND INTERFACE WITH LANDLORDS FIRE ALARM SYSTEM. TENANT SHALL FURNISH AN INSPECTORS TEST CONNECTION. THE TEST CONNECTION SHALL BE INSTALLED OFF THE MOST REMOTE SPRINKLER, AS PHYSICALLY POSSIBLE, FROM THE SPRINKLER SUPPLY MAIN. INSPECTORS TEST CONNECTION SHALL BE EQUIPPED WITH A 1" CORROSION- RESISTANT SHUT -OFF VALVE AND A SMOOTH BORE CORROSION- RESISTANT OUTLET DRAIN WITH HOSE BIB CONNECTION FOR DISCHARGE TO A SUITABLE RECEPTOR. 2 3 E.I ALL PIPING SHALL BE SUPPORTED FROM BEAMS /JOISTS ONLY. DO NOT ATTACH ANYTHING DIRECTLY TO THE UPPER LEVEL SLAB OR ROOF DECK. FASTENING AND /OR SUSPENSION DEVICES SHALL BE ATTACHED TO THE BUILDING STRUCTURE ONLY. FINAL CONNECTION TO LANDLORDS SPRINKLER MAIN SHALL NOT BE MADE UNTIL THE ENTIRE SYSTEM WITHIN THE DEMISED PREMISES IS PRESSURE TESTED AND READY FOR SERVICE. ALL SPRINKLER SYSTEM TESTS SHALL BE WITNESSED BY THE LANDLORDS ON -SITE REPRESENTATIVE AND LOCAL JURISDICTIONAL AUTHORITIES AS REQUIRED. ALL MATERIALS AND EQUIPMENT UNDER THIS SECTION SHALL BE NEW AND LISTED BY UNDERWRITERS LABORATORIES, INC. AND FACTORY MUTUAL FOR FIRE PROTECTION SYSTEM INSTALLATION, AND APPROVED BY ALL AUTHORITIES HAVING JURISDICTION AND GOVERNING CODES. ALL PIPING SHALL BE DESIGNED IN ACCORDANCE WITH NFPA #13 AND INSTALLED PER LANDLORDS INSURANCE CARRIERS REQUIREMENTS. ALL PIPING SHALL BE THREADED SCHEDULE 40 BLACK STEEL MEETING ASTM A135. ALL PIPE FITTINGS ARE REQUIRED TO BE PRESSURE CLASS 175. ALL HANGERS ARE TO BE OF AN APPROVED TYPE AND SPACED IN ACCORDANCE WITH NFPA #13. SEISMIC BRACING TO BE INSTALLED PER CODE. 5 1 6 1 7 0 NW-- / EXISTING SPRINKLER STEM TO BE REUSED. MODIFY AND /OR RELOCA EA AS NECESSARY TO ACHIEVE ADEQUATE C RAGE PER CODE REQUIREMENTS AND LAN EQUIREMENTS. APPROVAL ALSO REQUIRED BY Kb D'S INSURER. CONTRACTOR TO CONFIRM HYDRAULIC CAL TI ARE CORRECT AND CONFORM TO CODE. CONTRACTOR SHALL REUSE AS MUCH PIPING AS PRACTICABLE. FIRE PROTECTION PLANS ARE DIAGRAMMATIC, NOT SHOWING EVERY ITEM IN EXACT LOCATION OR DETAIL. MEASUREMENTS AND LOCATIONS MUST BE FIELD VERIFIED AND COORDINATED WITH ARCHITECTURAL, HVAC, FIRE PROTECTION, PLUMBING, STRUCTURAL, ELECTRICAL AND OTHER BUILDING DRAWINGS. IT IS REQUIRED THAT THE FIRE PROTECTION CONTRACTOR MUST VISIT THE JOB SITE TO FAMILIARIZE HIMSELF WITH MAJOR ITEMS SUCH AS STRUCTURAL ELEMENTS, PLUMBING LOCATIONS AND ELECTRICAL RUNS. ADDITIONALLY FIRE PROTECTION CONTRACTOR SHALL VERIFY EXACT LOCATIONS AND DIMENSIONS OF FIRE PROTECTION ITEMS AND HVAC SYSTEM COMPONENTS, ETC. PRIOR TO BID, AND CONTACT THE OWNERS CONSTRUCTION REP /ARCH/ ENGINEER AND REPORT ANY DIFFERENCES/ DISCREPANCIES IN THE DRAWINGS FOR A DECISION. FIELD VEMFY ALL CONDITIONS DESIGN DRAWINGS ARE SCHEMATIC. THIS CONTRACTOR SHALL VISIT THE SITE PRIOR TO BIDDING OR AWARD OF CONTRACT TO INSPECT EXISTING FIELD CONDITIONS. THIS CONTRACT SHALL INCLUDE ALL LABOR AND MATERIALS NECESSARY FOR FIELD MODIFICATIONS DUE TO EXISTING CONDITIONS. THE CONTRACTOR SHALL CONTACT THE ARCHITECT, ENGINEER OR OWNER PRIOR TO BIDDING FOR INTERPRETATIONS AND CLARIFICATIONS OF THE DESIGN AND INCLUDE IN HIS BID ALL COSTS TO MEET THE DESIGN INTENT. CLARIFICATIONS MADE BY THE ARCHITECT, ENGINEER OR OWNER AFTER BIDDING WILL BE FINAL AND SHALL BE IMPLEMENTED AT CONTRACTORS COST. BIDDING CONTRACTORS SHALL HAVE A WORKING KNOWLEDGE OF LOCAL CODES AND ORDINANCES AND SHALL INCLUDE IN THEIR BIDS THE COSTS FOR ALL WORK INSTALLED IN STRICT ACCORDANCE WITH GOVERNING CODES, THE PLANS AND SPECIFICATIONS NOT WITHSTANDING. THE CONTRACTOR SHALL ALERT ARCHITECT, ENGINEER OR OWNER OF ANY APPARENT DISCREPANCIES BETWEEN GOVERNING CODES AND DESIGN INTENT. SPRINKLER NOTES 1. SYSTEM SHALL BE ENGINEERED BY THE CONTRACTOR TO COMPLY WITH CODE AND MALL REGULATIONS. SUBMIT DRAWINGS, RISER DIAGRAMS AND CALCULULATIONS TO REGULATING AGENCIES AS REQUIRED FOR PERMITTING. 2. ALL HEADS IN PUBLIC AREAS SHALL BE CONCEALED TYPE WITH CUSTOM SHOP PAINTED COVER PLATES TO MATCH ARCHITECT'S SAMPLE. 3. ALL HEADS IN BACK OFFICE, STOCKROOM , ETC. SHALL BE SEMI RECESSED. 4. HEADS SHALL BE CAREFULLY ALIGNED WITH AND /OR CENTERED BETWEEN LIGHT FIXTURE GRID LINES, UNLESS OTHERWISE NOTED. MAINTAIN 6" MIN. CLEAR BETWEEN HEADS AND OTHER CEILING WORK. NO HEADS SHALL BE LOCATED ON CEILING BEAMS, EVEN IF THIS MEANS MORE HEADS ARE REQUIRED TO ACHIEVE COVERAGE. 5. IT IS THE GENERAL CONTRACTOR'S RESPONSIBILITY TO COORDINATE AND ISSUE SPRINKLER SHOP DRAWINGS TO THE ARCHITECT FOR APPROVAL, PRIOR TO PERMITTING. &INSTALLATION AND /OR MODIFICATION OF SPRINKLER SYSTEM SHALL BE BY A LANDLORD'S DESIGNATED OR APPROVED CONTRACTOR. SPRINKLER LEGEND • FULLY CONCEALED TYPE SPRINKLER HEAD FIELD VERIFY ALL CONDITIONS DESIGN DRAWINGS ARE SCHEMATIC. THIS CONTRACTOR SHALL VISIT THE SITE PRIOR TO BIDDING OR AWARD OF CONTRACT TO INSPECT EXISTING FIELD CONDITIONS. THIS CONTRACT SHALL INCLUDE ALL LABOR AND MATERIALS NECESSARY FOR FIELD MODIFICATIONS DUE TO EXISTING CONDITIONS. THE CONTRACTOR SHALL CONTACT THE ARCHITECT, ENGINEER OR OWNER PRIOR TO BIDDING FOR INTERPRETATIONS AND CLARIFICATIONS OF THE DESIGN AND INCLUDE IN HIS BID ALL COSTS TO MEET THE DESIGN INTENT. CLARIFICATIONS MADE BY THE ARCHITECT, ENGINEER OR OWNER AFTER BIDDING WILL BE FINAL AND SHALL BE IMPLEMENTED AT CONTRACTORS COST. BIDDING CONTRACTORS SHALL HAVE A WORKING KNOWLEDGE OF LOCAL CODES AND ORDINANCES AND SHALL INCLUDE IN THEIR BIDS THE COSTS FOR ALL WORK INSTALLED IN STRICT ACCORDANCE WITH GOVERNING CODES, THE PLANS AND SPECIFICATIONS NOT WITHSTANDING. THE CONTRACTOR SHALL ALERT ARCHITECT, ENGINEER OR OWNER OF ANY APPARENT DISCREPANCIES BETWEEN GOVERNING CODES AND DESIGN INTENT. VERIFY ALL CONDITIONS IN FIELD PRIOR TO BID �7 10 11 12 13 14 M— Retail Engineering, Inc. MPE Systems Engineering 750 Brooksedge Blvd. Westerville, OH 43081 614.818.2323 Fax: 614.818.2337 eoldenbura0m— coraorations.com APPROVED FOR BUILDING PERMITTING PURPOSES BY MIAMI -DADE COUNTY FIRE DEPARTMENT FIRE PROTECTION CONTRAC rORJS WORKING PLAN AS PER Nr PA 13 SHALL BE SUBMITTED FOR APPROVAL TO MIAMI -DADE FIB E DEPARTME BEFORE ANY FIRE PROTECTION STEM S8 INSTALLED OR REMOD E&D DATE 6Y 17 1524 Delancey Street Philadelphia. PA 19102 www.apg3.com t. 215.735.1524 L 215.735.4949 05.26.05 FIRE REVIEW COMMENTS 1 04.19.05 ISSUED FOR TENANT AND BUILDING DEPARTMENT N/A REVIEW Date Issue Rev. Na U p Against The Wall Space No. A -10 The Shops at Sunset Place South Miami, FL p r i n K l e r . --- �����Y• EGO �••�,o '�..�,, ..'JPT- �..�. 2 5 20 o 15 1 16 1 17 L J H F F E C 0 A