DIVISION 15 - MECHANICAL
SECTION 15000
MECHANICAL GENERAL PROVISIONS
A. GENERAL CONDITIONS
1.
DRAWINGS AND ORAL PROVISIONS OF CONTRACT, INCLUDING GENERAL AND
SUPPLEMENTARY CONDITIONS AND ALL OTHER SPECIFICATION SECTIONS ARE A
PART OF THIS CONTRACT AND APPLY TO THIS AND THE OTHER SECTIONS OF
DIVISION 15.
2.
THE CONTRACTOR FOR THIS WORK IS REWIRED TO READ THE ENTIRE
SPECIFICATIONS AND REVIEW DRAWINGS FOR ALL OTHER TRADES.
3.
THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING HIS SUBCONTRACTORS WITH
A FULL SET OF BID SET DOCUENTS (INCLUDING SPECIFICATIONS) AND THE
COORDINATION OF HIS WORK AND INSPECTIONS AND THE WORK AND INSPECTIONS
OF HIS SUBCONTRACTORS WITH ALL OTHER TRADES ON SITE CONFORMING TO THE
GENERAL CONTRACTOR'S TIME SCHEDULE.
4.
THE CONTRACTOR SHALL VISIT THE SITE PRIOR TO SUBMITTING HIS BID TO
DETERMINE CONDITIONS AFFECTING THE M. BIDS SMALL SERVE AS EVIDENCE
OF KNOWLEDGE OF EXISTING CONDITIONS AND ANY MODIFICATIONS WHICH ARE
REQUIRED TO MEET THE INTENT OF THE DRAWINGS AND SPECIFICATIONS.
FAILURE TO VISIT THE SITE DOES NOT RELIEVE THE CONTRACTOR OF
RESPONSIBILITY IN PERFORMANCE OF WORK.
5.
WHEN USED, THE TERM 'PROVIDED BY CONTRACTOR' SHALL BE INTERPRETED AS
MEANING 'FURNISHED AND INSTALLED* WITH THE EXCEPTION WMIERE ITEMS ARE
'PROVIDED BY TENANT* WHICH MEANS 'FURNISHED ONLY' (INSTALLED BY
CONTRACTOR), EXCEPT AS SPECIFICALLY NDTED OTHERWISE.
B. GENERAL REQU IREMENTS
1.
THE CONTRACTOR SHALL PROVIDE ALL LABOR. MATERIALS. EQUIPMENT.
SERVICES, TOOLS, TRANSPORTATION. INCIDENTALS AND DETAILS NECESSARY TO
PROVIDE A COMPLETE AND FULLY FUCT I ON& MECRAN I CAL SYSTEM AS SHOWN ON
THE DRAWINGS. CALLED FOR IN THE SPECIFICATIONS. AND AS REQU I RED BY JOB
CONDITIONS. ALL WORK NOT SPECIFICALLY NOTED AS BEING BY THE LANDLORD
SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR. CLOSELY COORDINATE
THE ENTIRE INSTALLATION WITH THE LANDLORD, AS REWIRED. FIELD VERIFY
THE EXACT TYPE. SIZE AND LOCATION. ETC. OF EXISTING PIPE AND DUCTS IN
THE TENANT SPACE PRIOR TO BID.
2.
THE DRAWINGS AND SPEC I F I CAT 1 ONS ARE INTENDED TO SUPPLEEN'T EACH OTHER
AND ANY MATERIAL OR LABOR CALLED FOR IN ONE SHALL. BE PROVIDED EVEN
D OM NOT SPECIFICALLY MEITIONED IN BOTH. ANY MATERIAL OR LABOR
WHICH IS NEITHER SHOWN ON THE DRAWINGS NOR CALLED FOR IN THE
SPECIFICATIONS, BUT M4R I CH IS OEIV I OUSL.Y NECESSARY TO COMPLETE THE WORK.
AND MH I CH IS USUALLY INCLUDED IN WORK OF SIMILAR CHARACTER. SHALL BE
PROVIDED AS PART OF CONTRACT.
3.
WHERE THE DRAWINGS OR SPECIFICATIONS CALL FOR ITEMS WHICH EXCEED CODES
OR THE LANDLORD'S TENANT CRITERIA, THE CONTRACTOR IS STILL RESPONSIBLE
FOR PROVIDING THE SYSTEM AS DESIGNED AND DESCRIBED ON THESE DRAWINGS,
UNLESS SPECIFICALLY NOTED OTHERWISE.
4.
ALL MECHANICAL WORK SHALL BE INSTALLED SO AS TO BE READILY ACCESSIBLE
FOR OPERATING, SERVICING. MAINTAINING. AND REPAIRING. THE CONTRACTOR
IS RESPONSIBLE FOR PROVIDING SUFFICIENT ACCESS TO ALL EQUIPMENT FOR
SERVICE.
5.
THE CONTRACTOR SHALL DO ALL CUTTING, CORE DRILLING. CHASING OR
CHANNNEL I NG AND PATCHING REQU I RED FOR ANY WORK UDDER THIS DIVISION.
CUTTING SHALL HAVE PRIOR APPROVAL BY THE TENANT'S CONSTRUCTION MANAGER
AND THE LANDLORD. PATCHING SHALL MATCH, FINISH OF SU RRRODUD I NG AREA.
C. CODES
1.
ALL WORK SHALL BE PERFORMED 1N A NEAT PROFESSIONAL MAKER USING GOOD
ENGINEERING PRACTICES. ALL WORK SHALL CONFORM TO THE LANDLORD'S
CRITERIA, THE STATE'S. COUNTY'S, CITY'S AND LOCAL CODES AND
ORDINANCES. SAFETY AND HEALTH CODES. NFPA CODES, ENERGY CODES AND ALL
OTHER APPLICABLE CODES AND REQUIREMENTS. THE CONTRACTOR SHALL INQUIRE
INTO AND COMPLY WITH ALL APPLICABLE CODES, ORDINANCES, AND
REGULATIONS. AFTER CONTRACT IS ISSUED. NO ADDITIONAL COST DUE TO CODE
ISSUES SHALL BE REIMBURSED BY THE TENANT M THE CONTRACTOR.
D. LICENSES, PERMITS, INSPECTIONS 3 FEES
1.
THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL LICENSES, PERMITS,
INSPECTIONS, AND FEES REWIRED OR RELATED TO HIS WORK.
2.
FURNISH TO THE TENANT'S CONSTRUCTION MANAGER ALL CERTIFICATES OF
INSPECTION AND FINAL. INSPECTION APPROVAL AT SUBSTANTIAL COMPLETION
DATE OF PROJECT.
E DRAWINGS
1.
DRAWINGS (PLANS. SPECIFICATIONS. AND DETAILS) ARE DIAGRAMMATIC AND
INDICATE THE GENERAL LOOT I ON AND INTENT OF THE MECIAN I CAL SYSTEMS.
BECAUSE OF THE SMALL SCALE OF THE DRAWINGS, IT IS NOT POSSIBLE TO
INDICATE ALL DUCT AND PIPING OFFSETS, FITTINGS AND ACCESSORIES THAT
MAY BE REQUIRED.
2.
THE LAYOUT SHOWN ON THE DRAWINGS IS BASED ON A PARTICULAR MAKE OF
EQUIPMENT. IF ANOTHER HAKE OF EQUIPMENT IS USED WHICH REWIRES
MODIFICATION OR CWIGE OF ANY DESCRIPTION FROM THE DRAWINGS OR
SPECIFICATIONS. THE CONTRACTOR SHALL BE RESPONSIBLE AS PART OF THIS
WORK, FOR MAKING ALL SUCH MODIFICATIONS AND CHANGES, INCLUDING THOSE
INVOLVING OTHER TRADES WITH THE COST THEREOF INCLUDED IN HIS BID. IN
SUCH CASE. CONTRACTOR SHALL SUBMIT DRAWINGS AND SPECIFICATIONS PRIOR
M STARTING WORK SHOWING ALL SUCH MODIFICATIONS AND CHANGES. HIS
PROPOSAL SHALL BE SUBJECT TO THE APPROVAL OF THE TEENANT'S CONSTRUCTION
MANAGER.
F. EXISTING SHELL SPACE CONDITIONS
1.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF THE
DEMOLITION OF EXISTING MECHANIIAL WORK SHOWN ON THE MECHANOIAL
DRAWINGS AND THE MECHANC I AL DEMO. I T I ON SHOWN ON THE ARCHITECTURAL
DRAWINGS.
2.
THE CONTRACTOR SHALL INCLUDE, AND WILL BE HELD RESPONSIBLE FOR, THE
REIMAL OF ALL EXISTING FIRE PROTECTION. PLUMBING FIXTURES, PIPING.
WAC UNITS, REFRIGERANT RECAPTURE. EXHAUST FANS, ETC. AND ASSOCIATED
ROOF CURBS NOT M BE REUSED ON THIS PROJECT. UNLESS SPECIFICALLY NOTED
OTHERWISE. CONTRACTOR MST VERIFY WITH THE LANDLORD ALL PRESUMED
ABANDONED EQU I RENT. PIPES. DUCTWORK. MO EQUIPMENT PRIOR TO REMOVAL.
ROOF CURBS SWILL BE REMOVED AND THE ROOF PATCHED UNLESS NOTED FOR
REUSE OR RECOiFIGURATION ON PLANS. ROOF PATCHING SHALL BE PERFORMED
AT THE CONTRACTOR'S EXPENSE BY A ROOFING CONTRACTOR APPROVED BY THE
LANDLORD. ALL EXTRANEOUS ITEMS IN THE SPACE OR ON THE ROOF (ABOVE
THIS SPACE) NOT APPL I CABLE TO THE NEW WORK OR PART OF THE LMDLORD' S
OR ANOTHER TENANT'S ACTIVE SYSTEM MUST BE REMOVED AND ROOF/MLL/FLOOR
PATCHED/REPAIRED TO MATCH EXISTING STRUCTURE. EXISTING ABANDONED
PIPES, DUCTS, OR EQUIPMENT IN THE FLOOR, EMBEDDED IN CONCRETE. OR
OTHERWISE INACCESSIBLE ARE TO BE CUT OFF AND SEALED BELOW OR WITHIN
FLOOR OR WALL LEVEL MEN THEY ARE NOT TO BE REUSED IN THIS PROJECT.
IF REND I RED BY LANDLORD OR CODES. ABANDONED PIPING AND/OR DUCTWORK
MUST BE REMOVED TO POINT OF ORIGIN. CONFIRM THE EXTENT OF DEMON. I T I ON
PRIOR TO BID AND INCLUDE IN BID PROPOSAL.
3.
ACTIVE LANDLORD OR OTHER TENANT SEEN I CES ENCOUNTERED IN WORK SHALL BE
PROTECTED AND SUPPORTED. IF EXISTING SERVICES NOT ANTICIPATED REQU I RRE
RELOCATION, CONTACT THE TENANT'S CONSTRUCTION MANAGER IMMEDIATELY.
ALL COSTS FOR REPAIR OF DAMAGES TO ACTIVE LANDLORD OR OTHER TENANT
SERVICES DURING CONSTRUCTION SHALL BE PAID FOR BY THE CONTRACTOR
CAUSING THE DAMAGE.
4.
TIE -INS AND MODIFICATIONS TO EXISTING LANDLORD SERVICES MUST BE DONE
WITH MINIM INTERRUPTION OF LANDLORD OPERATION AND DURING FOURS
SPECIFIED BY THE LANDLORD. THE CONTRACTOR IS RESPOS I BLE FOR
COF I ARM I ND EXACT WORKING HOURS OF THIS WORK WITH THE LMDLORD PRIOR
M SUBMITTING HIS BID. THE CONTRACTOR SHALL INCLUDE IN HIS BID, ALL
PREMIUM TIME REQUIRED TO PERFORM MODIFICATIONS DURING OTHER THAN
FORMAL WORKING HOURS. ALL SUCH WOES( MUST BE COORDINATED WITH THE
LANDLORD.
G. DISCREPANCIES IN DOCUMENTS
1.
DRAWINGS (R AS. SPECIFICATIONS. AND DETAILS ) ARE DIAGRAMMATIC AND
OF MECHAN I CAL SYSTEMS.
INDICATE THE GENERAL. LOCATION AND INTENT THE
WHERE DRAWINGS, EXISTING SITE CONDITIONS, SPECIFICATIONS OR OTHER
TRADES CONFLICT OR ARE UNCLEAR, ADVISE THE GENERAL CONTRACTOR IN
WRITING, PRIOR TO SUBMITTAL OF BID. THE GENERAL CONTRACTOR IS
RESPONSIBLE M ADVISE THE TENANT'S CONSTRUCTION MANAGER, IN WRITING,
OF VARIATIONS TO CONTRACT DOCUMENTS PRIOR TO SUBMISSION OF BID.
OTHERWISE, TENANT'S CONSTRUCTION MANAGER'S INTERPRETATION OF CONTRACT
DOCUMENTS OR CONDITIONS SHALL BE FINAL WITH ND ADDITIONAL COMPENSATION
PERMITTED.
H. TRADE NAMES AND MANUFACTURERS
1.
MERE TRADE AWES AND MANUFACTURERS ARE USED ON THE DRAWINGS OR IN THE
SPECIFICATIONS, THE EXACT EQUIPMENT SHALL BE USED AS A MINIMUM
STANDARD FOR THE BASE BID. MANUFACTURERS CONSIDERED AS AN EQUAL OR
BETTER IN ALL ASPECTS TO THAT SPECIFIED WILL BE SUBJECT TO APPROVAL
IN WRITING BY THE TENANT'S CONSTRUCTION MANAGER PRIOR TO ACCEPTANCE.
THE USE OF ANY UNAUTHORIZED EQUIPMENT SHALL BE SUBJECT TO REMOVAL AND
REPLACEMENT AT THE CONTRACTOR'S EXPENSE.
1. SHOP DRAWINGS
1.
SUBI I T SIX COPIES OF MATERIAL L I STS AND SHOP DRAWINGS FOR ALL
EQUIPMENT AND DUCT FABRICATION DRAWINGS TO TIE TENANT'S COSTRUCT I ON
MANAGER FOR APPROVAL PRIOR TO ORDERING EQUIPMENT. SUBMISSIONS MUST
BE EARLY ENOUGH M ALLOW THE TENANT'S CONSTRUCTION MANAGER EIGHT
WORKING DAYS FOR REVIEW WITHOUT CAUSING DELAYS OR CONFLICTS TO THE
JOB'S PROGRESS. SUBMITTALS SHALL BE IN ACCORDANCE WITH THE GENERAL
COD I T I ONS USING THE MANUFACTURER'S LISTED ON THE DRAWINGS. SHOP
DRAWINGS SHALL INCLUDE ALL DATA THAT PERTAINS TO THE REQUIREMENTS SET
FORTH ON THE DRAWINGS AND IN THE SPECIFICATIONS. THE SUBMITTAL SHALL
INCLUDE BUT MDT LIMITED TO CUTS OR CATALOGS INCLUDING DESCRIPTIVE
LITERATURE AND CHARACTERISTICS OF EQU I PIENT SHALL SHOW MAJOR
DIMENSIONS, ROUGHING -IN DATA, CAPACITY. (LINES. PRESSURE DROP, CODE
COMPLIANCE, MOTOR AND DRIVE DATA AND ELECTRICAL DATA. OBSERVE SPECIAL
INSTRUCTIONS WEN REWIRED. SUBMITTALS SWILL. BEAR THE STAMP OF THE
GEERAL AND SUB- CONTRACTOR SHOWING THAT HE HAS REVIEWED AND CONFIRMED
THAT THEY ARE IN CONFORMANCE WITH THE CONTRACT DRAWINGS AND
SPECIFICATIONS OR INDICATE WERE EXCEPTIONS TAKE PLACE. LAC( OF SUCH
CONTRACTOR'S REVIEW AND APPROVAL WILL BE CASE FOR REJECTION WITHOUT
REVIEW BY TENANT'S CONSTRUCTION MANAGER. ALL SHOP DRAWINGS MUST
APPEAR IN THE OPERATION AND MAINTENANCE MANUALS LEFT ON SITE AT JOB
COMPLETION.
1
2
1 3
4 1 5 1 6
2. TENANT'S CONSTRUCTION MANAGER'S REVIEW OF STOP DRAWINGS OR SCHEDULES
SHALL NOT RELIEVE THE CONTRACTOR FROM RESPONSIBILITY FOR ERRORS,
OMISSIONS OR OTHER DEFICIENCIES OR DEVIATIONS IN THE SHOP DRAWING FROM
THE CONTRACT DRAWINGS AND SPECIFICATIONS.
J. RECORD DRAWINGS
1. TIE CONTRACTOR SHALL MAINTAIN ONE COPY OF DRAWINGS AND SPECIFICATIONS
ON THE JOB SITE TO RECORD DEVIATIONS FROM CONTRACT DRAWINGS, SUCH AS:
A. LOCATION OF CONCEALED PIPING VALVES AND DUCTS.
B. REVISIONS, ADDENOUMS, AND CHANGE ORDERS.
C. SIGNIFICANT DEVIATIONS MADE NECESSARY BY FIELD CONDITIONS,
APPROVED EQUIPMENT SUBSTITUTIONS. AND CONTRACTOR'S COORDINATION
WITH OTHER TRADES.
D. EXACT ROUTING OF ALL SANITARY AND DOMESTIC WATER PIPING two
FLOOR.
2. AT COMPLETION OF THE PROJECT AND BEFORE FINAL APPROVAL, THE CONTRACTOR
SHALL MAKE ANY FINAL CORRECTIONS TO DRAWINGS AND CERTIFY THE ACCURACY
OF EACH PRINT BY SIGNATURE THEREON. THE DRAWINGS ARE M BE TURNED
OVER TO THE TENANT.
K. GUARANTEE
1. THE CONTRACTOR SWILL GUARANTEE ALL MATERIALS AND WORK UNDER HIS
CONTRACT AND SHALL MAKE GOOD, REPAIR OR REPLACE AT HIS OWN EXPENSE.
ANY DEFECTIVE WORK, MATERIAL. OR EQUIPMENT WHICH MAY BE DISCOVERED
WITHIN A PERIOD OF 12 MONTHS FROM THE DATE OF ACCEPTANCE (IN WRITING)
OF THE INSTALLATION BY THE TENANT'S CONSTRUCTION MANAGER. PROVIDE
EXTENDED WARRANTIES AS SPECIFIED WITH INDIVIDUAL EQUIPMENT. IN CASE
OF REPLACEMENT OR REPAIR OR EQUIPMENT DUE TO FAILURE WITHIN GUARANTEE
PEROID. GUARANTEE ON THAT PORTION OF WORK SHALL. BE EXTENDED FOR A
PEROID OF ONE (i) YEAR FROM DATE OF SUCH REIVZEMENN OR REPAIR.
L. OPERATIONS MANUALS
1. ONE COPY OF EACH OPERATION AND MAINTENANCE MANUAL FOR ALL EQUIPMENT
FURNISHED ON JOB SHALL BE COLLECTED AND INSERTED IN A 3' THREE RING
BINDER AND TURNED OVER TO THE TENANT. EACH NOTEBOOK SHALL INCLUDE BUT
NOT BE LIMITED TO INSTALLATION. MAINTENANCE AND OPERATING
INSTRUCTIONS, PAMPHLETS OR BROCHURES APPROVED SHOP DRAWINGS AND
WARRANTIES OBTAINED FROM EACH MANUFACTURER OF PRINCIPAL ITEMS OF
EQU IPMENT.
M. SLEEVES
1. THE CONTRACTOR SHALL PROVIDE SLEEVES TO PROTECT EQUIPMENT Olt
FACILITIES IN THE INSTALLATION. EACH SLEEVE SWILL EXTEND THROUGH IT'S
RESPECTIVE FLOOR, WALL OR PARTITION AND SHALL BE CUT FLUSH WITH EACH
SURFACE EXCEPT SLEEVES THAT PENETRATE THE FLOOR, WHICH SHALL Dam
2' ABOVE THE FLOOR.
2. ALL SLEEVES AND OPENINGS THROUGH FIRE RATED WALLS AND/OR FLOORS SHALL
BE FIRE SEALED WITH CALCIUM SILICATE. SILICONE 'RTV' FOAM, '31' FIRE
RATED SEALANTS OR EQUAL, SO AS TO RETAIN THE FIRE RATING OF THE FLOOR
OR WALL. CONFORM TO U.L. ASSEMBLY RATING OF FLOOR OR WALL.
3. SLEEVES IN BEARING AND MASONRY WALLS, FLOORS, AND PARTITIONS SHALL BE
STANOMD WEIGHT STEEL PIPE FINISHED WITH SMOOTH EDGES. FOR OTHER THAN
MASONRY PARTITIONS, THROUGH SUSPENDED CEILINGS, OR FOR CONCEALED
VERTICAL PIPING, SLEEVES SHALL BE NO. 22 U.S.G. GALVANIZED STEEL
MINIMUM.
4. DUCT SLEEVES TO BE MINIMUM 14 GAUGE STEEL.
N. HANGERS
1. HANGERS SHALL INCLUDE ALL MISCELLANEOUS STEEL SUCH AS ANGLE IRON,
BAWDS, C -CLAPS WITH RETAINING CLIPS, CUNELS, HANGER RODS, ETC.,
NECESSARY FOR THE INSTALLATION OF WORK.
2. HANGERS SHALL BE FASTENED TO BUILDING STEEL. CONCRETE, OR MASONRY. BUT
NOT TO PIPING OR DUCTWORK. HANGING FROM METAL DECK IS NOT PERMITTED.
HAVERS MUST BE ATTACHED TO UPPER CHORD OF BAR JOIST. WHERE
INTERFERENCES OCCUR, IN ORDER TO SUPPORT DUCTWOiRK OR PIPING, THE
CONTRACTOR MUST INSTALL TRAPEZE TYPE HANGERS OR SUPPORTS WHICH SHALL
BE LOCATED WHERE THEY DO NOT INTERFERE WITH ACCESS TO FIRE DAMPERS,
VALVES. ACCESS DOORS AND OTHER EQUIPMENT SERVICE REQUIREMENTS AND/OR
OTHER TRADES. HANGER TYPES AND INSTALLATION METHODS ARE SUBJECT TO
LANDLORD CRITERIA.
3. HANGERS FOR ALL INSULATED PIPING SWILL BE SIZED AND INSTALLED FOR THE
OUTER DIAMETER OF INSULATION. INSTALL 6' LONG SPLIT CIRCLE GALVANIZED
SADDLE BETWEEN THE HANGER AND THE PIPE INSULATION.
4. HANGERS AND PIPING OF DISSIMILAR METALS SHALL BE DI- ELECTRICALLY
SEPARATED FROM ONE ANOTHER.
0. ACCESS DOORS
1. FURNISH STEEL ACCESS DOORS AND FRAMES, MIN. 16' X 20' OR AS SHOWN ON
DRAWINGS. TO GENERAL CONTRACTOR FOR ALL LOOT I ONS WHERE NECESSARY TO
PROVIDE ACCESS TO CONCEALED VALVES. AND OTHER EQUIPMENT REQUIRING
SERVICE OR INSPECTION. LOCATION. TYPE, SIZE AND NUMBER AS DETERMINED
BY CONTRACTOR AND APPROVED BY TENANT CONSTRUCTION MANAGER TO SUIT
EQUIPMENT REQUIREMENTS. GENERAL CONTRACTOR WILL INSTALL ACCESS DOORS
AND FRAMES.
2. ACCESS DOORS LOCATED IN FIRE -RATED WALLS. FLOORS. CEILING -FLOOR OR
CEILING-ROOF ASSEMBLIES SHALL BE FIRE RATED. UNDERWRITER'S
LABORATORIES, INC., LISTED AND LABELED.
3. ACCESS DOORS SWUM. BE FLUSH TYPE, MANUFACTURED FROM ND. 14 GAUGE
STEEL. COMPLETE WITH FLUSH FLANGE TYPE FRAMES MANUFACTURED FROM ND.
16 GAUGE STEEL, PROVIDED WITH ANCHORS. ACCESS DOORS SHALL. BE SUITABLE
FOR INSTALLATION IN WALL OR CEILING MATERIALS SHOWN IN ROOM FINISH
SCHEDULES.
P. ELECTRICAL MOTORS
1. FURNISH. INSTALL AND ALIGN ALL MOTORS REQUIRED FOR THIS EQUIPMENT.
UNLESS THEY ARE FACTORY INSTALLED ON THE UNIT, ALL STARTERS AND
ASSOCIATED WIRING AND SAFETY SWITCHES FOR SUCH MOTORS SHALL BE
FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR. STARTERS SHALL
MEET ALL REQUIREMENTS AS DEFINED IN THE ELECTRICAL DIVISION OF THE
SPECIFICATIONS.
2. DESIGN. CONSTRUCTION AND PERFORMANCE CHARACTERISTICS OF MOTORS SHALL
CONFORM TO ALL APPLICABLE PROVISIONS OF LATEST W MA. ANSI. ISEE
STANDARDS FOR ELECTRICAL EQUIPMENT. ALL MOTORS SWILL BE SUITABLE FOR
OPERATION ON VOLTAGE VARIATION OF PLUS OR MINUS IDS. 40 DEGREES C
AMBIENT TEMPERATURE; HAVE A SERVICE FACTOR OF NOT LESS THAN 1.15.
Q. LOW VOLTAGE (24 VOLT) WIRING
1. THE CONTRACTOR IS TO INSTALL ALL LOW VOLTAGE WIRING REQUIRED FOR HIS
EQUIPMENT. THIS WORK INCLUDES ALL TRANSFORMERS AND DEVICES TO MAKE
THIS A COMPLETE FUNCTIONAL SYSTEM.
2. ALL WORK IS TO CONFORM TO THE LATEST ADDITION N.E.0 AND TO DIVISION
16 ELECTRICAL SPECIFICATIONS.
3. ANY CONDUIT REWIRED BY CODE OR THE LANDLORD WILL BE INSTALLED BY THE
ELECTRICAL SUBCONTRACTOR.
DIVISION 15 - MECHANICAL
SECTION 15200
PLUMBING
4
A. SCOPE OF WORK
1. THIS CONTRACTOR SWILL FURNISH ALL LABOR, MATERIALS. EQU IPMENT,
SERVICES, TOOLS, TRANSPORTATION AND FACILITIES NECESSARY FOR.
REASONABLY IMPLIED AND INCIDENTAL TO. THE FURNISHING. INSTALLATION,
COMPLETION AND TESTING OF ALL THE WORK FOR THE PLUMBING SYSTEMS AS
SHOWN ON THE DRAWINGS. CALLED FOR IN THE SPECIFICATIONS, AND AS
REQUIRED BY JOB CONDITIONS, TO INCLUDE. BUT NOT BE LIMITED TO THE
FOLLOWING: (REFER M RESPONSIBILITY SCHEDULE FOR EXACT RESPONSIBILITIES)
A. COMPLETE SANITARY PIPING SYSTEMS OF WASTE, DRAINS, AND VENTS.
B. COMPLETE COLD AND HOT WATER PIPING SYSTEMS. APPURTENANCES AND
INSULATION.
C. PLUMBING F I XTUiES AND EQUIPMENT AS SCHEDULED.
D. COMPLETE NATURAL GAS PIPING SYSTEMS (AS APPLICABLE. REFER TO
PLANS).
E. TESTS AND ADJUSTMENTS.
2. BEFORE STARTING WORK. THIS CONTRACTOR SHALL EXAMINE THE ARCHITECTURAL,
STRUCTURAL. MECHANICAL AND ELECTRICAL. PLANS AND SPECIFICATIONS TO
SEQUENCE, COORDINATE, AND INTEGRATE THE VARIOUS ELEMENTS OF THE
PLUMBING SYSTEM, MATERIALS, AND EQUIPMENT WITH OTHER CONTRACTORS TO
AVOID INTERFERENCES AND CONFRONTATIONS.
3. RELOCATION OF EXISTING WATER. GAS. WASTE, VENT, OR DRAINAGE LINES TO
FACILITATE STORE DESIGN CRITERIA MUST BE INCLUDED IN BID PROPOSAL.
B. PLUMB I NG EQU I PMENT
C. GENERAL. PIPING REQU I REENTS
1. GENERALLY. SANITARY AND POTABLE WATER TAPS WILL BE PROVIDED BY THE
LANDLORD. FIELD VERIFY EXACT CONNECTION POINTS PRIOR TO SUBMITTING
BID AND NOTIFY THE TENANT'S CONSTRUCTION MANAGER IF CONDITIONS ARE NOT
AS SHOWN ON THE PLANS OR AS STATED IN THE SPECIFICATIONS. CONTRACTOR
MUST VERIFY THE OPERABILITY OF ENTIRE SYSTEM PRIOR TO TIE IN AS
FOLLOWS:
A. SNAKE SANITARY FOR A DISTANCE OF 100 FEET AND REPORT ANY
BLOCKAGE.
B. TEST WATER PRESSURE TO INSURE MINIMUM OF 50 PSI.
2. INSTALL ALL NECESSARY PIPE HANGERS, SADDLES, AND CARRIERS TO PROPERLY
SUPPORT ALL PIPING AND FIXTURES. HUNGERS SHALL. SUIT TYPE OF PIPING
PROVIDED AND BE SPACED AT A MAXIMUM SPAN OF 5 FEET. PROVIDE SWAY AND
SEISMIC BRACING MERE REQUIRED BY CODES.
5
C.1
7
1.1
3. ESCUTCHEONS SHALL BE CROE PLATED, SIZE AS REQUIRED AND PLACED AT ALL
PIPE PENETRATIONS AT MALLS, FLOORS, AND CEILINGS IN FINISHED AREAS.
4. FLASHING SHALL BE SEALED WATERTIGHT AND PERFORMED IN ACCORDANCE TO THE
LANDLORD'S CRITERIA. USE A LANDLORD APPROVED ROOFING CONTRACTOR WHERE
APPLICABLE.
D. PIPING
1. SANITARY PIPING - ND PVC ALLOWED (STORM PIPING AS REWIRED)
A. WASTE. DRAIN AND VENT PIPING SHALL BE SERVICE WEIGHT, CAST IRON
SOIL PIPE. VENT PIPING ABOVE FLOOR 2' OR SMALLER MAY BE
GALVANIZED STEEL.
B. JOINTS: BELOW FLOOR SLAB - COMPRESSION TYPE PLASTIC SEA. (HUB
AND SPIGOT). ABOVE FLOOR SLAB - NEOPRENE SEALING SLEEVE WITH
STAINLESS STEEL SHIELD AND CLAMP WITH APPROVED NEOPRENE - BASED
LUBRICANT. (HU3LESS). GALVANIZED VENT - SCREWED JOINTS WITH
TEFLON TAPE ON MALE THREADS.
C. PITCH WASTE LINES 2' AND SMALLER MDT LESS THAN 1/4' PER FOOT.
PITCH LARGER MAINS NOT LESS THAN 1/8' PER FOOT.
D. INSTALL A CLEANWT AT BASE OF EACH SOIL STACK. AT EACH CHANGE IN
DIRECTION. AT INTERVALS NOT OVER 50 FEET. AND ELSEWHERE AS SHOWN
ON DRAWINGS OR REWIRED BY LOCAL CODE. CLEMOUTS SHALL NOT BE
INSTALLED IN PUBLIC AREAS WITHOUT SPECIFIC PERMISSION BY TENANT'S
CONSTRUCTION MANAGER; BUT WHERE NECESSARY. THE WALL COVERS ARE
M BE STAINLESS STEEL AND THE FLOOR COVERS ARE TO BE GRASS (FLUSH
WITH FINISHED FLOOR). PROVIDE COVERS WITH INSET AREA FOR
CARPETED FLOOR LOCATIONS. ALL CLEAN -OUT LOCATIONS SHALL BE
APPROVED BY THE TENANT'S CONSTRUCTION MANAGER.
E. INSULATE ALL HORIZONAL RUNS OF PIPING LOCATED IN CEILING SPACES
WHEN APPLICABLE. INSULATION M BE AS SPECIFIED FOR WATER PIPING.
F. INSULATE THE TRAP, SANITARY AND SUPPLY PIPES UNDER LAVATORY WITH
1/2' ARMSTRONG 'ARMAFLDP PIPING INSULATION OR TRIIEBRO MODEL 102N
wHANDI LAV GUARD' INSULATION KIT.
2. CONDENSATE PIPING SHALL. BE TYPE 'L' DRAWN COPPER TUBE WITH 95-5 TIN -
ANTIMONY SOLDERED JOINTS AND WROUGHT COPPER FITTINGS WITH DIELECTRIC
SEPARATION BETWEEN DISSIMILAR METALS.
3. POTABLE WATER PIPING:
A. BELOW GRADE: TYPE V. ANNEALED TWERED COPPER TUBE FOR PIPE
SIZES 2 INCHES AND SMALLER. BRAZE ALL JOINTS.
B. ABOVE GRADE: TYPE 'L' DRAWN COPPER TUBE WITH WROUGHT COPPER
FITTINGS AND 954 TIN- ANTIMONY SOLDER.
C. INSTALL AIR CHAMBER SHOCK ABSORBERS IN PIPING SYSTEM TO PREVENT
NDISE AND DAMAGE DUE TO WATER H AIAU.
D. ALL BRANCH PIPING SYSTEM SHALL HAVE ACCESSIBLE SERVICE VALVE.
PROVIDE SHUT OFF VALVES IN THE SUPPLY PIPING TO EVERY FIXTURE.
PROVIDE ACCESS DOCRS WHERE NECESSARY.
E. PROVIDE WATER METER AND REMOTE READER PER LANDLORD'S CRITERIA OR
LOCAL UTILITIES REQUIREMENTS IF APPLICABLE. REFER TO PLANS TO
DETERMINED IF WATER METER IS REWIRE).
F. SECURE PIPE AT ANGLE STOPS.
G. PROVIDE FLEXIBLE INSERTS AT ALL PIPE PENETRATIONS THROUGH FRAMING
TO KEEP PIPES FROM HITTING FRAME WHEN IN OPERATION.
4. GAS PIPING
A. PROVIDE A COMPLETE GAS PIPING SYSTEM IF APPLICABLE. REFER TO
PLATS M DETERMINE IF A GAS SYSTEM IS REQUIRED.
B. LON PRESSURE 14' W.C. AND BELOW) GAS LINES SHALL BE BLACK STEEL,
SCEDUULE 40, ASTM A -120, WITH MALLEABLE 'THREADED F i TT I NGS FOR 2'
AND SMALLER, AND WITH WELDED JOINTS FOR 2-1/2' AND LARGER.
MEDIUM PRESSURE ABOVE 14' W.C.) SHALL HAVE WELDED JOINTS.
C. PROVIDE A CAS COCK, DIRT LEG, AND UNION CONNECTION TO EACH PIECE
OF EQUIPMENT. PROVIDE GAS METER AND/OR REGULATOR AS REWIRED.
REGULATOR TO BE VENTED TO THE EXTERIOR.
D. PITCH PIPING AT A UNIFORM GRADE OF 1 4' IN 15 FEET UPWARD IN
DIRECTION OF FLOW. SUPPORT PIPING 5 FEET. SUPPORT AS
REWIRED BY LANDLORD CRITERIA. AS DETAILED ON DRAWINGS. CR BY
STANDARD INDUSTRY PRACTICE. WH I LEVER IS MORE STRINGENT.
E. GAS PIPING EXPOSED ON ROOF MUST BE PAINTED WITH RUST - INHIBITING
PAINT.
F. INSTALLATION, TESTING AND PURGING OF GAS PIPING SHALL BE DOE PER
THE REQUIREMENTS OF THE LOCAL GAS COMPANY, LOCAL CODES. AND
APPLICABLE NFPA 54 CODES.
G. CONTACT AND COORDINATE GAS SERVICE AND METER REQUIREMENTS WITH
THE LOCAL GAS COMPANY AND THE MALL'S MANAGER PRIOR TO BID.
5. INSULATION
A. INSULATE ALL WATER AND INTERIOR CONDENSATE PIPING WITH 1' THICK SNAP-ON FIBERGLASS PIPE INSULATION WITH AN ALL
SERVICE JACKET )TO MEET LOCAL CODES AND UL FLAME SPREAD RATING OF
25 AND SMOKE DEVELOPED RATINGS OF 50. APPROVED MANUFACTURER:
MANVILLE MICRO -LOK.
6. TEST Nk STERILIZATION
A. LEAKAGE TESTS SHALL BE PER LOCAL CODES. MINIMUM AS FOLLOWS:
1. TEST POTABLE WATER PIPING AND CONDENSATE PIPING AT 125 PSIG
FOR SIX FOURS.
2. TEST DRAIN, WASTE. VET PIPING BY AID' WATER COLUMN FOR
TWO HOURS. ALL JOINTS SHALL BE GAS AND WATER TIGHT.
3. TEST GAS PIPING WITH PER NFPA 54 CODES.
4. STERILIZE POTABLE HOT 0 COLD WATER LINES UPON COMPLETION OF
SYSTEM. STERILIZE WATER SYSTEM IN ACCORDANCE WITH LOCAL
CODES.
DIVISION 15 - MECHANICAL
SECTION 15500
HEATING, VENTILATION, AND AIR CONDITIONING
A. SCOPE OF WORK
1. THE HNAC CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, EQUIPMENT,
SERVICES, TOOLS, TRANSPORTATION AND FACILITIES NECESSARY FOR,
REASONABLY IMPLIED AND INCIDENTAL TO. THE FURNISHING, INSTALLATION,
COIPLET I ON AND TESTING OF ALL THE WORT( FOR THE MECHAN I CAL SYSTEMS AS
SHOWN ON THE DRAWINGS, CHILLED FOR IN THE SPECIFICATIONS. AND AS
REWIRED BY JOB CONDITIONS, TO INCLUDE, BUT NOT BE LIMITED TO THE
FOLUIWING:(REFER TO RESPONSIBILITY SCHEDULE FOR EXACT RESPONSIBILITIES)
A. HNAC UNITS, EQUIPMENT. AND APPURTENANCES.
B. DUCTWORK, FITTINGS. DAMPERS, AND INSULATION.
C. HYDRONIC PIPING AND INSULATION (AS APPLICABLE. REFER TO PLANS).
D. REFRIGERANT PIPING (AS APPLICABLE. REFER TO PLANS).
D. DIFFUSERS, GRILLES, AND REGISTERS.
E. CURBS AND STEEL FRAMING FOR SUPPORT (AS APPLICABLE. REFER TO
PLANS).
F. TESTING. ADJUSTING. AND BALANCING.
G. OPERATIONS MANUALS.
H. TEMPERATURE CONTROLS AND RELATED DIAGRAMS.
1. SEQUENCES OF OPERATION.
J. CONNECTION M ANY LANDLORD DEW MANAGEMENT SYSTEM.
3. BEFORE STARTING WORK, THIS CONTRACTOR SHALL EXAMINE THE ARCHITECTURAL,
STRUCTURAL, MECFAN I CAL AND ELECTR I CAL PLANS AND SPECIFICATIONS TO
SEQUENCE, COORDINATE, AND INTEGRATE THE VARIOUS ELEMENTS OF THE WAC
SYSTEM, MATERIALS, AND EQUIPMENT WITH OTHER CONTRACTORS TO AVO I D
INTERFERENCES AND CONFRONTATIONS.
B. WAC EQUIPMENT
1. PRIMARY HEATING, VENTILATION AND AIR CONDITIONING UNITS.
A. PRIMARY HEATING. VENTILATION, AND AIR CONDITIONING UNITS ARE TO
BE BY TRAE COiRPORATION AS SCHEDULED. Al COMPRESSORS ARE TO
INCLUDE A 5-YEAR MUM WARRANTY.
B. EQUALS EQUIPMENT AS MANUFACTURED BY CARRIER OR YORK IF
NOT AVAILABLE THROUGH REASONABLE EFFORT.
C. ALL EQUIPMENT SHALL BE COMPLETE IN EVERY RESPECT WITH ALL
DEVICES, APPURTENANCES, AND ACCESSORIES PROVIDED TO MEET THE
DESIGN INTENT AND OPERATION OF THE SYSTEMS SHOWN ON THE DRAWINGS
AND SPECIFIED HEREIN.
D. EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE
MANUFACTURER'S INSTRUCTIONS. ALL AIR CONDITIONING EQUIPMENT MAST
HAVE A CONDENSATE DRAIN AND BE TRAPPED IN ACCORDANCE WITH
MANUFACTURERS DATA. SEE DRAWINGS FOR ADDITIONAL DETAILS.
E. SECONDARY DRAIN PANS ARE REWIRED TO BE INSTALLED BENEATH ALL
INDOOR AIR CONDITIONING EQUIPMENT WITH THE EXCEPTION OF VAV
BOXES. SECONDARY PANS ARE TO PROTECT ENTIRE UNIT. PROVIDE
CONDENSATE PUMPS, AS REQUIRED. CONDENSATE SHALL BE DIRECTED TO
MOP SINK OR AS SPECIFIED ON PLANS.
2. VAR I ABLE AIR VOLUME BOXES (VAV)
A. MERE SHOWN ON DRAWINGS. PROVIDE VAV BOXES COMPLETE WITH
CONTROLS. HEATING COILS (FANS AS REQU I RED) . ALL DUCT CONNECTIONS
FLEXIBLE DUCT/PIPE CONNECTIONS SHALL BE PROVIDED BY THE
CONTRACTOR.
3. TOILET EXHAUST FANS
A. MERE SHOWN ON DRAWINGS, PROVIDE A TOILET EXHAUST FAN UNIT
COMPLETE WITH GRAVITY BACK DRAFT DAMPERS. ALL DUCTWORK, ROOF
OPENINGS AND CAPS NECESSARY TO PROVIDE A COMPLETE EXHAUST SYSTEM
SHALL BE PROVIDED BY THE CONTRACTOR. REFER TO PLANS FOR
APPLICABILITY.
4. BASEBOARD. CABINET. AND UNIT HEATERS
A. WHERE SHOWN ON DRAWINGS, PROVIDE ELECTRIC HEATERS COMPLETE WITH
ELECTRIC HEATING COIL, CONTROLS, AND INTEGRAL THERMOSTAT.
5. INLINE PUPS
A. MERE SHOWN ON DRAWINGS PROVIDE AN INLINE CLOSE COUPLED PUP(S).
BRONZE FITTED, PUMPS SHALL BE FURNISHED WITH BRONZE CASE WEARING
RINGS. BRONZE SHAFT SLEEVE AND MEC WN I CA. SHAFT SEAL RATED FOR.
PUMPS TO BE SO CONSTRUCTED THAT THEY MAY BE MOUNTED IN A
HORIZONTAL OR VERTICAL PIPE LINE. MOTOR TO BE 1750 RPM UNLESS
NOTED OTHERWISE.
8. VIBRATION ISOLATION DEVICES
A. VIBRATION ISOLATION DEVICES SHALL BE PROVIDED IN ALL SUPPORTS
BETWEEN VIBRATING EQUIPMENT (FANS, ROOFTOP UNITS. AIR HIADLERS,
FAN POWERED VAV BOXES, ETC. AND STRUCTURE.
B. V I BRAT I NG EQUIPMENT HUNG FROM STRUCTURE SHALL BE ISOLATED WITH
RUBBER AND SPRING DEVICES. VIBRATING EQUIPMENT SUPPORTED FROM
FLOOR OR DECK SHALL BE ISOLATED WITH HOUSED SPRING MOUNT DEVICES.
C. EXAMINE DEAD LOAD AND OPERATING LOAD CONDITIONS WHEN SELECTING
DEVICES. ADJUST FOR PROPER ALIGNMENT AND LOADING. AVOID
'GROUNDING' THE ISOLATOR.
D. CHECK HANGER ROD SIZE FOR ALLOWABLE LOADS AT THE ISOLATING DEVICE
AND AT THE UPPER AND LOWER ATTACHMENTS TO STRUCTURES, DUCTS,
EQU I PARENT. ETC.
E. CONSULT MANUFACTURER FOR APPLICATION DATA.
7
'._]
9 I 10 I 11
7. CURBS AND STEEL FRAMING FOR SUPPORT
A. THIS CONTRACTOR WILL PROVIDE ALL NECESSARY CURBS AND STEEL
FRAMING REQUIRED TO INSTALL ALL WAC EQUIPMENT AS DESCRIBED OR
IMPLIED ON THE DRAWINGS. CURBS SHALL BE A MINIMUM OF 14' HIGH,
OF THE SAME MANUFACTURER OF THE EQUIPMENT SUPPORTED. INSULATE
UNDER THE COMPRESSOR SECTION TO PREVENT CONDENSATION. ALL CURBS
MUST BE INSTALLED SO THAT TOP OF CURBS ARE 'DEAD' LEVEL. ALL
PENETRATIONS OF EXISTING STRUCTURE SHALL BE DONE IN ACCORDANCE
TO THE LANDLORD'S GUIDELINES AT THIS CONTRACTOR'S EXPENSE.
E. METAL DUCTWORK - NO FIBERGLASS DUCT ALLOWED
1. ND DUCTWORK SWILL BE FABRICATED PRIOR TO APPROVAL BY THE TENANT'S
CONSTRUCTION MANAGER. SIGNIFICANT DEVIATIONS FROM DESIGN MUST BE
APPROVED BY TENANT'S CONSTRUCTION MANAGER PRIOR TO FABRICATION OR
INSTALLATION. ALL DUCT MAINS ARE TO BE RECTANGULAR UNLESS NOTES
OTHERWISE. ALL DUCT BRANCHES TO DIFFUSERS ARE TO BE ROOD RIGID DUCT.
(FLEXIBLE DUCT CONNECTIONS TO THE DIFFUSER ARE NOT TO EXCEED 5' -0').
2. EXCEPT AS OTHERWISE INDICATED, FABRICATE AND INSTALL RECTANGULAR DUCTS
WITH GALVANIZED SHEET STEEL. IN ACCORDANCE WITH SMACNA 'HVAC DUCT
CONSTRUCTION STANDARDS' OF THE LATEST EDITION. CONFORM TO THE
REQUIREMENTS IN THE REFERENCED STANDARD FOR METAL THICKNESS.
REINFORCING TYPES AND INTERVALS, TIE ROD APPLICATIONS. AND JOINT TYPES
AND INTERNALS.
3. EXCEPT MERE OTHERWISE INDICATED. CONSTRUCT DUCT SYSTEMS TO THE
FOLLOWING PREP CLASSIFICATIONS: (VERIFY WHETHER RETURN OR EXHAUST
DUCT IS POSITIVE OR NEGATIVE PRESSURE).
A. SUPPLY DUCTS: 2 INCHES WATER GAUGE. POSITIVE PRESSURE
B. RETURN AND EXHAUST DUCTS: 2 INCHES WATER GAUGE. NEGATIVE
PRESSURE.
PRESSURE TEST DUCTS FOR LEAKAGE. REMAKE LEAKING JOINTS AND APPLY
SEALANTS AS REQUIRED TO FABRICATE A SYSTEM THAT DOES NOT EXCEED 5W
LEAKAGE OR LESS AS STATED BY PRESSURE CLASS RATINGS IN SMACNA
STANDARDS.
4. AS A MINIMUM. OAK ALL FLAT SURFACES OR REINFORCE WITH A BEAD
APPROXIMATELY 3/8' WIDE X 3/16' DEEP ON 12' CENTERS TO PREVENT
VIBRATIONS.
5. INSTALL DOUBLE THICKNESS TURNING VANES IN ALL RIGHT ANGLE ELBOWS.
8. INSTALL RIGID ROUE AND RECTANGULAR METAL DUCT WITH SUPPORT SYSTEMS
INDICATED IN SMACNA STANDARDS. SUPPORT HORIZONTAL DUCTS WITHIN 2 FEET
OF EACH ELBON AND WITHIN 4 FEET OF EACH BRANCH INTERSECTION USING
DOUBLE STRAP HANGERS ON EACH SIDE OF FITTING. SUPPORT VERTICAL DUCTS
AT A MAXIMUM INTERVAL OF 18 FEET AND AT EACH FLOOR. NO WOOD SHALL BE
USED TO SUPPORT OR BRACE DUCTS. PROVIDE SWAY AND SEISMIC BRACING AS
REQUIRED BY STATE AND LOCAL CODES OR BY LANDLORD.
7. WHERE DUCTS PASS THROUGH ROOFS AND FLOORS. PROVIDE AS MINIMUM 1-
1 'X1 -1/2' X1/8' STEEL ANGLE FRAMES AT EACH SIDE OF OPENING. THE
AWILAR SPACE BETWEEN DUCT AND ANGLE FRAMES SHALL BE CAULKED WITH
SILICONE SEALANT OR FIREPROOFED AS REQUIRED BY ASSEMBLY FIRE RATING.
B. ALL TRAVERSE JOINTS AND SEAMS IN SUPPLY AIR DUCT SHALL BE SEALED AIR
TIGHT WITH DAP CIC DUCT SEALER. JOINTS ALSO SHALL BE RIVETED OR
CONNECTED WITH SHEET METAL SCREWS.
9. SOFT ELASTOER BUTYL GASKET WITH ADHESIVE BACKING SHALL BE USED TO
SEAL FLANGED JOINTS.
10. DUCT TRANSITIONS SHALL NOT EXCEED 30 DEGREES SLOPE EXCEPT AS
SPECIFICALLY NOTED OTHERWISE.
11. PROVIDE ACCESS M ALL MOTORIZED DAMPERS. FIRE DAMPERS. CONTROLS. AND
OTHER ITEMS IN DUCi1ORK THAT REQUIRE SERVICE OR INSPECTION. IF THE
ACCESS PANEL LOCATION IS EXPOSED TO THE SALES AREA, IT MUST BE
APPROVED BY THE TENANT'S CONSTRUCTION MANAGER PRIOR TO INSTALLATION.
LAY-IN SUPPLY AND RETURN AIR DIFFUSERS, GRILLES AND REGISTERS WITH
PLASTER FRAMES MAY BE USED AS ACCESS LOCATIONS.
12. FLEXIBLE CONNECTIONS
A. FLEXIBLE COLLARS SHALL BE PROVIDED IN ALL CONNECTIONS BETWEEN
VIBRATING EQUIPMENT (FINS. ROOFTOP UNITS, AIR HANDLERS, FAN
POWERED VAV BOXES, ETC AND DUCTS OR CASINGS. ALSO. PROVIDE
FLEXIBLE CONNECTIONS WHERE DUCTS CROSS BUILDING EXPANSION JOINTS.
B. FLEXIBLE CONNECTIONS SHALL CONSTRUCTED OF NEOPRENE-COATED
FLAMEPROOF FABRIC. PROVIDE ADEQUATE JOINT FLEXIBILITY TO ALLOW
FOR MOVEMENT AND PREVENT THE TRANSMISSION OF VIBRATION.
C. FLEXIBLE CONNECTION IS TO BE RATED FOR THE OPERATING PRESSURE OF
THE SYSTEM.
13. FIRE CAMPERS
A. PROVIDE PR I MARY FIRE DAMPERS WHERE INDICATED OR REQUIRED BY
CODES. DAMPERS SHALL BE DESIGNED FOR HORIZONTAL OR VERTICAL FLOW
OF AIR AS REQUIRED. FIRE DAMPERS SHALL BE UL LABELED.
B. FIRE DAMPERS SHALL HAVE THE BLADES OUT OF THE AIRSTREAM AND A
15507 FUSIBLE LINK. TYPE A. AS MINIMUM.
C. PROVIDE ALL NECESSARY FRAMING AND SLEEVES FOR DAMPER MOUNTING PER
UL AND CODE REQU I RELENTS.
D. PROVIDE DUCT ACCESS DOORS IN AN ACCESSAB.E LOCATION FOR ALL FIRE
DAMPERS. DOOR IS TO BE 20 GA GALVANIZED DOOR WITH QUICK- OPENING
LATCH AND PIAD HINGE.
14. FLEXIBLE AIR DUCT
A. FLEXIBLE AIR DUCT SHALL BE 1' INSULATED CLASS 1 AND RATED FOR THE
OPERATING PRESSURE OF THE SYSTEM. DUCT CONSTRUCTION MATERIAL
LADLORD E S REQUIREMENTS AND BE INCLUDED ASL20 I CODES THE BID.
B. FLEXIBLE AIR DUCT MAY ONLY BE USED IN VERTICAL APPLICATIONS WITH
PRIOR APPROVAL FROM TENANT'S CONSTRUCTION MANAGER.
C. FLEXIBLE DUCT SHALL NOT EXTEND OVER 5' -0' IN LENGTH AT ANY ONE
LOCATION.
15. SUPPLY AIR TAKE -OFF FITTINGS
A. PROVIDE CONICAL OR 'BELL- MOUTH' TAKE-OFFS FROM MAIN DUCTWOiRK TO
ROBE BRANCHES. INSTALL PER MANUFACTURER'S INSTRUCTIONS.
B. PROVIDE 45' RECTANGULAR TAKE -OFFS FROM MAIN DUCTWORK TO
RECTANGULAR BRANCHES.
18. DAMPERS
A. PROVIDE MANUAL LOCKING QUADRANT VOLUME CONTROL DAMPERS WITH
HAANME OPERATORS IN EACH BRANCH MICT AND AS SHOWN ON PLANS TO
FACILITATE AIR BALANCING.
B. WHERE ACCESS M BALANCING DAMPER IS RESTRICTED, YOUNG'S
REGULATORS SHALL BE USED.
C. ALL RECTANGULAR DAPERS IN OUTSIDE AIR, RELIEF AIR. OR RETURN AIR
DUCTS ARE TO BE OF OPPOSED BLADE TYPE. ALL OUTSIDE AIR DUCT
DAMPERS MST ALSO BE OF THE LOW LEAKAGE TYPE.
D. ALL MOTORIZED DAMPERS NOT FURNISHED WITH EQUIPMENT ARE TO BE
HONEYWELL DAMPERS.
17. DIFFUSERS, GRILLES, AND REGISTERS
A. PROVIDE DIFFUSERS GRILLES AND REGISTERS AS SCHEDULED. DEVICES
TO BE COMPLETE WITH DAMPERS FRAMES AND ALL ACCESSORIES. FINISH
AS INDICATED.
B. INSTALL ALL AIR DEVICES AS LOCATED ON THE ARCHITECTURAL REFLECTED
CEILING PLAN.
C. APPROVED MANUFACTURERS: TITUS IS SPECIFIED, EQUALS BY METALAIRE
OR KRUEGER IS ACCEPTABLE.
18. MEDIUM PRESSIIitE DUCT
A. WHERE DUCTWORK IS SPECIFICALLY NOTED AS MEDIUM PRESSURE. IT SHALL
BE CONSTRUCTED IN ACCORDANCE WITH SMACNA STANDARDS FOR A PRESSURE
RATING OF 3 INCES WATER COLUMN MINIMUM OR LARGER AS REQU IRED BY
LANDLORD.
B. ALL GAUGES AND RE I NFORCEiENT MUST MEET WITH THE LATEST EDITION
OF SMACNA STANDARDS FOR MED 1 UM PRESSURE DUCT AND WITH THE
LANDLORD'S CRITERIA.
C. ALL OTHER ITEMS FROM METAL DUCTWORK SPEC I F I CAT 1 ON SECTION APPLY
TO THIS SECTION
19. DUCTWORK INSULATION
A. INSTALL INSULATION PRODUCTS IN ACCORDANCE WITH MANUFACTURER'S
WRITTEN INSTRUCTIONS, AND IN ACCORDANCE WITH RECOGNIZED INDUSTRY
PRACTICES. INSULATION MUST COMPLY WITH NFPA ODA.
B. DUCT SIZES SHOWN ON DRAWINGS ARE INSIDE CLEAR DIMENSIONS.
INSULATE SUPPLY AND RETURN AIR RECTANGULAR DUCTWOW MERE SHOWN
ON PLAN. DUCTWORK SHALL BE INTERNALLY INSULATED WITH 1' THICK,
1 -1/2 I.B. DENSITY LINER (0-0.28 0 757). LINER IS TO HAVE A
COATED SURFACE EXPOSED TO AIRSTREAM TD PREVENT EROSION. APPLY
ADNES I VES AND MECHW I CA. FASTENERS AS RECOMMENDED BY SMACNA AND
THE MANUFACTURER TO PREVENT LINER SEPARATION FROM THE DUCT. ALL
TRANSVERSE EDGES TO BE COATED WITH ADHESIVE.
C. ALL ROUND AND OUTSIDE AIR DUCTWORK ABOVE THE CEILING SHALL BE
EXTERNALLY INSULATED WITH A MINIMUM OF 1'THICK. 1 -1/2 I.B. DENSITY
(R -5.6) DUCT WRAP WITH VAPOR BARRIER. VAPOR BARRIER IS TO BE
MAINTAINED THROUGHOUT DUCT SYSTEM. ALL JOINTS MUST BE TAPED SO
THAT ND INSULATION FIBER IS VISIBLE. EXTEND DUCTWORK INSULATION
WITHOUT i NTERRUPT I ON THROUGH WALLS, FLOORS, AND SIMILAR
PENETRATIONS.
D. ALL INSULATION SHALL HAVE A FLAME SPREAD RATING OF NDT MORE THAN
25 AND A SMOKE DEVELOPED RATING OF NO HIC ER THAT 50 WEN TESTED
IN ACCORDANCE WITH ASTM C 411. OR AS REQUIRED BY LOCAL CODES.
20. SYSTEM CLEAMOUT
A. DUCTWORK AND AIR HANDLING EQUIPMENT IS TO BE CLEWED OUT AND
BLOWN OUT BEFORE PAINTING IS STARTED BY TIE GENERAL CONTRACTOR.
B. FILTERS MUST BE IN UNITS AT ANY TIME FANS ARE OPERATED.
F. HHYDRONIC PIPING
1. PROVIDE A COMPLETE HYDRONIC PIPING SYSTEM IF APPLICABLE. REFER TO
PLANS TO DETERMINE IF A HYDRONIC SYSTEM IS REQUIRED.
2. PIPING
A. HYDRONIC PIPING FOR CHILLED WATER AND/OR HEATING WATER AND/Olt
CONDENSER WATER SHALL BE ASTM A-120, SCHEDULE 40, ERN, BLACK
STEEL PIPE WITH PLAIN ENDS. INSTALL STEEL PIPE WITH WELDED
JOINTS WHERE PIPE IS 2-1/2 INCH AND LARGER. INSTALL STEEL PIPE
WITH THREADED JOINTS AND FITTINGS OR INSTALL TYPE 'K' AMEALED
TEMPERED COPPER TUBE WITH SILFOS JOINTS FOR 2 INCH AND SMALLER
PIPE. PROVIDE DIELECTRIC UNIONS BETWEEN DISSIMILAR METHS. ALL
PIPING SHALL BE IN STRICT CONFORMANCE WITH ASTM, ASA, AND
LANDLORD'S REQUIREMENTS, WH I CEVER IS MOST STRINGENT. UNIONS OR
FLANGES MUST BE USED AT EQUIPMENT CONNECTIONS MERE SERVICE OR
REMOVAL MAY BE REQU I RED.
B. ALL PIPING AND EQUIPMENT SHALL BE PRESSURE TESTED WITHOUT LEAKAGE
AT A MINIMUM PRESSURE OF 125 PSI.
9 I 10 I 11
12 1 13
C. ALL HYDRONIC PIPING AND EQUIPMENT CONNECTED TO THE HVAC PIPING
SYSTEM SWILL BE CLEANED AND FLUSHED. REMOVE, CLEAN, AND REPLACE
STRAINER SCREENS. FILL TENANT'S SYSTEM WITH DOMESTIC MATER AND
VENT ALL PIPING AND EQUIPMENT PRIOR TO CONNECTION M THE
LANDLORD'S SYSTEM. CONTRACTOR SHALL NOT FILL TENANT'S SYSTEii
WITH WATER FROM THE LANDLORD'S SYSTEM UNLESS SPECIFICALLY
INSTRUCTED TO DO SO FROM THE LANDLORD'S FIELD REPRESENTATIVE.
D. PRIOR TO CONNECTION TO THE LANDLORD'S SYSTEM, CONTRACTOR SHALL
OBTAIN WRITTEN CONFIRMATION FROM THE LANDLORD'S FIELD
REPRESENTATIVE. THAT ALL TESTING, FLUSHING, AND PROPER FILLING
OF THE TENANT'S SYSTEM WAS BEEN COMPLETED IN ACCORDANCE TO THE
LANDLORD'S REQUIREMENTS AND THAT THE TENANT'S SYSTEM IS READY M
BE CONNECTED TO THE LANDLORD'S SYSTEM.
3. VALVES
A. GATE VALVES. 2-INCH AND SMALLER: CLASS 150. BODY AND UNION
BONNET OF ASTM B 62 CAST BRONZE WITH THREADED OR SOLDER ENDS.
INTEGRAL SEAT. RENEWABLE SOLID BRONZE WEDGE DISC. RISING STEM,
SCREWED ONO AND RE- PACKABLE UNDER PRESSURE. BALL VALVES ARE
ACCEPTED AS AN EQUAL SUBSTITUTION.
B. GATE VALVES, 2-1/2 INCH AND LARGER: CLASS 125 CAST IRON BODY.
RENEWABLE BRONZE SEATS AND SOLID WEDGE DISC, RISING STEM, FLANGED
ENDS. AND RE- PAIXABLE UNDER PRESSURE.
C. SWING CHECK VALVES. 2-INCH AND SMALLER: CLASS 150. CAST BRONZE
BODY AND CAP CONFORMING TO ASTM B 62 WITH HORIZONTAL SWING. Y-
PATTERN, RENEWABLE BRONZE DISC, AND HAVING THREADED OR SOLDERED
D.
ENDS. CHECK VALVE. 2-1/2 INCH AND LARGER: CLASS 125 CAST IRON
BODY AND BOLTED CAP, HORIZONTAL SWING, RENEWABLE BRONZE DISC,
FLANGED ENDS AND CAPABLE OF BEING REFITTED WHILE THE VALVE
REMAINS IN THE LINE.
E. COMBINATION BALANCING AND SHUT -OFF VALVES: BELL & GOSSETT
CIRCUIT SETTER WITH LOCKING SETPOINT. A CIRCUIT SETTER BALANCE
WHEEL MUST BE INCLUDED WITH 0 t M MANN..
F. FLOW METER: BELL AND GOSSETT TNERMCIFLO INDICATOR MODEL TFI.
4. PIPING SPECIALTIES
A. SSUR _
FITTINGS M RECEIVE EITHER A�TUR E C1t
PROBE 1/8
INCH O.D. FITTING AND CAPS SHALL BE BRASS WITH VALVE CORE OF
MOM. RATED AT 400 PSIG, 07 TO 2007.
B. STRAINERS - 'Y' PATTERN STRAINERS. 125 PSIG. CAST IRON BODY WITH
PERFORATED STAINLESS STEEL SCREEN, THREADED FOR 2 INCHES AND
SMALLER. FLANGED FOR 2-1/2 INCHES AND LARGER. SCREEN OPENING
SIZE AT 0.033 INCH FOR HEATING AND 1/8 INCH FOR CHILLED OR
CONDENSER WATER. PROVIDE WITH BLOWDOWN VALVE WITH HOSE END
FITTING.
C. THERMOMETERS - DIE CAST ALUMINUM, 9' INDUSTRIAL MERCURY
THERMOMETER. FULLY ADJUSTABLE WITH CLEAR ACRYLIC WIN= AND BRASS
SEPARABLE SOCKET.
D. MANUAL AIR VENTS - 1/8' COIN - OPERATED VENT. PROVIDE AN AIR
CHAMBER CONSISTING OF A 3/4' NIPPLE AND BUSHINGS.
5. GENERAL INSTALLATION
A. INSTALL WATER MAINS WITHOUT PITCH. USE ECCENTRIC REDUCING
COUPLINGS AT CHANGES IN SIZE WITH THE TOP OF PIPES AT SAME
ELEVATION. MAKE CHANGES IN DIRECTION WITH FITTINGS.
B. BRAKES TO UNITS BELOW MAINS TO BE TAKEN FROM BOTTOM OF MAINS
AT A 45 DEGREE ANGLE, PITCH DOWNWARD TOWARD UNITS. BRANCHES TO
UNITS ABOVE MAINS TO BE TAKEN FROM TOP OF MAINS AT A 45 DEGREE
ANGLE PITCHED UPWARD TOWARDS UNITS. PITCH NOT LESS THAN 1' TO
10 FEET.
C. HANGERS SHALL BE SIZED AND INSTALLED FOR THE OUTSIDE DIAMETER OF
THE INSULATED PIPE. INSTALL 6' LONG SPLIT CIRCLE GALVANIZED
SADDLE BETWEEN THE HANGER AND PIPE INSULATION.
D. HANGERS AND PIPING OF DISSIMILAR METALS SHALL BE DIELECTRICALLY
SEPARATE) FROM ONE MOTHER.
E. SEE PLANS FOR APPLICABLE DETAILS.
F. ALL PRESSURE PIPING SYSTEMS INSTALLED SHALL CONFORM TO THE
REQUIREMENTS OF THE STATE PIPING AND WELDING CODES.
G. INSTALL VALVES AT LOW POINTS FOR DRAINING EACH SYSTEM AND INSTALL
MANUAL VENTS AT ALL HIGH POINTS OF EQUIPMENT AND PIPING IN THE
SYSTEM TO PROPERLY REMOVE ENTRAPPED AIR.
6. INSULATION
A. ALL HYDRONIC PIPING FOR CHILLED WATER AND/OR HEATING WATER,
VALVES, FITTINGS, AND ACCESSORIES SWILL BE INSULATED. FOR PIPE
SIZES UP TO 2 INCHES. INSULATE WITH 1 INCH THICK (K-0.23 0 75 -F
FIBERGLASS INSULATION WITH ALL SERVICE JACKET AND VAPOR BARRIER.
FOR PIPE SIZES 2-1/2 INCHES AND LARGER, INSULATE WITH 1 -1/2 INCH
THICK (K-0.23 0 757) FIBERGLASS INSULATION WITH ALL SERVICE
JACKET AND VAPOR BARRIER.
B. INSULATION AT ALL HANGERS FOR PIPING 2-1/2 INCHES AND LARGER
SHALL BE HARD AND NON - COMPRESSIBLE.
C. ALL INSULATION SHALL HAVE A FLAME SPREAD RATING OF NOT MORE THAN
25 AND A SMOKE DEVELOPED RATING OF ND HIM" THAT 50 TO CONFORM
WITH THE REQUIREMENTS OF THE NFPA.
G. REFRIGERANT PIPING
1. PROVIDE A COMPLETE REFRIGERANT PIPING SYSTEM BETWEEN INDOOR FAN UNITS
AND WTDOOR CONDENSING UNITS, IF APPLICABLE. PROVIDE OIL, REFRIGERANT
CHARGE AND TEST SYSTEM. REFER TO PLANS TO DETERMINE IF A REFRIGERANT
PIPING SYSTEM IS REQUIRED.
2. MATERIALS
A. REFRIGERANT PIPING SHALL BE TYPE 'L' DRAWN COPPER TUBING ASTM
B58), WRCUMIT COPPER OR CAST BROKE FITTINGS (ANSI 816.22), WITH
SI SOLDERED JOINTS.
B. SERVICE VALVES, CHARGING PORTS. FILTER - DRIER. SIGN GLASS. AND
A THERMOSTATIC EXPANSION VALVE (TXV) SWILL. BE INSTALLED FOR EACH
SYSTEM AS A MINIMUM.
3. INSTALLATION
A. SIZE LINES WITH ADEQUATE LIFT TRAPS AND DOUBLE SUCTION RISERS AS
NECESSARY TO MEET THE NEEDS OF EQUIPMENT SPECIFIED, FIELD
CONDITIONS. AND EQUIPMENT MANUFACTURER'S RECOMMENDATIONS.
B. PRESSURE TEST FOR LEAKS WITH AN INERT GAS AT 250 PSIG. REDO
LEAKING JOINTS AND RETEST UNTIL SYSTEM IS TIGHT. EVACUATE GAS
AND CHARGE SY STEM. RE -TEST SYSTEM AND CHECK FOR LEAKS WITH
HALIDE LEAK DETECTOR. ALL LEAKING JOINTS MUST BE COMPLETELY RE-
DOE UNTIL ND LEAKS EXIST.
C. UPON COMPLETION OF TESTING, BUT BEFORE INSULATION IS APPLIED,
PIPING MUST BE INSPECTED BY A REPRESENTATIVE OF THE LOCAL
GOVEi N I NG AUTHORITY AS NECESSARY.
D. REFRIGERANT LINES SHALL BE INSULATED WITH 1 INCH THICK RUBATEX
OR ARMSTRONG REFRIGERANT PIPE INSULATION IN ACCORDANCE WITH
INDUSTRY STANDARDS.
H. SYSTEM TESTING. ADJUSTING, AND BALANCING
1. TESTING. ADJUSTING AND BALANCING OF ALL WORK SHALL BE MADE BY AN
INDEPENDEGT CONTRACTOR UNHD IS CURRENTLY LICENSED ASSOCIATED AIR
BALANCING COUNCIL (NBC ) OR NATIONAL ENVIRONMENTAL BALANCING BUREAU
(NAB) BALANCING CONTRACTOR. ND OTHER BALANCE REPORTS WILL BE
REVIEWED OR ACCEPTED. ALL BALANCING WORK MUST BE COMPLETE AND DONE
IN ACCORDANCE WITH THE MOST RECENT STANDARDS OF THEIR SOCIETY.
PAYMENT OF ALL COSTS FOR TEST INO SHALL BE MADE BY THE WAC CONTRACTOR.
2. THE WAG CONTRACTOR SWUM. INSTALL NEW FILTERS IN ALL UNITS PRIOR TO
THE AIR BALANCE. THE COMPLETE AIR BALANCE SHALL TAKE PLACE WITH
OUTSIDE AIR DAMPERS IN MINIMUM POSITION.
3. BAIJM AIR AND WATER QUANTITIES TO WITHIN + 5C OF THAT INDICATED ON
THE DRAWINGS. ANY REQUIRED CHANGES IN SHEAVES. BELTS, PULLEYS, OR THE
ADDITION OF DAMPERS REQUIRED TO ACHIEVE SPECIFIED FLOW RATES SHALL BE
PERFOBED BY THE HVAC CONTRACTOR WITH ND ADDITIONAL COST TO THE
TENANT.
4. THE BALANCE REPORT SHALL INCLUDE AS A MINIMUM THE FOLLOWING
INFORMATION:
A. AABC OR NEBB CERTIFICATION NUMBER AND SIGNATURE OF BALANCING
CONTRACTOR.
B. INSTRUMENTATION LIST WITH LAST CAI. I BRAT I ON DATES.
C. MAKE AND MODEL NUMBERS OF ALL WAC EQUIPMENT TESTED.
D. AIR C2M1 AND STATIC PRESSURE READINGS (DISCHARGE AND SUCTION) AS
MEASURED BY P I TOT TUBE DUCT TRAVERSE AT THE UNIT.
E. MOTOR NAMEPLATE DATA WITH ACTUAL FIELD VOLTAGE AND AMPERAGE
READINGS FOR EACH LEG.
F. MOTOR AND FAN RPMS, SHEAVE SIZES AND BELT SIZES.
G. OUTSIDE, RETURN, MIXED AND SUPPLY AIR TEMPERATURES AT FULL
COOLING.
H. WATER BALANCE DATA INCLUDING GPM WITH INLET AND OUTLET
I MATURE AND PRESSURE READINGS (WHERE APPLICABLE).
1. MAKE AND MOTEL NUMBERS OF ALL AIR D I STR I BUT I ON EQUIP".
J. FINAL BALANCED AIR VOLUMES AT ALL OUTLETS (INCLUDING RETURNS
MERE DUCTED).
K. INDEXED PLAN WITH DIFFUSER AND RETURN LOCATIONS.
5. ALL CONTROL SEQUENCES SHALL BE TESTED (I NTERLOOM EQUIPMENT. SMOKE
DETECTORS. SMOKE EVACUATION. ECONOMIZER, ETC.) AND OPERATING STATUS
RECORDED IN THE REPORT.
6. THREE COPIES OF THE BALANCE REPORT SWILL BE SUBMITTED THROUGH THE
GENERAL CQTTRACTOR TO THE TENANT'S COSTRUCT I ON MANAGER FOR APPROVAL.
7. THE BALANCING CONTRACTOR SHALL PERFORM ALL APPLICABLE TESTING AND
BALANCING FUNCTIONS REQUIRED FOR THE SYSTEM DESIGNED IN THESE
DRAWINGS. THE BALANCING CONTRACTOR SHALL RECHECK ANY ITEMS THAT THE
TENANT DEEMS NECESSARY AT ND ADDITIONAL COST TO THE TENANT.
8. FINAL BALANCE REPORT SHALL BE INCLUDED IN THE OPERATION k MA INTENANCE
MANUALS.
I. FINAL WAC INSPECTIONS
1. ASIDE FROM NORMAL INTERIM INSPECTIONS OF WORK IN PLACE, THE TENANT
SHALL HAVE THE RIGHT TO AN INDEPENDENT WAC CONTRACTOR INSPECT TIE
FINISHED WAC INSTALLATION UPON COMPLETION FOR COMPLIANCE WITH THE
PLANS, SPECIFICATIONS, AND CODES. THE INSTALLING CONTRACTOR WILL BE
RESPONSIBLE TO BRING ALL ITEMS REPORTED BY THE INDEPENDENT WAC
CONTRACTOR UP M PLANS AND SPECIFICATION REQUIREMENTS AT ND COST M
TENANT.
12 1 13
A- - - - -- --
14 I - 1 ; - = I; _;__ = T
. , .:3
:1*1. ., :
. 0.0 9 ..
0*0 "
M- Retail Engineering. Inc.
MPE Systems Engineering
750 Brooksedge Blvd.
Westerville, OH 43081
614.818.2323 Fax: 614.818.2337
eol den b u rgOm- corporation s. corn
`o x
"
.1 i
17
1524 Delancey Street
Phladelphia. PA 19102
www.sPg&00M
t. 215.735.1524
f. 215.735.4949
N
M
L
J9
J
H
G
F
E
f - _ .
��
,' �,
•lr;
1t
I. _ ,
-. : , "_ "
T . , . D
" � 1 92005
04.19.05 ISSUED FOR TENANT AND BUILDING DEPARTMENT N/A
REVIEW C
Date I Issue I Rev. No.
Up Against The Wall
Space No. A -10
The Shop at Sunset Place
Sout�� Miami, FL
Prof Na : 0504005
Mechanical °W
Spf ecifica tic n
a% 0 Ql:_D�' qD I
14 15 16 17
0
Vim!