05-893-003�N M I -K J H G F E 0 C 1 2 3 4 IVISION %00 — ACOUSTICAL CEILINGS PART I - GENERAL WORK INCLUDES: SUSPENDED ACOUSTICAL TILE CEILING SYSTEM AS ILLUSTRATED. STANDARDS: ASTM 0635, C636, E119 -76: UL LABORATORIES. PART II - MATERIALS SUSPENSION SYSTEM: CODE APPROVED METAL T-BAR SYSTEM - EXPOSED TEE OR FIRE GUARD GRID (AS REQUIRED BY LOCAL CODE) BY ARMSTRONG OR EQUAL COLOR: WHITE HANGER WIRE: ASTM A641, CLASS I, GALVANIZED, 10 GAUGE SOFT- ANNEALED STEEL WIRE COMPRESSION POSTS: ROBLIN BUILDING PRODUCTS SERIES CS, DONN CORP. CS SERIES, GALVANIZED STEEL, PERIMETER MOLDINGS: PROVIDE MOLDINGS WITH MATERIAL AND FINISH TO MATCH THE EXPOSED SUSPENSION COMPONENTS, ACCESSORIES: AS REQUIRED TO COMPLETE AND COMPLEMENT THE SYSTEM AND INSTALLATION OF LIGHTING AND "VAC. PART III - INSTALLATION GENERAL: FINISHED CEILINGS SHAD.. BE TRUE TO LINES AND LEVELS AND FREE FROM WARPED, SOILED OR DAMAGED GRID OR ACOUSTICAL UNITS, INSTALL AFTER MAJOR A50VE-CEILING WORK IS COMPLETE COORDINATE THE LOCATION OF HANGERS WITH OTHER WORK. ENSURE HANGERS AND CARRYING CHANNELS ARE LOCATED TO ACCOMMODATE FITTINGS AND UNITS OF EQUIPMENT WHICH ARE TO BE PLACED AFTER THE INSTALLATION OF CEILING GRID. WHERE DUCTS OR OTHER EQUIPMENT PREVENT THE REGULAR SPACING OF HANGERS, REINFORCE THE NEAREST ADJACENT HANGERS AND RELATED CARRYING CHANNELS AS REQUIRED TO SPAN THE REQUIRED DISTANCE. PROVIDE ADDITIONAL HANGERS AND INSERTS AS REQUIRED BY CODE FOR CEILING INSTALLATION. HANG INDEPENDENTLY OF WALLS, COLUMNS, DUCTS, PIPES AND CONDUIT. WHERE CARRYING MEMBERS ARE SPLICED, AVOID VISIBLE DISPLACEMENT OF THE LONGITUDINAL AXIS OR FACE PLANE OF ADJACENT MEMBERS, LIGHTING FIXTURES SHALL NOT BE INSTALLED SUCH THAT THE MAIN RUNNERS AND CROSS RUNNERS WILL BE ECCENTRICALLY LOADED, WHERE FIXTURE INSTALLATION WOULD PRODUCE ROTATION OF RUNNERS, PROVIDE STABIUZER BARS, INSTALL: UNITS LEVEL, IN UNIFORM PLANE AND FREE FROM TWIST, WARP AND DENTS, ADJUST ANY SAGS OR TWISTS WHICH DEVELOP IN THE CEILING SYSTEMS AND REPLACE ANY PART WHICH IS DAMAGED OR FAULTY, INSTALL EDGE MOLDINGS AT INTERSECTION OF CEILING AND VERTICAL SURFACES, USING MAXIMUM LENGTHS, STRAIGHT, TRUE TO LINE AND LEVEL, MITER CORNERS, PROVIDE EDGE MOLDINGS AT JUNCTIONS WITH OTHER CEIUNG FINISHES, Ml W.. 0_00 4 PART I - GENERAL WORK INCLUDES: STONE TILE AS ILLUSTRATED, STANDARDS: TILE COUNCIL OF AMERICA (TCA) - HANDBOOK FOR CERAMIC, TILE INSTALLATION, ANSI A108,5 - INSTALLATION OF CERAMIC TILE WITH DRY -SET PORTLAND CEMENT MORTAR OR LATEX- PORTLAND CEMENT MORTAR PART II - MATERIALS TILE: REFER TO FINISH SCHEDULE FOR TILE MORTAR: PORTLAND CEMENT MORTAR WITH LATEX ADDITIVE, ANSI AI18,4, ORGANIC ADHESIVES: AT VERTICAL APPLICATIONS, ANSI A136,1 TYPE I, INCLUDING PRIMER/SEALER AS RECOMMENDED BY MANUFACTURER, CLEAVAGE MEMBRANE POLYETHYLENE FILM, 4 MIL, NOMINAL THICKNESS, COMPLYING WITH ASTM CIA TYPE 1,1,2, REINFORCING MESH: WELDED WIRE FABRIC 2 INCHES X 2 INCHES 16/16 GAUGE, BOND COAT ADHESIVE: THINSET BOND COAT, CONSISTING OF LATEX CEMENTiTIOUS MORTAR CONFORMING TO ANSI AI18,4, MIX WITH LATICRETE 4237 ADDITIVE. GROUT RELEASE: CERAMASEAL SILOX 8 BY CERAMASEAL STONE 4 TILE CARE PRODUCTS, GROUT: WATER -PROOF CEMiENTITICUS TYPE, WITH LATEX ADDITIVE. LATICRETE 3701 CONFORMING TO ANSI A115A COLOR AS SCHEDULED AND IN CONFORMANCE WITH ARCHITECT- APPROVED SAMPLE, MAX WIDTH 1/8 INCH, WATER: CLEAN, POTABLE AND FREE OF DELETERIOUS SUBSTANCES, CLEANER: CERAMASEAL NEUTRAL CLEANER BY CERAMASEAL STONE 4 TILE CARE PRODUCTS, PART III - EXECUTION DO 1407 USE TILE AND TRIM WITH CHIPS, CRACKS, VOIDS, STAINS, OR OTHER DEFECTS WHICH MIGHT BE VISIBLE IN THE FINISHED WORK. COMPLETED INSTALLATION SHALL 13E FREE OF BROKEN, DAMAGED, OR FAULTY TILES, LAY ALL TILE UNITS IN PATTERN SHOWN ON DRAWINGS, WHERE THE PATTERN IS NOT N -loWN, AVOID USE OF UNIT LESS THAN HALF SIZE, UNLESS OTHERWISE NOTED, ALIGN UNIT SQUARE, PARALLEL AND STRAIGHT, WHEN CUTTING IS REQUIRED, GRIND EDGES SMOOTH, ACCURATELY CUT UNIT AROUND WORK OF OTHER TRADES SO THAT BRACKETS, ESCUTCHEONS, OR OTHER COVERINGS WILL COMPLETELY COVER TILE EDGES, FIRMLY EMBED ALL UNITS IN SETTING MATERIAL WITH FINISHED SURFACES BROUGHT TO TRUE PLANES, SET ALL TILES IN UNIFORM JOINT WIDTH, ALL JOINTS SHALL BE PLUMB AND LEVEL: ALIGN VERTICALLY AND HORIZONTALLY, AND ALL TILES TO FORM FLUSH PLANE WITH NO TWO CONTIGUOUS TILES OUT OF FLATNESS BY MORE THAN 1/32 INCH, INSTALL 9/6 EDGE ANGLES AGAINST ALL PERIMETER TILE EDGES WHERE TILE MEETS DISSIMILAR MATERIALS, SOUND TILE AFTER SETTING, REMOVE AND REPLACE HOLLOW SOUNDING UNITS, GROUT JOINTS, AS SOON AS POSSIBLE AFTER INITIAL SET OF SETTING BED, FORCE GROUT INTO JOINTS, STRIKE FUISHT, AND TOOL SLIGHTLY CONCAVE, WET JOINT SURFACES, IF DRY, PRIOR TO GROUTING, USE WHATEVER MEANS NECESSARY, WITHOUT BEING HARMFUL TO TILE WORK AND ADJACENT CONSTRUCTION, TO PREVENT GROUT COLOR FROM STAINING THE FACE OF TILES, PROVIDE PROPER TEMPERATURE AND HUMIDITY CONDITIONS FOR CURING. CLEANING: UPON COMPLETION OF PLACEMENT AND GROUTING, CLEAN ALL TILED SURFACES SO THAT THEY ARE FREE OF FOREIGN MATTER. PROHIBIT FOOT AND WHEEL TRAFFIC FROM USING TILED FLOORS FOR AT LEAST 7 DAYS AFTER GROUTING IS COMPLETED, PART I - GENERAL WORK INCLUDES: EXTENT OF RESILIENT FLOORING AND ACCESSORIES INCLUDING BASE AS OUTLINED ON DRAWINGS, SITE CONDITIONS: INSURE FLOOR SURFACES ARE SMOOTH AND FEAT WITH MAXIMUM VARIATION OF I/8 INCH IN 10 FEET, PREPARE FLOOR AS NECESSARY TO MEET THESE REQUIREMENTS, INSURE FLOORS ARE DRY (MAXIMUM 7 PERCENT MOISTURE CONTENT) AND EXHIBIT NEGATIVE ALKALINITY, CARBONIZATION OR DUSTING. MAINTAIN MINIMUM 70 DEGREES F AIR TEi'1PERATURE AT FLOORING INSTALLATION AREA FOR 3 DAYS PRIOR TO, DURING, AND FOR 24 (HOURS AFTER INSTALLATION, STORE FLOORING MATERIALS IN AREA OF APPLICATION. ALLOW 3 DAYS FOR MATERIAL TO REACH SAME TEMPERATURE AS AREA, INSTALL RESILIENT FLOORING AND ACCESSORIES AFTER OTHER FINISHING OPERATIONS, INCLUDING PAINTING, HAVE BEEN COMPLETED, PART II - MATERIALS VINYL: ARMSTRONG 1/6 INCH GA. 12 INCHES X 12 INCHES REFER TO "FINISH LEGEND" FOR SPECIFICATION. BASE: ARMSTRONG 4 INCH VINYL. COVE BASE REFER TO COLOR SCHEDULE FOR SPECIFICATION, PRIMERS AND ADHESIVES: WATERPROOF: OF TYPES RECOMMENDED BY RESILIENT FLOORING MANUFACTURER FOR SPECIFIC MATERIAL. LEVELING COMPOUND: LATEX TYPE AS RECOMMENDER BY FLOORING MANUFACTURER, PLYillOOD AS FILLER: 1/2 INCH EXTERIOR GRADE SEALER AND WAX: NON -SKID TYPE RECOMMENDED BY RESILIENT FLOORING MANUFACTURER FOR MATERIAL TYPE AND LOCATION, PART III - EXECUTION PREPARATION: REMOVE SUB-FLOOR RIDGES AND BUMPS, USE LEVELING COMPOUND AS RECOi'1MENDED BY FLOORING MANUFACTURER FOR FILLING SMALL CRACKS AND DEPRESSIONS IN SUB - FLOOR, CLEAN FLOOR AND LAG PLYWOOD FILLER IN ADHESIVE TO LEAVE SMOOTH, FLAT, HARD SURFACE, PROH11331T TRAFFIC UNTIL ADHESIVE IS CURED, APPLY CONCRETE SLAB PRIMER, IF RECOMMENDED BY FLOORING MANUFACTURER, PRIOR TO APPLICATION OF ADHESIVE. APPLY IN COMPLIANCE WITH MANUFACTURER'S DIRECTIONS, INSTALLATION: INSTALL FLOORING USING METHOD INDICATED IN STRICT COMPLIANCE WITH MANUFACTURER'S RECOMMENDATIONS, EXTEND TILE INTO TOE SPACES, DOOR REVEALS AND INTO CLOSETS AND SIMILAR OPENINGS, SCRIBE FLOORING To WALLS, COLUMNS, CABINETS, FLOOR OUTLETS AND OTHER APPURTENANCES, To PRODUCE TIGHT JOINTS, APPLY WALL BASE TO WALLS, COLUMNS, PILASTERS, SCHEDULED CASEWORK AND OTHER PERMANENT FIXTURES IN ROOMS WHERE BASE IS REQUIRED. INSTALL BASE IN LENGTHS AS LONG AS PRACTICAL, TiGHTLY BOND BASE To SUBSTRATE THROUGHOUT LENGTH OF EACH PIECE WITH CONTINUOUS CONTACT AT HORIZONTAL AND VERTICAL SURFACES. RUN TILE GRAIN IN ONE DIRECTION, CLEAN UP AND PROTECTION: REMOVE EXCESS ADHESIVE FROM FLOOR, BASE AND WALL SURFACES WITHOUT CAUSING DAMAGE. CLEAN, SEAL AND WAX FLOOR AND BASE SURFACES IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS, PROHIBIT TRAFFIC FROM FINISHED FLOOR FOR 48 HOURS AFTER INSTALLATION, PROTECT COMPLETED WORK WITH NON - STAINING BUILDING PAPER UNTIL FINAL ACCEPTANCE OF WORK, DIVISION %80 - CARPETING PART 1 - GENERAL, WORK INCLUDES: TACKLESS INSTALLATION OF CARPET. EXTENT OF CARPET AND ACCESSORIES IS SHOWN ON DRAWINGS, PROJECT CONDITIONS: DO NOT INSTALL CARPET UNTIL DIET CONSTRUCTION IS COMPLETED AND SURROUNDING AIR HAS MAXIMUM MOISTURE CONTENT OF 40 PERCENT, PROVIDE PERMANENT HEAT, LIGHT AND VENTILATION PRIOR TO INSTALLATION, MAINTAIN ROOM TEMPERATURE AT A MINIMUM OF 65 DEGREES F FOR A PERIOD OF 7 DAYS PRIOR TO THE DELIVERY OF MATERIALS, DELIVERY AND STORAGE: DO NOT DELIVER MATERIALS UNTIL SITE CONDITIONS ARE ADEQUATE TO RECEIVE WORK, PROTECT FROM WEATHER WHILE IN TRANSIT, AND AGAINST MOISTURE AND ABRASION AFTER DELIVERY, PART 11 - MATERIALS CARPET: BY OWNER. REFER TO FINISH SCHEDULE TACKLE% STRIPPING: STANDARD SEAM SEALER., ORCON "CT -3" TAPE, ROBERT COMPANY "GOLDEN TOUCH ", L.D. BRINKMAN +55 "SUPREME OR COMPATABLE MATERIAL DIRECTED BY CARPET MANUFACTURER, PART III - EXECUTION PREPARATION: CLEAN FLOORS OF DUST, DIRT, SOLVENTS, OIL, GRE45E, PAINT, PLASTER AND OTHER SUBSTANCES DETRIMENTAL TO PROPER PERFORMANCE OF ADHESIVE AND CARPET, ALLOW FLOORS TO THOROUGHLY DRY, INSURE CONCRETE FLOORS ARE FREE FROM SCALING AND IRREGULARITIES AND DWIBIT NEUTRALITY RELATIVE TO ACIDITY AND ALKALINITY, USE AN APPROViD CE I- IENTMOUS FILLER TO PATCH CRACKS AND SMALL HOLES, AND FOR LEVELING. INSURE FLOORS ARE LEVEL WITH MAXIMUM SURFACE VARIATION OF 1/8 INCH IN 10 FEET, NONCUMULATIVE. COMMENCEMENT OF CARPET INSTALLATION SHALL SIGNIFY ACCEPTANCE OF SATISFACTORY CONDITIONS, INSTALLATION A Architectural Specifications 2 GENERAL: THE CONTRACTOR SHALL SCHEDULE THE WORK SO THAT A MINIMUM OF PAINTING WILL OCCUR OVER LAID CARPET AND ASSURE THAT THE CARPET IS PROTECTED FROM DAMAGE FROM ANY SOURCE. UNLESS OTHERWISE DIRECTED BY THE OWNER OR THE G.C., THE CARPET SUBCONTRACTOR SHALL BE RESPONSIBLE FOR THE REMOVAL OF ALL INTERIOR DOORS, STACKING NO MORE THAN 4 TOGETHER WITH PROTECTIVE SPACERS BEIWEETI, AND REHANCsFNs, CHECK MATCHING OF CARPET BEFORE CUTTING AND INSURE THERE IS NO VISIBLE VARIATION BETWEEN DYE LOTS. CUT CARPET WHERE REQUIRED, IN A MANNER TO ALLOW PROPER SEAM AND PATTERN MATCH, INSURE CUTS ARE STRAIGHT AND TRUE AND UNFRAYED. CUT CARPET FROM FACE ONLY BETWEEN ROWS UAT14 ADJUSTABLE LOOP PILE CUTTER. SEAL ALL CUT EDGES WITH BEAD OF SEAM SEALER NOTED ABOVE, ALLOW TO DRY PRIOR TO SEAMING, INSTALLATION: ALL CARPET SHAD- BE LAID IN THE SAME DIRECTION UNLESS SPECIFICALLY SHOWN OTHERWISE NO SEAMS SHALL OCCUR PERPENDICULAR TO DOORS OR ENTRIES, SEAMS OCCURRING PARALLEL TO DOORS SNAIL BE CENiiRED DIRECTLY UNDER THE DOOR, SEAMS OCCURRING AT CORRIDOR CHANGE OF DIRECTION SHALL FOLLOW WALL LINE PARALLEL TO CARPET DIRECTION. LOCATE SEAMS IN ACCORDANCE WITH APPROVED LAYOUT AND SEAMING PLANS, TRIM EDGES AND HEAT SEAM, USING MATERIALS AND METHODS RECOMMENDED BY CARPET MANUFACTURER AND IN ACCORDANCE WITH MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS. INSURE SEAMS ARE STRAIGHT, NOT OVERLAPPED OR PEAKED, AND IRE, PROM GAPS. VACUUM CLEAN SUBSTRATE. CUT AND FIT CARPET NEATLY AROUND PROJECTIONS THROUGH FLOOR, AND TO WALLS AND OTHER VERTICAL SURFACES, THE FINISHED INSTALLATION SHALL BE TREE FROM TACKS, SCRAPS, CARPET RIPPLES, SCALLOPS, PUCKERS, SPROUTS AND OTHER DEFECTS. CLEAN UP 4 PROTECTION: AFTER INSTALLATION IS COMPLETE, CLEAN UP ALL DIRT AND DEBRIS AND CLEAN ALL SPOTS WITH PROPER SPOT REMOVER REMOVE ALL LOOSE THREADS AND VACUUM, THE OWNER SHALL REVIEW ALL CARPET SCRAPS AND RETAIN ANY IT CHOOSES FOR FUTURE REPAIRS, SECTION 97000- CEMENTITIOUS DECKS AND TOPPINGS (ARDEX) PART I: GENERAL A. Summary I, Section includes: a. Self - leveling cementAtious underlayment. B, Qualifications 1, Installation of the cement - based, self - leveling underlayment must be by an applicator using mixing equipment and tools approved by the manufacturer. 2, Provide adex K -15 self - leveling underlayment concrete as manufactured by Ardex, Inc,, 630 Stoops Ferry Road Corapolis, PA 15108, 3, Underlayment shall be walkable after two hours at 70° F and be able to be covered by flooring material In 16 hours. C. Submittals I. Product Data: a. Materials list of Items proposed to be provided under the section. D. Dellver, Storage, and Handling I. Dellver materials in their original, unopened packages and protect from freezing, direct sun exposure, an exposure to moisture. PART 2: PRODUCTS A, Materials I, Primer for standard absorbent concrete shall be Ardex P -51 primer, 2, Primer for non - porous substrate, cut -back adhesive residue, and metal and wooden subfloora shall be Ardex P -82 ultra- prime. 3, The additive to be mixed with Ardex K -15 when used over cut -back adhesive, metal or wooden subfloors shall be Ardex E -25 resilient emulsion, 4, Aggregate shall be well - graded, washed pea gravel (1/8" to 1/4" or larger) for use when underlayment Is Installed over 1 -1/2" thick, 5, Water shall be clean, potable, and sufficientiy cool Mot warmer than 70' F), B, Technical Data. all data Is based on a mixing ratio of 3,5 P.B.V, of powder to I P.B,v, of water, 1. Flowing Time: approximately 10 minutes at 70° F 2, Initial Set, ASTM C191: approximately 30 minutes at 70° F 3, Final Set, ASTM CI91: approximately 2 hours at 70" F 4, Compressive Strength, ASTM C- 109/MOD: approximately 4,100 PSI after 48 days 5, Flammability, ASTM E- 84 -81A: a, Flame Spread: 0, b, Fuel Contribution: O. c, Smoke Development: O, 6, Coverage, 551b, bag: a. Approximateiy 60 S,F, at 1/8" b, Approximateiy 30 S,F, at 1/4" PART 3: EXECUTION A. Preparation I, In addition to the general procedures described herein, refer to manufacturer's current published product literature for complete installation details for the underlayment system being Installed, 2, All surfaces regardless of material, must be solid, thoroughly cleaned of all deletrious material Including loose agcIre- , particulate and grease, and dried of any surface moisture. B, Priming I. Primer for standard absorbent concrete subfloors, a, Prime with Ardex P -51 Primer, underlayment shall not be applied until primer Is dry. C. Installation I. Installation to be done by installer certifled by the manufacturer, using mixing and installation methods as specifled by the manufacturer. I8 I 9 I 10 I DIVISION 9900 - PAINTING PART I - GENERAL WORK INCLUDES: EXTENT OF PAINTING AND FINISHING INCLUDES (BUT IS NOT LIMITED TO) WORK AS SHOWN ON DRAWINGS AND SCHEDULES AND AS HEREIN SPECIFIED, PAINTING ALL GYPSUM DRYWALL EXPOSED TO VIEW, INCIDENTAL PAINTING AND TOUCHING UP AS REQUIRED TO PRODUCE PROPER FINISH FOR ALL PAINTED SURFACES, INCLUDING TOUCHING UP OF FACTORY FINISHED ITEMS. PAINTING OF ANY SURFACE, NEW OR EXISTING, NOT SPECIFICALLY MENTIONED TO BE PAINTED HEREIN OR ON DRAWINGS BUT FOR WHICH PAINTING IS OBVIOUSLY NECESSARY TO COMPLETE THE JOB, DEFINITION: PAINT, AS HEREIN USED, MEANS ALL COATING SYSTEM MATERIALS INCLUDING PRIMERS, EMULSIONS, ENAMELS, STAINS, SEALERS AND FILLERS AND OTHER APPLIED MATERIALS WHETHER USED AS PRIME, INTERMEDIATE OR FINISH COATS, WORK NOT INCLUDED: THE FOLLOWING CATEGORIES OF WORK ARE NOT INCLUDED AS PART OF FIELD APPLIED FINISH WORK UNLESS OTHERWISE INDICATED: I, WALLS AND CEILINGS IN CONCEALED AND INACCESSIBLE AREAS, 11 FINISHED METALS SUCH AS ANODIZED ALUMINUM, STAINLESS STEEL, CHROME PLATE, BRONZE AND SIMILAR FINISHED MATERIALS, 3, DO NOT PAINT OVER ANY CODE REQUIRED LABELS, SUCH AS UNDERWRITERS LABORATORIES AND FACTORY MUTUAL OR ANY EQUIPMENT IDENTIFICATION PERFORMANCE RATING, NAME OR NOMENCIATLI RE PLATES, 4. MOVING PARTS OF OPERATING UNITS, JOB CONDITION: APPLY WATER -BASE PAINTS ONLY WHEN TEMPERATURE OF SURFACES TO BE PAINTED AND SURROUNDING AIR TEMPERATURE ARE BETWEEN 45 DEGREES F (7 DEGREES C) AND % DEGREES F (35 DEGREES C), UNLESS OTHERWISE PERMITTED BY PAINT MANUFACTURER'S PRINTED INSTRUCTIONS, PART II - MATERIALS MANUFACTURER: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE BEST QUALITY PRODUCTS OF THE SHERWIN WILLIAMS CO, SHERWIN WILLIAMS ARCHITECTURAL DEPARTMENT 1- 800 - 321.8194 PART III - EXECUTION INSPECTION: EXAMiINE AREAS AND CONDITIONS UNDER WHICH PAINTING WORK IS TO BE APPLIED AND NOTIFY CONTRACTOR IN WRITING OF CONDITIONS DETRIMENTAL TO PROPER AND TIMELY COMPLETION OF WORK. STARTING OF PAINTING WORK WALL BE CONSTRUED AS APPLICATOR'S ACCEPTANCE OF SURFACES AND CONDITIONS WITHIN ANY PARTICULAR AREA, SURFACE PREPARATION: REMOVE HARDWARE, HARDWARE ACCESSORIES, MACHINED SURFACES, PLATES, LIGHTING FIXTURES AND SIMILAR ITEMS M PLACE AND NOT TO BE FINISH- PAINTED, OR PROVIDE SURFACE - APPLIED PROTECTION PRIOR TO SURFACE PREPARATION AND PAINTING OPERATIONS. FOLLOWING COMPLETION OF PAINTING OF EACH SPACE OR AREA REINSTALL REMOVED ITEMS, APPLICATION GENERAL: APPLY PAINT IN ACCORDANCE WITH MANUFACTURER'S DIRECTIONS, USE APPLICATORS AND TECHNIQUES 13EST SUITED FOR SUBSTRATE AND TYPE OF MATERIAL BEING APPLIED. APPLY ADDITIONAL COATS WHEN UNDERCOATS, STAINS OR OTHER CONDITIONS SHOW THROUGH FINAL COAT OF PAINT, UNTIL PAINT FILM IS OF UNIFORM FINISH, COLOR AND APPEARANCE GIVE SPECIAL ATTENTION TO INSURE THAT SURFACES, INCLUDING EDGES, CORNERS, CREVICES, WELDS AND EXPOSED FASTENERS RECEIVE A DRY FILM THICKNESS EQUIVALENT TO THAT OF FLAT SURFACES, PRIME, STAIN, OR SEAS_ WOOD REQUIRED TO BE JOB PAINTED IMMEDIATELY WON DELIVERY TO JOB, PRIME EDGES, ENDS, FACETS, UNDERSIDES AND BACKSIDES OF SUCH WOOD, INCLUDING CABINETS, COUNTERS, CASES, PANELING, PAINT SURFACES BEHIND MOVABLE EQUIPMENT AND FURNITURE SAME AS SIMILAR EXPOSED SURFACES, PAINT SURFACES BEHIND PERMANIENTLY -FIXED EQUIPMENT OR FURNITURE WITH PRIME COAT ONLY BEFORE FINAL INSTALLATION OF EQUIPMENT, PAINT INTERIOR SURFACES OF DUCTS, WHERE VISIBLE THROUGH REGISTERS OR GRILLES, WITH A FLAT, NON- SPECULAR BLACK PAINT. PAINT BACK SIDES OF ACCESS PANELS, AND REMOVABLE HINGED COVERS TO MATCH EXPOSED SURFACES, CLEAN-UP: DURING PROGRESS OF WORK, REMOVE FROM SITE DISCARDED PAINT MATERIALS, RUBBISH, CANS AND RAGS AT END OF EACH WORK DAY. UPON COMPLETION OF PAINTING WORK CLEAN WINDOW GLASS AND OTHER PAINT - SPLATTERED SURFACES, REMOVE SPLATTERED PAINT BY PROPER METHODS OF WASHING AND SCRAPING, USING CARE NOT TO SCRATCH OR OTHERWISE DAMAGE FINISHED SURFACES, AT COMPLETION OF WORK OF OTHER TRADES, TOUGH -UP AND RESTORE ALL DAMAGED OR DEFACED PAINTED SURFACES, UPON COMPLETION OF THE WORK, REMOVE SURPLUS MATERIALS, EMPTY PACKAGES AND CONTAINERS AND DEBRIS FROM THE SITE AND DISPOSE BY LEGAL MEANS, PROTECTION: PROTECT WORK OF OTHER TRADES, WHETHER TO BE PAINTED OR NOT, AGAINST DAMAGE BY PAINTING AND FINISHING WORK, CORRECT ANY DAMAGE BY CLEANING, REPAIRING OR REPLACING, AND REPAINTING AS ACCEPTABLE TO THE ARCHITECT. PAINT SCHEDULE REA=R TO FINISH SCHEDULE FOR COLOR GYPSUM DRYWALL SURFACES: SALES AREA-WALLS IST COAT- CUICK DRY PRIME SEAL COLOR 2ND COAT - WALL SATIN FLAT COLOR 3RD COAT - WALL SATIN FLAT SAI E5 AREA - WOODWORK AND DOORS IST COAT - ALKYD ENAMEL. UNDERBODY COLOR 2ND COAT - SEMI-GLOSS COLOR 3RD COAT - SEMI -GLOSS SALES AREA - HALLWAYS IST COAT - QUICK DRY PRIME SEAL COLOR 2ND COAT - EGGSHELL COLOR 3RD COAT - EGGSHELL STOCK AREA -WALLS IST COAT - QUICK DRY PRIME SEAL_ COLOR 2ND COAT - WALL SATIN COLOR 3RD COAT - WALL SATIN FLAT STOCK ,AREA - WOODWORK AND DOORS IST COAT - ALKYD ENAMEL UNDERBODY COLOR 2ND COAT - SEMI -GLOSS COLOR 3RD COAT - SEMI-GLOSS HOLLOW METAL DOORS 4 FRAMES- EXTERIOR LOCATIONS: IST COAT - RUST INHIBITOR COLOR 2ND COAT - SE MI -GWSS COLOR 3RD COAT - SEMI-GLO% INTERIOR LOCATIONS: • COLOR FOR SALES AND STOCK IST COAT - WHITE PRIMER 2ND COAT - SEMI -GLOSS 3RD COAT - SEMI -GLOSS 11 12 13 14 DIVISION 9950 - WALL COVERNGS PART I - GENERAL WORK INCLUDES: VINYL COATED AND FABRIC WALLCOVERINGS AS ILLUSTRATED. QUALITY ASSURANCE: USE ONLY SUBCONTRACTORS EXPERIENCED WITH THE INSTALLATION OF SIMILAR MATERIALS, FIRE HAZARD CLASSIFICATION: PROVIDE MATERIALS BEARING UL LABEL AND MARKING, INDICATING FIRE HAZARD CLASSIFICATION OF WALL COVERING, AS DETERMINED BY ASTI1 E 84, PROVIDE MATERIALS WITH THE FOLLOWING FIRE HAZARD CLASSIFICATIONS: FLAME SPREAD NOT MORE THAN 25, SMOKE DEVELOPED NOT MORE THAN 50, PART II - PRODUCTS VINYL WALL COVERING: REFER TO FINISH SCHEDULE MEDIUM DUTY: TYPE II: TOTAL WEIGHT NOT LESS THAN 13 OZ, PER SQUARE YARD, VINYL COATING NOT LESS THAN 7 OZ, PER 50, YD, SEE FINISH SCHEDULE FOR MANUFACTURER AND COLOR. ADHESIVES: PROVIDE MANUFACTURER'S RECOMMENDED ADHESIVE, PRIMER AND SEALER, PRODUCED EXPRESSLY FOR USE WITH SELECTED WALL COVERING ON SUt36TRATE AS SHOIIM ON DRAWINGS, PROVIDE MATERIALS WHICH AIRE MILLDIEW- RESISTANT AND NON-STAINING TO WALL COVERING, RELEASE COAT: OIL BASE SEALER OR ENAMEL UNDERCOATER FOR VIRGIN DRYWALL SUBSTRATES AS RECOMMENDED BY COVERING MANUFACTURER, PART III - EXECUTION PREPARATION: ACCLIMATIZE WALL COVERING MATERIALS BY REMOVING FROM PACKAGING IN AREA OF INSTALLATION NOT LESS THAN 24 HOURS BEFORE APPLICATION, REMOVE SWITCH PLATES, WALL PLATES AND SURFACE- MOUNTED FIXTURES IN AREAS WHERE WALL COVERING IS TO BE APPLIED, PRIME AND SEAL SUBSTRATES IN ACCORDANCE WITH WALL COVERINGS MANUFACTURER'S RECOMMENDATIONS FOR TYPE OF SUBSTRATE APPLY SURFACE SEALER TO GYPSUM DRYWALL WHICH WILL PERMIT SUBSEQUENT REMOVAL OF WALL COVERING WITHOUT DAMAGE TO PAPER FACING, INSTALLATION: ILLUMINATE AREAS OF INSTALLATION USING BUILDING'S PERMANENT LIGHTING SYSTEM: TEMPORARY LIGHTING ALONE WILL NOT BE ACCEPTABLE PLACE WALL COVERING PANELS CONSECUTIVELY IN ORDER CUT FROM ROLLS, INCLUDING FILLING OF SPACES ABOVE OR BELOW OPENINGS, HANG BY REVERSING ALTERNATE STRIPS EXCEPT ON MATCH PATTERNS APPLY ADHESIVE TO BACK OF WALL COVERING AND PLACE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS, INSTALL SEAMS PLUMB, AND AT LEAST 6 INCHES AWAY FROM CORNERS, HORIZONTAL SEAMS ARE NOT PERMITTED, OVERLAP SEAMS AND DOUBLE-CUT TO ASSURE TIGHT CLOSURE ROLL, BRUSH, OR USE BROAD KNIFE TO REMOVE AIR BUBBLES, WRINKLES, BUSTERS AND OTHER DEFECTS, CUT WALL COVERING EVENLY TO EDGES OF WALL PENETRATIONS, TRIM SALVAGES AS REQUIRED TO ASSURE COLOR UNIFORMITY AND PATTERN MATCH, REMOVE EXCESS ADHESIVE ALONG FINISHED SEAMS WHILE IT IS STILL WET USING WARM WATER AND CLEAN SPONGE, AND WiPE DRY, REPLACE REMOVED PLATES AND FIXTURES: VERIFY CUT EDGES OF WALL COVERINGS ARE COMPLETELY CONCEALED, REMOVE SURPLUS MATERIALS, RUBBISH, AND DEBRIS RESULTING FROM WALL COVERING INSTALLATION UPON COMPLETION of WORK, AND LEAVE AREAS OF INSTALLATION IN NEAT, CLEAN CONDITION, DIVISION 9975 - NON -SKID TILE TREATMENT PARTI - GENERAL WORK INCLUDES: INSTALLATION OF A NON- SKID SAFETY FINISH ON ALL TILE FLOOR SURFACES. QUALITY ASSURANCE: USE ONLY SUBCONTRACTORS EXPERIENCED WITH THE INSTALLATION OF SIMILAR MATERIALS. FIRE HAZARD CLASSIFICATION: PROVIDE MATERIALS BEARING UL LABEL AND MARKING, INDICATING FIRE HAZARD, PART II - PRODUCTS "NO- SLIP" TREATMENT SLIP RESISTANT FINISH, INSTALLED PER MFGR. INSTRUCTIONS. PRODUCT AS SUPPLIED BY 051 HARD SURFACES, 6 KENVIE W BLVD., BRAMPTON, ONTARIO, CANADA L&T 5E4 PHONE 905 - 7934930 CONTACT: WENDY O'BRIEN M-ReWI Englneedng, Inc. WE System Enptneeiino o= 760 OmdMdfle INV& weetenAde, OH 43061 6142182923 Fox 614.818.2337 04,19,05 ISSUED FOR TENANT AND BUILDING DEPARTMENT REVIEW Date Issue 17 1524 Delancey Street Philadelphia, PA 19102 www.spg3.com t. 215.735.1524 f. 215.735.4949 ,..,, .._.. Rev. No. Up Against The Wall Space No. A -10 The Shops at Sunset Place South Miami, FL •ti. „._ A k6;+1ft0,} I Proj. No.: 5016.00 r, 3 4 5 6 7 8 9 10 11 12 13 14 15 N M L J H C 19 E 0 C [to Ulm Specifications QAoQJJQ�Jd A G: 16 1 17