SPECIFICATIONS
6ENERAL INFORMATION
A. 6ENERAL
1. CONFORM TO ALL 6EERAL AND SPECIAL CONDITIONS OF CONTRACT AS
SPECIFIED BY ARCHITECT, EN6IMOZ AND OWNER.
2. SPECIFICATIONS ARE APPLICABLE TO ALL CONTRACTORS AND
SUBCONTRACTORS FOR MECHANICAL AND E_EGTRIGAL SYSTEMS.
3. CONTRACTOR SHALL 13E FAMILIAR WITH OWN(ER'S STANDARDS, RULES
AND R56UL.ATIONS. ALL OWNER'S CRITERIA SHALL BE COMPLIED
WITH AND INGL.UDtED IN THIS BID. CHECK OTHER PLANS AND
5PEGIFIGATION5 AND FULLY COORDINATE WITH OTHER TRADE5 AND
ARCHITECT'S FEQIIREBNTS.
4. VISIT SITE, CHECK FACILITIES AND CONDITIONS, AND VERIFY ALL
UTILITY COMPANY fFMIRIEEN75 AND CONNECTION POINTS IN FIELD
PRIOR TO STARTIN6 WORK. TAKE ALL ITEMS INTO CONSIDERATION
IN BID.
5. SY5TEM5 ARE TO BE COMPLETE AND WORKABLE IN ALL RE517MTS,
PLACED IN OPERATION AND PROPERLY ADJUSTED.
6. EACH CONTRACTOR SHALL PROVIDE FOR HIS OWN GLEAN -UP, R@1OVAL
AND LE6AL DISPOSAL OF ALL RUBBISH DAILY.
7. ARRAN6E FOR AND OBTAIN OWNER'S AND INSURANCE
REPRESENTATIVE'S PERMISSION FOR ANY SERVICE SHUTDOWN5.
SHUTDOWNS MUST BE PERFORMED WITHOUT DISRUPTION TO FACILITY
OPERATIONS, AS SCHEDULED WITH THE OWNER. INCLUDE ANY
PREMIUM TIME REQUIRED IN BID.
8. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR CONSTRUCTION
MFJIDS, METHODS, SEQ)ENCE5 OF CONSTRUCTION AND THE SAFETY OF
WORKMEN. COMPLY WITH ALL OSHA R156ULATIONS.
4. NO PIPING, DUGTWOR1(, CONTROLS, ETC,., SHALL BE INSTALLED OR
ROUTED ABOVE ELECTRICAL PANEL5 AND EGIU I FMENT OR T} RO"
ELEVATOR ROOMS OR SHAFTS.
10. THE MMEGHAIIGAL AND EL.EGTRIGAL CONTRACTORS 5HHALL COORDINATE
THE ELECTRICAL CHARACTE3RISTICS OF ALL MECHANICAL EQUIPMENT
PRIOR TO ORDERIN6 OF EQUIPMENT. NO ADDITIONAL PAYMENT WILL
BE MADE FOR LACK OF CgNTRAGTOR COORDINATION OF ELECTRICAL
CHHARACTERISTICS.
11. OBTAIN, BECOME FAMILIAR WITH, AND COMPLY WITH ALL FACILITY
SPECIFICATIONS.
12. ALL MECHANICAL AND ELECTRICAL SYSTEM COMPONENTS SHALL BE
ROUTED T16HT TO UNDERSIDE OF 5TRUG7URE AND THNROU6H JOISTS OR
TRUSSES WHERE POSSIBLE. COORDINATE INSTALLATION TO PROVE
HEADROOM, EOIUIPMENr ACCESS, AND ARCHITECTURAL GLEARANGE5 FOR
FINISHES, INGLUDINN5 CEILINN6 HEI6HT'S. COORDINATE WITH ALL
OTHER TRADES AND DO NOT CONFLICT WITH THE ARCHITECTURAL..
REQUUIMMENT5 FOR THE FINISHED CONSTRUCTION. PROVIDE OFFSETS
WHERE REQUIRED TO COORDINATE WITH OTHER TRADES.
13. TO ARCHITECTURAL REFLECTED CEILING PLAN5 FOR LOGATION5
OF ALL 6RI LLE5 AND DIFFUSERS.
B. CODES, STANDARDS AND MS ULATION5
I . CONFORM TO ALL APPLICABLE COPIES, 6OVERNMENT RE6ULATION5,
UTILITY COMPANY REQUIREENT5, AND NATIONAL ELECTRICAL CODE.
2. OBTAIN PERMITS AND PAY ALL FMS. ARRANGE FOR ALL REQUIRED
I145PECTION5 AND APPROVALS.
G. RELATED WORK SPECIFIED ELSEWHERE
I. OFMIN65 AND CHASES, WHEN SHOWN ON ARCHITECTURAL DRAWIN65.
D. PRANIN65
I. THE SYSTEMS AS SHOWN ON THE CONTRACT DRAWIN6S ART=
DIA6RAMMATIG.
2. THE INTENT IS FOR COMPLETE AND WORKABLE SYSTEMS. THE
MMIN65 AND THEE NOTES ARE TO BE USED T06ETHMER AS A BASIS
OF S IOW1N6 AND /OR DESGRIBIN6 THE SYSTEM MGVIR1 =MENTS FOR THE
FACILITY.
3. VERIFY ALL DIMENSIONS AND CLEARANCES BY FIELD MFA5l1RlEMENr
AND CHECK FOR INS PRIOR TO STARTIN6 WORK.
E. DEMOLITION AND REMOVAL
I. CONTRACTOR SHALL VISIT SITE PRIOR TO SUBMITTIN6 BID AND BE
FAMILIAR WITH ALL DEMOLITION WORK.
2. MECHANICAL CO MV_7, OR SHALL- DISCONNECT, DISA56EELE, AND
REMOVE EXISTIN6 EQUIPMENT, A55XIATO DUCTWORK, DIFFUSERS,
6RILLIES, SUPPORTS, PIPING AND ASSXIATED CONTROLS, ETC., NOT
OTHERWISE INDICATED TO BE M50 ON DRAWIN65. ALL OPENIN65
ON PIPING AND DUCTS THAT REMAIN SHALL BE GAPPED /PLU66ID AND
PROPER -Y SECURED.
3. ALL ABANDONED aEGTRICAL DEVICES, WIRING, CONDUIT, ETC.,
SEW_ BE REMOVED. WIRINN6 SHALL BE DISCONNECTED AT CIRCUIT
BREAKERS AND REMOVED AND BREAKERS MARKED 'SPARE.
4. ANY EQU I PMEJT DE5I6NATED BY CANNER TO BE SALVA6ED SHALL BE
PFMMTED AND DELIVERED TO THE OWNER ON SITE, OSTHE3KI5E,
CONTRACTOR SHALL DISPOSE OF L66ALLY AS DIRECTED BY OWNER.
5. DEMOLITION TO BE DONE IN A MANNER 50 AS NOT TO DAUA6E
ADJACENT WORK AND NOT AFFECT THE OPERATION OF SYSTEMS TO
REMAIN IN USE. ANY ITEM TO REMAIN THAT I5 DAMA6ED BY THE
CONTRACTOR SHALL BE REPLACED AT HI5 EXPENSE.
6. AREAS OF THI5 PROJWT LEFT TO LANDLORD ARE TO REMAIN AS I5
WITH NO DEMOLITION WORK UNLESS SPECIFICILL.Y NOTED OTHERWISE.
F. BASE EQUIPMENT AND MATERIALS AND SUBSTITUTIONS
1 . ALL EQUIPMENT AND MATERIALS SHALL BE NEW, FREE OF DBSGT5
AND U.L. LABELED.
2. BASE BID MANUFAACTUR136 AND MODELS ARE INCLUDED IN
SPECIFICATIONS OR LISTED IN 5GFEDULE ON PRAWIN6. ANY OTHER
MANUFACTURER OR MODEL I5 A 5UBSTITUTION.
3. SUBSTITUTIONS ARE SUBJECT TO THE APPROVAL OF THE OWNER AND
SHALL BE LI51W ON THE FORM OF PROPOSAL. FOR THE OWNER'S
CONSIDERATION PRIOR TO CONTRACT AWARD. IF SUBSTITUTION 15
SUBMITTED, IT I5 THE CONTRACTOR'S RESPONSIBILITY TO EVALUATE
IT AND CERTIFY THAT THE SUBSTITUTION I5 EGiUIVALENT IN ALL
RESPECTS TO THE BASE SPECIFICATIONS.
4. IF SUBSTITUTIONS ARE APPROVED, NNOTIFY ALL OTHER CONTRACTORS,
SUBCONTRACTORS OR TRADES AFFECTED BY SUBSTITUTION AND FULLY
COORDINATE. ANY COSTS RESULTIN6 FROM SUBSTITUTION, WHETHER
BY CONTRACTOR OR OTHERS, SHALL BE RESPONSIBILITY OF AND PAID
FOR BY 5MTI7UTINN6 CONTRACTOR.
5. ALL EQUIPMENT SHALL BE INSTALLED IN FULL ACCORDANCE WITH THE
MANUFAGTURER'5 INSTALLATION INSTRLUCTION5. IT I5 THIS
CONTRACTOR'S RESPONSIBILITY TO CHECK AND CONFORM TO THESE
REQUIREMENTS PRIOR TO STARTIN6 WORK.
6. CHECK, TEST, START, ADJUST, BALANCE AND INSTRXTION5
1 . AFTER INSTALLATION, CHECK ALL EQJ I PMENT, AND P67P M START
UP IN ACCORPANGE WITH THE MANUFACTURER'S INLSTRUGTION5.
2. ALL PIPING SHALL BE TESTED AND FREE OF LEAKS.
3. BALANCE ALL SYSTEMS, CALIBRATE CONTROLS, CHECK FOR PROPER
OPERATING 5EGIM CE UNDER ALL CONDITIONS, AND MAKE ALL
NEGE55ARY ADJUSTMENTS.
4. ALL WIR1N6 SHALL BE FULLY TESTED AND MADE FRED OF 6ROUND5
AND SHORT CIRCUITS.
5. INSTRUCT OWNER IN OPERATION OF SYSTEMS AND SUBMIT OPERATIN6
AND MAINTENANCE MANUAL. ON ALL 6QU I PMBNT AND SYSTEMS.
6. PROVIDE EEN61RAVED LABELS AND IDENTIFICATION TA65 FOR ALL
PIPING SYSTEMS, VALVES AND EQUIPMENT.
7. PROVIDE TYPED PANEL DIREGTORIES AND E:N61RAAVED LABELS FOR ALL
PANELS AND EGlU I PMEdT.
6. CUTTIN6, PATCHING AND VRILLIN6
1. ALL CU17I146 AND C4A5INN6 OF THE BUILDIN6 C"TRUGTION
REQUIRED FOR THIS NOW SHALL 13E BY THIS CONTRACTOR UNLE55
SHOWN ON ARCHITECTURAL DRAWIN65 AND CONFIRMMED AS TO SIZE AND
LOCATION PRIOR TO NEW CONSTRUCTION. CUTTIN6 SHALL BE IN A
NEAT AND WORKMANLIKE MANNER.
2. NEATLY SAW CUT ALL REECTAN6ULAR OPENIN55, SET SLEEVE 7HRO"
OPENIN6, AND FINISH PATCH OR PROVIDE TRIM FLANGE AROUND
OPENIN6.
3. NEATLY SAW GUT FLOORS FOR SB°ER INSTALLATION AND PATCH FLOOR
TO MATCH EXISTIN6, INCLUDING FLOOR COVERINN6.
4. CORE DRILL AND SLEEVE ALL ROUND OPBNIN65.
5. GUT AND PATCH FXISTINN6 BUILDINN6 WALLS AS MQLUIRED FOR DUCT
INSTALLATION. PROVIDE STEM LINTEL ABOVE OPENIN6 KIPM THAN
10' . 5ER STHRIJGTURAL DRAWIW65 FOR SIZES. PROVIDE
E5GUTCHEONS OR 2' WIDE SHAT METAL FJAN6E5 AROUND ALL
EXPOSED PENETRATIONS.
6. DO NOT GUT ANY STRIUGTA AL GOMPONE T5 WITHOUT ARCHITECT'S
APPROVAL..
7. PATCH AND FINISH TO MATCH ADJACENT AREAS THAT HAVE BEEN GUT,
DAMA6ED OR MODIFIED TO INSTALL EQUIPMENT FOR THIS PROJECT.
8. FIRE STOP ALL PENETRATIONS OF FIRE RATTED CONSTRUCTION IN A
CODE APPROVED KAMM, U5IN6 UL LISTED FIRE RATED MATERRIALS.
4. ALL C44 TRACTORS, SHALL CONFIRM KITH OWNER, PRIOR TO BID,
TIMME5 AVAILABLE FOR NOISE PRODUGIN6 WORK SUCH AS CUTTIN6 AND
GORE DRILLIN6 OF FLOORS, WALLS, ETC., AS WEE. AS TIMffi FOR
WORK WHIGH REQUIRE ACCESS INTO ADJOININ6 AREAS. INCLUDE ANY
PREMIUM TIME i GV11;ED IN BID.
H.
1. FULLY WARRMfr ALL MATERIALS, EGIJIR04T AND MMMOW 5HHIP FOR
ONE (1) YEAR FROM DATE OF ACCEPTANCE.
2. EXTEND ALL MANUFACTURER'S WARZARTIE5 TO OWNER.
3. REPAIR OR M11-ME WITHOUT CHARGE TO THE OWNER ALL ITEMS
FOUND DEFECTIVE DURING THE WARRANTY PERIOD.
MECHANICAL LAICAL SYSTEMS
PLUMBIN6 SYSTEM
A. SCOPE
1. FURNISH ALL PLUMBIN6 FIXTURE5, EQUIPMENT AND MATERIAL
INDICATED AND SHOWN ON DRAWIMS AND INSTALL COMPLETE AND
PLACE IN PROPER OPERATION.
2. PLUM5IN6 SYSTEM5 TO E55ENTIAL-LY CONSIST OF THE FOLLOWIN61
A. SANITARY WASTE AND VENT PIPING AND SANITARY SEWER
EXTRUDED TO EXI5TIW BUILDIN6 FACILITIES.
B. DOMESTIC WATER EEXTEDEP FROM EXISTIN6 BUILDIN6
FAGILITIE5 AND DISTRIBUTION 5Y5TE4 TO NEW FIXTURES.
G. PLUMBIN6 FIXTURES AND EQUIPMENT WITH ALL MGVIR12D TRIM,
CONTROLS AND AGGE550RIE5.
D. INSULATION OF PLUMBING IT845.
E. OTHER ITEMS INDICATED ON DRAWIN65 OR RLSGVIRID FOR
COHPIETE INSTALLATION.
B. EXCAVATION AND BAGKFILL
1. PERFORM ALL EXCAVATION AND BACKFILL REQUIRED FOR
INSTALLATION OF BE OH -6RADE PIPING.
2. EXCAVATE TO DEPTH REQUIRED TO INSTALL PIPING AT REQUIRED
LEVI =L AND PITCHH. PIPE TO BE LAID ON BEDDIN6 OF SAND OR
INTIRLOCKIN6 A66M67ATE TO 6IVE UNIFORM WMINN6 ALON6 LEN6TH
OF PIPE.
3. BACKFILL WITH BEDDING MATERIAL TO A MINIMUM OF TWELVE (12)
INCH1E5 ABOVE TOP OF PIPES AND COMPACT. BALANCE OF SACKFILL
SHALL- BE INTERLOCKING A66R56ATF. ALL BACKFILL SHALL BE
COMPACTED IN MAXIMUM b' LAYERS. COORDINATE TREENCHIN6 OF
FLOOR WITH MALL CRRITERIA.
4. PATC4 FLOOR TO MATCH IDUSTIN6.
G. SANITARY 5H'L-RS
1. INSTALL SANITARY , STACKS, VENTS, FLOOR DRAINS AND
CLEANOUTS FOR PROJECT AND EXTEND TO EXI5TIN5 BUILDING
FACILITIES.
2. SEEMER5 TO BE PITCH® A MINIMUM OF 1/4' PER FOOT FOR 2 -i/2'
512 ES AND UNDER AND 1/6' PER FOOT FOR 3' SIZES AND LA R6ER OR
TO 6RA9E5 INDICATED ON DRAWIN65.
3. CHANGED IN DIRECTION AND BRANCH CONNECTIONS SHALL BE MADE
WITH APPROVED DRAINA6E FITTIN65 COMPATIBLE WITH THE PIPING
SYSTEM MATERIAL IN WHICH IT I5 INSTALLED.
4. ALL FIXTURES AND SANITARY DRAINS SHALL BE VENTED AS
INDICATED ON DRAWIN65 AND IN ACCORDANCE WITH CODE. VENTS ARE
TO BE ECTENDED TO EXISTING BUILPIN6 FACILITIES AS INDICATED
ON DRAWING.
5. WHEN CONN65TIN6 TO AN EXISTIN6 WITHIN BUILDIN6, VERIFY
SEWER I5 ACTIVE 13Y FLJ)SHIN6 WITH WATER, MINIMUM 5.0 6PM, FOR
FOUR HOURS PRIOR TO THE START OF WORK.
6. PVC PIPING
A. MAY ONLY BE USED WHEN SPECIFICALLY LI51E'D DELON.
B. SMALL NOT BE INSTALLED IN RETURN AIR PLE LAG OR WHERE
DISCHAR5E WATER TEMPERATURE EXCEDUS 120 DE6. F, USE NO
HUB CAST IRON OR 6ALVANIZED STS PIPING.
G. SMALL NOT BE INSTALLED UN.E55 PERMITTED 13Y GORE.
7. SEEKER AND VENT MATERIAL_ SMALL BE AS FOLLOW5:
A. BELOW 61RADE SANITARY INSIDE BUILDIN6
1. PVC-DWV PLASTIC ASTM D-2665 WITH ASTM D-2665 DWV
SOLVENT WELD SOCKET FITTIN65.
B. ABOVE 61RADE VENTS AND SANITARY -
1. NO-HUB CAST IRON PIPE ASTM A -888 WITH ASTM G -564
ELASTOMERIG MECHANICAL JOINT.
2. SCH. 40 6ALVANIZW STEEL PIPE ASTM A-53 WITH CAST
IRON 500ED FIMN65 A5ME 816.12.
Fil
1. aEANOUTS SHALL BE INSTALLED FLUSH WITH FINISHED FLOOR WITH
PLAT® COVERS.
2. ALL CLOSURE RX66 ARE TO BE SEALJD HATERTI6W TO THE PIPE IN
WHICH IT IS IPSEZTED.
3. GLIEANOU'TS SHALL BE AS FOL..LONS:
MARK ITEM DESCRIPTION
CO-A CLFANOUT FLOOR TYPE, J. R. SMITH
SERIES 4020 WITH
POLISH® BRQNM TOP
CO-B CLPJNOUT EXPOSED WALL TYPE, J. R.
SMITH SERIE5 4402 WITH
STAINLE55 57f$ ACCESS
COVER
F. FIXTUR155 AND EQUIPMENT
1 . FURNISH ALL FIXTURES AND ECIIU I PMENr INDICATES AND SC EMLED
ON DRAWIN65, COMPLETE WITH ALL ACGE560RIES, CONTROLS AND
INSTALLATION ITEMLS REQUIRED.
2. INSTALL IN FULL ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATIONS AND PLACE IN SATISFACTORY OPERATION.
3. FI X7UR!IE5 AND EQU I PMBNT SHALL. BE AS FOLLOWS
MARK ITEM DESCRIPTION
P -1 H WATER CLOSET AMERICA STANDARD CADET NO.
2317.100 FLOOR MOUNTED PRESSURE
ASSISTED TANK TYPE SIPHON JET WITH
METAL HANDLE AND WHITE OPEN FRONT
COMMERCIAL 6RADE SEAT WITH CHECK
HINGE. TANK LEVER SHALL BE ON
WIDE 5IDE OF TOILET AREA
P -24 LAVATORY AMERICA STANDARD LUCERNE ENO.
0355.012 WALL. HUNG WITH FLOOR
MOUNTED CARRIER, WITH CHHICA60 NO.
802- 665 -CP SELF- GL35IN6 FAUCET,
WITH 6RID DRAIN AND TAILPIECE
P -3 JANITOR SINK FIAT NO. MSB 2424 WITH CHICA60 NO.
8q7 FAUCET AND FIAT RIM 6UARD, HOP
HOOK, HOSE WITH BRACKET, AND
5TAINL.E55 STEM SPLASH 6UARD ON
WALL
P -4H SINK JUST NO. SL -ADA- 2122 -A-6R, 18
6AU6E STAINLE55 STEEL. WITH
AMERICAN STANDARD NO. 4205.000
FAUCET AND JUST NO. J-35 CRUMB
CUP, DRAIN AT CENTER MAR
diG- i H H.EG. MAIM HALSEY TAYLOR, WAIL. HUNG, HIAC8FBL-
COOLER VR-Q BI- LP/El. HANDICAPPED COOLER,
8.0 6PH, 1/5 HP, 120/1/60
ELECTRIC, STAINLE55 STEEL FINISH.
HIW-1 HOT WATER HEATER A. 0. SMITH ELSG /105, 15 6AI1AN,
1.5 KW INPUT, 120/1/60 ELECTRIC, 6
6PHH RECOVERY AT 100 DE6RE5 F RISE
WITH WATTS NO. IOOXL TE PERATURE
AND PRESSURE RELIES VALVE
FD -1 FLOOR DRAIN J. R. SMITH SERIES 2005 -6A FEAT
STRAIN WITH NICKEL BRONZE FINISH
AND 1/2' TRAP PRIMER TAP. PROVIDE
SQUARE 6RATE FOR TILE FLOORS.
MV -1 MIXING VALVE POWERS HYDROGUARD S6ZIE5 480,
UNDER THE SINK TEMPEZIN6 VALVE,
SET TEHHPERATURE AT 100}F
TPV -1 TRAP PRIMMER VALVE PRbGI5ION PL.UMBIN6 PRCIM;CT5,
ORE5GN NO. i
NOTE:
I. AN 'H' AFTER THE FIXTURE DM16NATION INDICATES A HANDICAPPEDD
ACCESSIBLE FIXTURE TO 13E INSTALLED PER THE REQUIREMENTS OF A.D.A.
AND ANSI MQUIR@i!ENT5.
2. ALL 'P' TRAPS TO BE CHROME PLATED, SEAMLESS CAST BRASS, 17 6A.
WITH aEANOUT AND ESCUTCHEON PLATE.
3. ALL STOPS' TO BE CHROME PLATED ANGLE VALVES WITH FLEXIBLE RISER
AND ESCUTCHEON PLATE.
4. ALL DRAIN PIPES FROM TRAP PRIMMER VALVES TO BE P1TC.H11ED AT 1 /2%
MINIMUM FROM VALVE TO FLOOR DRAIN.
6. WATER PIPIN6
1. EXTEND DOMIESTIC WATER FROM EXI5TIN5 BUILDIN6 FACILITIES AS
INDICATED ON DRAAMMIN65. INSTALL DIOMESTIC WATER DISTRIBUTION
PIPING TO ALL FIXTUI;a5 AND EGUIPMENT MOMRIN6 SAME.
INCLUDE ALL FITTIN65, VALVES, HAIN61ERS, AND OTHER AGGESSORIE5
REQUIRED FOR COMPLETE INSTALLATION.
2. INCLUDE UNIONS, OR OTHER DI5C.ONf•EGT HEADS, STOPS OR VALVE
FOR ISOLATION OF FIXTURES AND EQUIPMENT. VALVES TO BE FULLY
COMPATIBLE WITH PIPING FOR SERVICE INTENDED AS MANUFACTURED
BY NIBCO, CRANE OR OTHER APPROVED MANE AGTURHR. VALVES
SHALL BE LOCATED IN ACCESSIBLE CEILINGS OR AGCE55 PANELS
SHALL BE INSTALLED FOR ACCESS INTO PLASTER WALLS OR
CEILIN65. INCLUDE HOSE OR DRAIN VALVES AT LOW POINTS WHERE
FIXTURES CANNOT BE USED FOR DRAINA6E.
3. INSTALL SHOCK ABSORBERS AT EACH FIXTURE WITH QUICK CLOSIN6
VALVES OR WHERE MQIIRED TO PREVENT WATER HAMMER.
4. HANGERS ON INSULATED PIPE TO BE OUTSIDE OF INSULATION, SIZED
ACCORDIN6LY AND WITH SUFFICIE3NT SADDLE TO PROTECT
INSULATION.
S. WATER PIPIN5 ABOVE 61RA1DE SHALL BE TYPE 'L' HARD COPPER ASTH
B 88 WITH WR4U6HHT COPPER FITTIN65 ASME B 16.22 AND NOWLi =AD
OR ANTIMONY SOLDER JOINTS AND TYPE 'K' SOFT COPPER WITH
SILVER SOLDER JOINTS BELOW 6RADE. WATER SERVICE AND
DISTRIBUTION PIPING SHWA_ CONFORM TO NSF 61. SOLDER JOINTS
SHALL CONFORM TO ASTM 8828 AND FLUX SHALL CONFORM TO ASTM B
813. PIPING SHALL 13E LABEL TO I1751NTIFY TYPE OF SERVICE.
b. FLUSH, VENT AND SANITIZE ALL WATER PIPING WITH EQUIVALENT
SOLUTION OF 50 PPM OF AVAILABLE CHLORINE UPON COMPLETION.
H. SUPPORTS AND HAN6ER5
1. HAN6ER5 AND .SUPPORTS ARE TO BE PROVIDED TO PROPERLY SUPPORT,
SECURE AND ALI6N PIPING AND TO MEET CONDITIONS.
2. SPACING TO COMPLY WITH LOCAL CODE MWIiREEINITS.
J. INSULATION
1. INSULATE ALL ABOVE -GRADE NEW AND EXISTIN6 HOT AND COLD WATER
PIPING AND CONDENSATE DRAINS WITHIN CEILING PLENUMS WITH ONE -
HALF (1/2) INCH THICK MOLDED FIBER ASS HAVING TYPE ASJ
JACKET AND MANUFACTURED BY OVENS - YARNING FIBER6LA5 COMPANY.
PROVIDE ONE (1) IN1C44 THICK INSULATION FOR ALL HOT AND
TEMPERED WATER PIPING.
2. INCLUDE INSULATION OF FITTIN69 AND VALVES. KEEP VAPOR
BARRIERS INTACT. APPLY TO MANUFACTURER'S RSC040NDATION5.
3. INSULATE ALL B130W -6RADE WATER PIPING INSIDE BUILDIN6 WITH
3/8' FOAMED PLASTIC, INSULATION.
4. INSULATE ALL EXQO"r WASTE AND SUPPLY PIPING UNDER
LAVATORIES WITH THE HANOI -LAV GUARD INSULATION KIT BY
TRUEBW OR EQUAL.
5. INSULATE ALL CONGEALED WASTE PIPING FROM ELECTRIC WATER
COOLERS.
FIRE PROTECTION SPRINKLER SYSTEM
A. SCOPE
1. FURNISH ALL LABOR, MATERIALS AND EWIPMENr AS RSQJIR® TO
INSTALL COMPLETE FIRE PROTECTION SYSTEM FOR PROJECT.
2. SPRINKLER WORK FOR PROJECT 155ENTIALLY CONSISTS OF THE
FOLLOWINbs
A. MODIFY EXI5TIN6 FIRE PROTECTION SYSTEM AS REQUIRED TO
CONF'ORM TO NEEM CEILIN6 AND PARTITION LAYOUT.
B. FIRE PROTECTION SYSTEM FOR ALL AREAS OF THE PROJWT.
G. SPRINKLER CONTRACTOR TO BE APPROVED BY MALL
CONISPTRUGTION MANA6FR TO DO WORK AT HALL.
D. PREPARE SUBMITTAL DRAMIN69 AND H(DRAU)LIG GALCULATION5
IN ACCORDANCE WITH OWNER'S INSURANCE COMPANY, BUILDIN6
DEPARTMENT, AND LOCAL FIRE AUTHORITY'S REG U I REMEN'T'5 AND
SUBMIT FOR APPROVAL.
E. FLUSH AND CONDUCT' PRE55U1;E T1E5T OF COMPLETED 5Y5TE4 IN
ACCORDANCE WITH NFPA AND AUTHORITIES HIAVIN6
JURISDICTION.
F. OTHER ITEMS INDICATED ON PRAMIN65 OR REQUIRED FOR
COMPLETE INSTALLATION.
B. PM16N BASIS
1. PMI6N BASIS FOR SYSTEM SHALL BE PER ALL APPLICABLE NFPA
STANDARDS, INCLUDIN6 BULLETINS 13 AND 30, BUILDIN6 CODE,
INSURANCE UNDERWRITER, AND FIRE MARSHAL REQUIREMENTS.
SYSTEM SHALL BE A HYDRAULICALLY DE5I6NED SYSTEM.
G. MMIN65 AND CALCULATIONS
1. CONTRACTOR SHALL PREPARE SUBMITTAL DRAWIN6 AND HYDRAULIC
CALCULATIONS FOR SPACE IN ACCORDANCE WITHH OWNISV5 INSURANCE
COMPANY AND BUILDIN6 DEPARTMENT MQUIREHE TS.
2. CONTRACTOR SHALL OBTAIN FLOW TEST DATA ON CITY WATER MAIN
AND SUBMIT DATA WITH CALCULATIONS. PERFORM FLOW TEST IF
ACCURATE REGENT DATA I5 NOT AVAILABLE.
3. CONTRACTOR AND DEIMER SHALL 13E STATE CERTIFIED.
4. CONTRACTOR SHALL_ INSTALL ALL SPRINKLER PIPING AS HI6H AS
POSSIBLE, TI6HHT TO UNDERSIDE OF STRUCTURE, AND THRM6H
JOISTS OR 7Rl1SSE5 WHERE POSSIBLE WITH DRAINS AND OFFSET'S
BELOW BEAMS. SPRINKLER CONTiRACTOR SMALL COORDINATE
SPRINKLER SYSTEM WITH DUCTWORK AND LI6HHT5. ALL COSTS
A55XIATM WITH RAI5IN6 SPRINKLER PIPING WHERE THE
ARCHITECTURAL DEBI6N CANNOT BE ACCOMPLISHED SHALL BE THE
RESPONSIBILITY OF THE SPRINKLER CONTRACTOR.
D. PIPING
1. ALL PIPING SHALL BE INSTALLED IN ACCORDANCE WITH NFPA
REQUIREMENTS AND FM APPROVED.
2. FIRE PROTECTION PIPING SHALL BE AS FOLLOWS:
A. PIPING SHALL MATCH EXI5TIN6 BUILDIN6 STANDARDS.
B. CONTRACTOR SHALL ARRAN6E FOR SHUTDOWN OF EXISTIN6
SYSTEM WITH LANDLORD, OWNER AND INSURANCE UNDERWRITER.
G. FLUSH ALL PIPING UPON COMPLETION OF PROJECT AND TEST
PER NFPA 13.
D. NO WET SPRINKLER PIPING SHALL BE INSTALLED AT LOCATIONS
SUBX39T TO iFNZIN6. PROVIDE 6LYCOL LOOP OR DRY SYSTEM
FOR AREAS SU5J6GT TO FREEZIN6.
E. PLASTIC. PIPING I5 NOT APPROVED.
E. SPRINKLER HEADS
i . SPRINKLER HEADS SHAM- BE 1/2' ORIFICE, K--5.6, 165 D55REH3 F,
U.L. LISTED, AND SHALL MATCH EXISTINN6 BUILDING STANDARDS.
2. SPRINKLER HEADS SHALL BE AS FOLLOWS:
A. AREAS WITH EXPOSED STMXTURE
1. UPRI6HT - ROU6H BRA55 SPRINKLER HEAD.
B. AREAS WITH CEILIN65
1. FI..0 *1 SPRINKLER HEAD - FLUSH SPRINKLER HEAD WITH
CEILIN6 DISC COLOR TO MATW CEILING FOR ALL AREAS
WITH CEILIN65.
3. INSTALL HI6HER TEMPERATURE SPRINKLER HEADS WHEEZE REGUIMP BY
CODE OR APPLICATION AND QUICK RESPONSE HEAD5 IN L16HT HAZARD
OCCUPANCIES.
4. SUBMIT 5APLE5 OF SPRINKLER HEAD5 TO ARCHfITECT PRIOR TO
FABRICATION OF ANY PIPIN6.
S. INSTALL INSPSGTOR'S TEST CONNEECTION WITH VALVE AND TERMINATE
DRAIN TWZU6H ECTIERIOR WALL WITH TEST FITTIN6 AND SPLASH
BLOCK. COORDINATE LOCATION WITH ARCHITECT.
F. VALVES
i. INSTALL ALL VALVES REQUIRED BY NFPA WHICHH ARE 'UL' LISTED
AND FM APPROVED.
2. ALL 5HUT -OFF VALVES SMALL 13E FITTED WITH TAMPER SWITC+IE5 BY
FIRE PROTECTION CONTRACTOR AND HNIED BY ELECTRICAL
CONTRACTOR.
3. INSTALL FLOW SWITCHH PROVIDED BY FIRE PROTECTION CONTRACTOR
AND WIRED BY ELECTRICAL CONTRACTOR.
HEATIN6, VENTILJATIN6 AND AIR CONDITIONINNS
A. SCOPE
1. FURNISH ALL EQUIPMMENT, MATE3RIALS, LABOR, TOOLS, ETC., FOR
THE COMPLETE HNAG SYSTEM. INSTALL COMPLETE AND PLACE IN
OPERATION.
2. WAG SYSTEM E55E NTIALL.Y CONSISTS OF THE FOLLOWINN6s
A. REiOCCATION OF EXISTING AIR HHADLIN6 UNITS WITH CHILLED
WATER COILS AND ELECTRIC, HEAT COILS.
B. TOILET ROOM EXHALU5T SYSTEMS EXTENDED TO LANDLORD
PROVIDED DUCTWORK.
G. CHILL® Wl1ii3R PIPING AND GADESATE PIPING TO AIR
HWNDLIN6 UNITS.
D. DUGTWORK, 6RILLIES, DIFFUSERS AND OTHER AGCES ORIE5.
E. INSULATION OF HNAG ITEMS.
F. BALANCING, 7MTIN6 AND START UP.
6. TEMPERATURE CONTROL SYSTEM.
H. OTHER I785 INDIGATED ON DRAWINGS OR REQUIRED FOR
COMPLETE INSTALLATION.
I. I 3ZATURE CONTROL. 5YSTEMM.
J. DEMOLITION OF EXI5TIN6 MECHANICAL SYSTE45 REQUIRED FOR
THIS PROJECT.
K. OTHER ITEMS INDICaATED ON DRAWIN65 OR REQUIRED FOR
COMPLETE INSTALLATION.
I. FABRICATE AND 5ELT ALL DUCTWORK TO ASHRAE AND SMACNA
STANDARDS FROM N0. 1 6ALVANIZED STEEL. ALL DUCTWORK IN
AREAS WITHOUT CEILIN66, THAT I5 TO BE PAINTED SHALL BE
PROVIDED WITH PAINT 6RIP FINISH. COMPLY WITH SMAGNA
STANDARDS, AND NFPA BULLETIN 40A REQUIFBIENTS.
2. DUCTWORK SHALL BE SMACM LOW PREBSURE CONSTRUCTION 2' STATIC
PRIE55U1;E RATING WITH SEAL CLASS B SEAMS AND JOINTS.
3. ALL DUCTWORK SHALL_ BE INSTALLED TIGHT TO UNDERRSIDE OF
GONCM`M STRUCTURE OR TO HEI6HHT AS INDICATED ON PLANS.
4. FLEXIBLE DUCTS SHALL BE INDEPENDENTLY SUPPORTED FROM THE
STRUCTURE AND COMEGTiS WITH PLASTIC, DRAW BANDS TI6HTETED
WITH MANUFACTURER'S TOOL. FLEXIBLE DUCTS SHALL BE LIMITED
TO 48' STRAI6HT LEN6TF5 AND ARE NOT PERMITTED IN ROOMS
WITHOUT CEILIN65. FLEXIBLE DUCTS SHALL BE ATCO TYPE
010, 1 1/2' INSULATION AND RATED AT 10' W.G. FOR SIZES
THHR41U614 12', U.L. LISTED, AND MEET 25/50 FLAME AND SMOKE
TEST. NO INTERIOR COLOR OTHER THAN BLACK 15 PERMITTED FOR
FLEXIBLE DUCTS. EGdUIVAL.ENT BY VAL.UFLEX, FLEX -AIRS, FLEXIBLE
TM44OL06IE5, THERKAFLB( OR 6E4FLEX.
5. INCLUDE ALL TURNIN6 VANES, MANUAL DAMPERS, FLEXIBLE
C,OMAEGTOR5, 6RILLE5 AND DIFFUSJER5, ACOUSTIC LININ6, AND
OTHER SHAT ME7AL ACaR5SORIE5 FOR THE PRO-ECT. VOLUME
DAMPERS TO BE OF OPPOSED BLADE CONSTRUGTION WITH LOCKING
QUADRANTS. PROVIDE VOLUME DAMPERS AT SUPPLY AIR RUNOUT5 TO
ALL CEILIN6 DIFFUSERS.
6. CONTRACTOR SHALL PAINT INTERIOR OF ALL DUCTS VISIBLE FROM
FLOOR TO MATCH THE SURROUNDIN6 FINISH.
7. ALL BRAND4 GONTELTION FITTIN65 IN RECTAN61ULAR DUCTWORK SHALL
BE 45 DES TRANSITION TYPE, CONICAL FITTIN65 OR SPIN -IN
FITTIN65 WITH INTE6RAL AIR SCOOPS. BUTT FITTIN65 ARE NOT
ACCEPTABLE.
8. ACOUSTIC, LINE ALL 1;5CTAN6ULAR DUCTS INDICATIED ON DRANIN165
WITH MINIMUM ONE (1) INCH THICK NON- FLAKIN6, COATED MEDIUM
DENSITY LINER. APPLY TO MANUFACTURER'S RECOMMMENDATIONNS.
DUCT DIMEN5ION5 ARE OUTSIDE DIMENSIONS, AND INCLUDE ACOUSTIC
LININ6.
q. INSTALL U.L. LISTED STATIC FIRE DAMPERS WITH ACCESS DOORS AT
ALL FIRE RATED WAL15, PARTITIONS AND CEILIN65. DAMPERS SHALL
HAVE RATING EQUIVALIENT TO BARRIER.
G. GHIIL.ID WATER PIPING
1. EXTEND CHILLED WATER PIPIN6 FROM EXISTIN6 BUILDIN6 MAINS AND
PIPE TO NEW AIR HANDL_IN6 UNITS.
2. PROVIDE VENTS AT HI6H POINTS AND DRAIN VALVM AT LOW POINTS.
INCLUDE OFF5ET5 TO SUIT THE BUILDIN6 CONSTRUCTION.
3. INSTALL PIPIN6 TO ALLOW CLEARANCE FOR EXPANSION AND
CONTRACTION.
4. MAKE CONNECTIONS TO EGVIPHENT WITH SHUT -OFF VALVES ON SUPPLY
AND BALANCE VALVES ON R1= TURNS.
5. PIPING SHALL BE SCHEDULE 40 BLACK STEEL WITH THREADED
FITTIN66 OR TYPE 'L' C0P1:E R WITH q5/5 SOLDER FITTINFf.
D. INSULATION
I. THE FOLLOWIN6 DUCT SYSTEMS, WHERE CONGEALED ABOVE CEILIN65,
SHALL BE INSULATED WITHI 'INSTALLED' R VALUE (AT 25%
GOMPRE99ioN) OF NOT L Ess THAN 6, WITH FOIL FACED REINFORCED
KRAFT JACKET FIBER&-&% DUCT WRAP:
A. LINED AND UNLINED SUPPLY AND IETURN AIR DUCTS INGLUDIN6
BACKS OF DIFFUSHRS.
2. INSULATE OUTSIDE AIR DUCTS WITH 1-1/20-THICK RI6I0
FIBEd61.A55 DUCT INSULATION, FULLY 5EGl1RED TO DUGT. FAGIN6
SHALL BE WHITE 6LAS5 CLOTH VAPOR BARRIER.
3. INSULATE CHHILLED WATER PIPING WITH 1' MOLDED FIBHa6LA55
INSULATION WITH A VAPOR BARRIER JACKET, COMP05W OF ALUMINUM
FOIL WITH A FLAME RESISTANT KRAFT PAPER FACING AND SELF -
SFALIN6 ADHESIVE LAP JOINT. INSULATION SHALL INCLUDE ALL
PIPE FITTIN65, VALVE ETC, TO PREVENT CONDENSATION FROM
FORMIN6. IF CONDENSATION FORMS ANYWHERE ON CHILLED WATER
SYSTEM CONTRACTOR SHALL REINSUTATE AS REQUIRED TO PREVENT
CONDENSATION.
4. INSULATE CONDENSATE PIPING WITH 1/2' THICK MOLDED FIBER6LASS
INSULATION WITH SELF- SFALIN6 LAPS. SEAL ALL JOINTS VAPOR
TI6HT WITH APPROVED TAPE. ALL FITTIN65 AND VALVES TO BE
PSRF•ORMEP WITH FACTORY FABRICATED PVC, JACKET.
5. ALL INSULATION TO BE APPLIED IN FULL ACCORDANCE WITH THE
MANIFAGTURi9R'S RSGOMMENDATIONS. ALL INSULATION SHAD- COMPLY
WITH 25/50 FLAME AND SMOKE HAZARD RATIN6S PER A57H E -84,
NFPA 255 AND UL '723.
E. CONDENSATE AND OTHER DRAINS
I. FROM EACH AIR HHANDLIN6 UNIT, INSTALL FOUR (4) INCH DEEP
TRAPPED CONDENSATE DRAIN WITH GLEANOUT AND SECONDARY DRAIN
AND EXTEND TO BUILDIN6 CONDENSATE PIPING SYSTEM AS SHOWN ON
PLAN. CONDENSATE DRAIN MATERIAL SHALL 13E COPPER (DWV) ASTM
B- 306 -83 WITH WROU6HT COPPER FITTIN65.
F. EQUIPMENT
I. HVA, CONTRACTOR TO FURNISH ALL HVAC EQUIPMENT INDICATED
AND /OR 5GH1EPULEP ON THE DRAWIN65 COMPLETE WITH BA5Ea,
ISOLATORS, SUPPORTS AND OTHER REQUIRED ACCESSORIES.
2. INSTALL COMPLETE AND PLACE IN PROPER OPERATION PER
MANUFACTURER'S RECOMMENDATIONS, LUBRICATE AND ADJUST AS
R56VIRED. FURNISH AND INSTALL CLEAN 5ET OF FILTERS PRIOR TO
BAL.ANGIN6.
3. EQUIPMENT TO BE MAKE AND MODEL AS SCHEDULED UNLEE% OWNER
APPROVE), EG U I VALENT QUALITY AND PERFORMANCE EQUIPMENT I5
SUBMITTED AS SUBSTITUTION. ALL SUBSTIMIONS SUBJECT TO
AC EFTM46E WITHOUT QUALIFICATION BY OWNER, LANDLORD AND
ARCHITECT. "
4. THIS CONTRACTOR SHALL PERFORM ROUTINE SERVICE INSPECTION OF
ALL EXISTIN6 HNAC UNITS TO BE RE15ED FOR THIS PROJECT.
LJU13RICATE BEARIN65, SPE32VICE CONTROL SYSTEMS, RIPLACCE FAN '
BELTS AND INSTALL. NEW FILTERS IN EACH UNIT. CONTRACTOR SHALL
FIND VERIFY REFRI6ERANT GHHAR6E AND NOTIFY OWNER IF THE
CHARGE IS LESS THAN MANUFACTURER' 5 5PWIFICATIONS. SUBMIT
SERVICE REPORT TO TENANT INDICATIN6 CONDITION OF UNIT AND
REPORT ANY MAJOR COMPONENT FAILURES OR MALFUNCTIONS. REPORT
SHALL INCLUDE COST TO RERAIR ALL ITEMS ABOVE AND BEYOND THEE
I TEEMS LISTED ABOVE. EQU I PME3NT 54ALL BE PLACED IN FULL
OPERATION WITH CONTROLS CALIBRATED UPON COMPLETION OF
PROJECT. .
6. BALANGIN5, START UP AND INSTERUGTIONS
1. AFTER INSTALLATION AND EGU I PMENT I5 PLACED IN OPERATION,
HVAG CONTRACTOR I5 RESPONSIBL.E FOR BALANCIN6 SYSTEMS TO
DE516N FLOW WITH REPORT SUBMITTED TO OWNER. BALANCINN6 .HAIL
BE PERFORM BY AN INDEPENDENT AABC CERTIFIED SUBCONTRACTOR.
2. START UP AND PLACE ALL 5Y5TE345 IN OPERATION AND TA6 ALL
5MITCHE5 AND CONTROLS WITH PERMANENT LABELS.
3. INSTRUCT OWNER ON PROPER OPERATION AND MAINTENANCE OF
SYSTEM.
H.
1 . FURNNISH AND INSTALL ALL CONTROLS FOR HVAC SYSTEMS. PROVIDE
ALL RELAYS AND DWIGES REQUIRED FOR COMPLETE OPERATION.
MOUNT ALL GONTROL5 FURNISHED AS AGGES60RIE5 TO EQIRPME T AND
PROVIDE ALL CONTROL WIRIN6.OR POWER WIRING REQUIRED FOR
CONTROL SYSTEM WHEEZE NOT SPECIFICALLY SHOWN ON ELECTRICAL
PLANS. ALL FXPOSHD WIRIN6 SHALL BE IN EMT CONDUIT PER
N.E.G., CONCEALED WIRIN6 IN CEILIN6 PLENUMS MAY BE UL LISTED
PLENUM RATED CABLE NEATLY SUPPORTED IN WIRE RIN65.
2. SMOKE CONTROL I 1' .
ELECTRICL CONTRACTOR SHALL FURNISH,.. INSTALL AND WIRE A
PHOTO- ELECTRIC, DUCT SMOKE DETECTOR AT EACH AIR HHANDLIN6 UNIT
TO SHUT DOWN FAN ON ALARM. DETECTOR SHALL. BE LOCATED AT THE
SUPPLY AIR AND RETURN AIR DUCTS. --
3. NO THERMOSTATS SHALL• BE, INSTALLED ABOVE ANY HEAT PRODUCIN6
EQUIPMENT.
4. CONTROL SEQUENCE SHALL BE AS FOLLOWSs
A. AH /1, 2 AND 3 CHIILLED WATER AIR HANDL-IN5 UNIT'S -
HONEYWE.L T7350 WALL THERMOSTAT IN MANA6E:R'S OFFICE
WITH REMOTE SENSOR MOUNTED IN SALES OR STOCK AREA SHALL.
MODULATE FAN AND CHILLED WATER MODUL.ATIN6 TWD -WAY
CONTROL VALVE AND ELECTRIC, HEAT TO MAINTAIN SPACE SET
POINT. CYCLING, OR ON/OFF, CONTROL I5 NOT PERMMITTED.
THE CHILLED WATER CONTROL VALVE SHALL BE AS NOTED ON
DRAWIN6 H2. A NORMALLY CL05ED THREE- WAY MMODVL ATIN6
CONTROL. VALVE WITH EQUAL PERGENTA6E VALVE
CHARACTERISTIC, SIZED FOR A DIFFRNTIAL PRESSl1RE OF NO
L E55 THAT FIVE (5) PSI AND NO MORE THAT TEEN (10) PSI
ACROSS THE VALVE AT DE'S•I6N FLOW RATE. THE MAIN
MAINTAINS CLASS IV LFAKA6E RATING UP TO 100 PSI
PRLx5URE DIFFEFtB4TIAL AC1R0S5 THE VALUE. FOLLOW
MANA=AGTURER5 REQUIRE EATS FOR PROPER I NSTALL.ATI ON .
MOTORIZED OUTDOOR AIR DAMPERS SHALL OPEN AND FAN SHALL
RUN CONTTINIOUSLY DURIN5 ALL OCCUPIED HOURS. OUTDOOR AIR
DAMPERS SHALL CLOSE AND FAN SHALL CYCLE DURINN6
UNOCCUPIED HOURS. TH S44 TAT SHALL HAVE SUBBASE
SELECTOR SWITCH TO ALLOW SELECTION OF
HHFATIN6 /COOLIN6 /AUT0 AND FAN ON/AUTOMATIG OPERATION.
B. EF/ 1 AND 2 REST ROOM FXHAU5T FANS - INTERLOCK FANS TO
OPERATE WITH GOR12E5S IN6 ROOM LI6HT5. (BY ELECTRICAL
CONTRACTOR) .
G. V'T-i VOLUME CONTROL. TERMiINAL - THERMOSTAT SHALL
MODULATE DAMPER TO MAINTAIN SPACE SET POINT. DAMPER
SHALL REVETRSE OPERATION BASED UPON AIR CONDITIONIN6
UNIT HFJATIN6 OR COOLIN6 MODE. CHANGEOVER SHALL OCCUR
AT -5 D66RE=5 SET POINT.
ELECTRICAL SYSTEM
A. SCOPE
I. INCLUDE ALL LABOR, EQUIPMENT, TOOLS AND MATERIALS FOR
ELECTRIC DISTRIBUTION, AS SHOWN ON DWAWIN65.
2. REYHORIK DXISTINS 2 -7/480 VOLT POWER SERVICE TO SPACE AS SHOWN
ON DRAWIN65.
3. ALL ELECTRICAL WORK, INICLLIDIN6 POWER WIRIN6 FROM PANEL IN
BUILDIN6 AND WIRING MOTHER ITEMS INDICATED.
4. FURNISH AND INSTALL NEW LI6HTIN6, EMEdSENCY AND EXIT
LI6HTIN6 AS INDICATED ON DRAWIN65.
5. PROVIDE FACILITIES TO MHORK EEXISTIN6 71ELEPHOW SERNICE.
b. PROVIDE A MANUAL FIRE ALARM SYSTEM AS SHOWN ON DRAWIN65.
7. OTHER ELECTRICAL ITEMS INDIGA'TED ON PRAIIN65 OR REQUIRED FOR
COMPLETE INSTALLATION.
8. ANY INSTALLATION COSTS ASSESS® BY UTILITY GOMPANIE5 FOR
INGOMIN6 S13RVICE INSTALLATION SHALL BE INCLUDED IN BID AND
PAID FOR BY THE ELEGTRICAL CONTRACTOR.
5. CONDUIT INSTALLATION
I. ALL WIRIN6 TO BE INSTALLED IN CONDUIT IN ACCORDANCE WITH THE
N.E.G. AND 50 THE REQUIRED CONDUCTORS MAY BE PULLED WITHOUT
INJURY OR STRAIN AND PROPERLY SUPPORTED. INCREASE CONDUIT
TRADE SIZE AS REQUIRED FOR LONG PULLS ABOVE MINIMUM 1EQIIRFD
SIZE.
2. ALL CONDUIT SHALL BE ROUTED TO PRE E1;?VE HEADROOM, EQUIPMENT
ACCESS, AND ARCHIITEGTURAL CLEARANCES FOR FINISHES, INGLUDINN6
CEILIN6 HHEI6HTS WITHOUT ADDITIONAL CLARIFICATION.
COORDINATE WITH ALL OTHER TRADES 50 THAT CONDUIT RUNS DD NOT
BLOCK ARCHIITECTURAL M01JIMMEENT'5 FOR FINISHED CONSTRRUCTION.
3. ALL CONDUITS TO BE CONGEALED IN BUIL.DIN6 NEW CONSTRUCTION
WHERE AVAILABLE.
4. EXPOSED CONDUIT MAY BE RUN ON EXISTIN6 MASONRY WALLS IN
EG UIPMENT ROOMS. VERIFY ALL LOCATIONS WITH OWNER PRIOR TO
ROUGH-IN.
5. INTERIOR WIRING TO BE INSTALLED IN ELECTRICAL METALLIC
TUBIN6 (EMT) WITH STEEL SET SGREK TYPE COUPLIN65 AND
CONNECTORS. WHERE CONGEALED, USE TYPE MG ARMORED CABLE. EMT
OR MG GABLE I5 NOT APPROVED FOR INSTALLATION IN CONCRETE
SLABS OR UNDER6ROUND.
6. CONDUIT ON BUILDING EXTERIOR SHALL BE RI6ID ALUMMINUM OR
6ALVANIZED STEEL WITH WEATHER-TIGHT FITTIN65 AND DEVICES.
PROVIDE EXPANSION FITTIN65 WHERE CONDUITS EXIT FROM 61RADE.
I. UNDERISROUND CONDUIT BELOW 6RADE SHALL BE RI6ID SCHEDULE 40
PVC, WITH SOLVENT WEB FITTIN65. INSTALL GORE SIZED 6ROUND
CONDUCTOR IN ALL PVC, CO MIT. PENETRATION5 OF FLOOR SLABS
SHALL BE MADE WITH RI6ID 6ALVANIZED STS., WHERE CONDUITS
ARE FXPOS.V TO MECHANICAL DAMA6E. PVC, PBNETRATION5 ARE
ACCEPTABLE WHt3iE PROTECTED FROM PHYSICAL DAMA6E. PROVIDE
EXPANSION FITTIN65 AS RSGOMMENDED BY THE MANUFACTURER.
8. NO CONDUIT TO BE RUN EXPO50 ON EXTERIOR OF BUILDING WALLS
OR ON THE FLOORS.
4. PROVIDE ALL PULL BOXES AND FITTIN65 WHEMVER NECESSARY OR
SHOWN. ALL SWAI6HT CONDUIT RUNS SHALL NOT EXCEED 100 FEET
WITHOUT PULL BOX, NOT OVER 75 FEET FOR RUN WITH ONE (1)
RIGHT ANGLE BEND AND NOT OVER 50 FEET FOR RUN WITH TWO (2)
RI6HHT MN6LE5.
10. ALL CONDUIT SHALL BE PROPERLY SUPPORTED IN ACCORDANCE WITH
THE N.E.G. CONDUIT SHALL BE IMDEPBNVEE!'MY SUPPORTED FROM
STRUCTURE AND NOT FROM DUCTWORK, CEILIN6 HAN61E S OR CEILIN6
SUPPORT WINErP. NO CONDUIT SHAH. ROUTE THROU6HH ROOF TOP
EQUIPMENT 1;El1URN AIR OPBNIN65.
11. FINAL CONNECTION TO LI6HiT FIXTURES AND EQUIPMMENE SHALL BE
MADE WITH FLEXIBLE STEEL CONDIUIT ('6>RffWIELD' - 6' MAXIMUM
LEN6THH) IN DRY AREAS AND LIQUID TIGHT FLEXIBLE METALLIC
CONDUIT ('SEALTITE') IN DAMP OR WET AREAS.
12. ALL EMPTY CONDUITS ARE TO BE PROVIDED WITH PULL WIRE5 AND
NYLON BUSHIN65 AT BOTH ENDS.
13. CONDUIT PER TR,ATION5 OF ROOFS SHALL. BE MADE WITH PATE PIPE
GURB5 OR PIPE SEALS AS MG1U I RED, I NSTALLFD W THE PROJECT
ROOFIN6 CONTRACTOR. FOR EXI5TIN6 ROOFS, THE PENETRATION
SHALL BE MADE BY AN OWNER APPROVED CONTRACTOR TO MAINTAIN
DEED ROOF WARRANTY. GONN!ECTIONS TO ROOF TOP EGUIPMENNT SHALL
BE MADE THPZU6HH THE ROOF CURB WHERE CURB I5 DESI6NED FOR
THIS CONNECTION.
14. PROVIDE SURFACE WIRBMOLD AND BOXES FOR SURFACE WORK IN
FINISHED AREAS W4E3RE SPECIFICALLY APPROVED BY THE ARCHITECT.
15. GON W I T5 ROUTED BELOW FLOOR SLAB ARE TO BE COORDINATED WITH
OTHER BB.OW -SLAB UTILITIES. INSTALL CONDUITS BBAW FLOOR
SLAB, NOT IN FLOOR POUR. GUT AND PATCH EXI5TIN6 FLOORS
WHERE CONDUIT MUST BE CONGEALED IN OR BELOW FLOOR. COMDUIT5
SHOWN RUN OVERHEAD GANNOT 13E RUN BELOW 6RADE WITHOUT PRIOR
APPROVAL AND COORDINATION WITH THEE EN6I1N®R AND ALL AFFECT®
CONTRACTORS.
16. PROVIDE SEALS WHEN CONDUIT 15 PAS5IN6 FROM GOLD TO WARM
BNVIRONME31M. USE SILICONE 5PALANT AROUND BOXE5 AND
EXTERIOR OF RACEKAV5 AND SEJALINS COMPOUND OR FOAM -IN- PLACE
SEALANT WITHIN RACEEKAYS.
G. "OUTLET BOXES
• � 1 i. ' SUPPOR VAI.;4 BOXES FROM BUILDIN6 STRUCTURE INDEPENDENT OF THE
GONDUIT`SYSTEM.
2. ` FLUSH' OrEVICE BOREE5 IN MASONRY HALLS SHALL BE DE5I6NED FOR
THE PURPOSE WITH RAISED COVER.
3. WIRIN4 DEVICE BOXE =S FOR SURFACE CONDUIT WORK SHALL BE F5
SERIES 'EAST BOXES.
4. DEVICES ON BUILDIN6 EXTERIOR SHAW_ BE WEATHERPROOF NEMA 31R.
5. BOXES FOR FLUSH HOUNNTIN6 SHALL BE 4' SQUARE MINIMUM WITH
DEVICE -RING FOR WIRING DEVICE TO BE INSTALLED. COMMUNICATION
JUNCTION 50)05:5HALL BE 2 -1/8' DER MINIMUM.
b. PROVIDE CUSTOM MADE DEVICE BOXES TO ACCOMMODATE CONDUIT
PENETRATIONS SHOWN ON PLANS.
D. WIRE AND GABLE
I. WIRE.AND GABLE SHALL BE AS FOLLOWS:
A. - #12 AW6 AND #10 AW6 SOLID OR STRANDED CONDUCTOR COPPER,
600 VOLT, TYPE TH MN/THHHN, XHH H, OR THIN (-M/90 D56RFE5
C).
B. #8 A16 TO AND INCLUDIN6 #500 KCMIL AWE, STRANDED
CONDUCTOR, COPPER, 600 VOLT, TYPE THWN/TH#N, XHHW OR
THIN ('15/40 D55RER5 0.).
G. TYPE THHHN (40 DE61REE!5 C.) WIRE FROM OUTLET BOX TO L16HT
FIMUR95.
D. #14 AW6 MAY BE USED FOR LOW VOLTA6E CONTROL WIRIN6
ONLY.-
E. ELECTRICAL CONTRACTOR MAY OPTION TO USE TYPE MG
(AIMED GABLE) FOR BRANCH CIRCUITS FOR CONCEALED MORK,
IF APPROVED BY OWNER AND LANDLORD PRIOR TO BID.
2. COLOR CODIN6 SHALL BE USED FOR ALL WIFE AND GABLES IN
ACCORDANCE WITH N.E.G. CODINS STANDARDS. CONTROL CONDUCTORS
SHALL BE GONITINJOUSLY COLOR CODE). 6ROUND GONDUGTOR SHALL
BE 6R®N.
3. JOINTS IN #10 AW6 AND SMALLER WIRE SHALL BE MADE WITH
'SCOTCH LOCKS' (OR EQUAL) AND BE INSULATED WITH SCOTCH #33
ELECTRICAL TAPE.
4. JOINTS IN #8 AW6 AND LAR6E2 SHALL BE HAVE WITH P TYPE
MECHANICAL CONNECTOR AND IN5ULA1W WITH ELECTRICAL TAPE: TO
150% OF THE INSULATIN6 VALUE OF THE CONlMXTOR.
5. IMGRFASE WIRE SIZE BY ONE AMERICAN HIM 6AU6E SIZE FOR EVERY
75 LINEAR FEET OF WIRE RUN.
E. SWITCHES,
1. SAFE=TY SWITCHES SHALL BE HEAVY DUTY, SIZE AND ELECTRICAL
CHARACTERISTICS INDICATED, SURFACE MOUNTED, FUSIBLE RATES AT
250 VOLTS ON THE 206 VOLT SYSTEM AND 600 VOLTS ON THE 460
VOLT SYSTEM, AMPERE RATIN65 AS NOTED ON THE DRAWIN65, 60
HERTZ, THE (3) BLADES, I NGORPORATI N6 QUICK- MMAKE, QUICK-
BREAK TYPE SHITCEES.
2. FUSISs UN.E % INDICATED ON THE DRAWIN65 AS NON-FUSED TYPE,
PROVIDE FU5F5 FOR SAFETY SWITCHES. FUSE5 TO BE TIME - DELAY,
GURRBNr- LIMITING U.L. GLA% RKI, AND HAVE AN INTEERRUPTIN6
RATING OF 200,000 RMS AMPERES SYMMETRICAL.
3. DISCOMEG75 FOR 120 VOLTS, SIN5LF PHASE EQUIPMENNT SHALL BE
HEAVY DUTY TYPE SUITABLE FOR THHE SERVICE INTENDED. INCLUDE
THE F44AL OVERLOAD PROTECTION Ii TE6RAL_ WITH DISCONNECT FOR
MOTORS OR WERE REQUIRED BY CODE.
4. SWITCIE5 INSTALpL�EAD IN OUTDOOR LOCATIONS SHALL BE
WEATHERPROOF NB4A 3R.
5. PROVIDE B46FAVM NA EPL ATE FOR EACH DISCONNECT SWITCH
INDICATIN6 VOLTA6E, PHASE, LOAD SERVIED, AND GIRCIIT ORI6IN.
F. LI6HTIN6 AND POWER PM 3MAFWS
I . PROVIDE DEAD- fRON'T SAFETY TYPE LI6H'TIN6 AND POWER
PANEJ30ARD5 AS INDICATED, WITH SWITWIN6 AND PROTECTIVE
DEi/IGLi IN QUANNTITIES, RATIMN65, TYPES AND iAFRNN6E4BNr AS -
SHOWN, EQ)IPPED WITH STANDARD " ►HAKE, FuLa -5mED tH''TI'.AL
BAR, WITH PLUG - I N TYPE MOLDED :.A=SE k3RAtvG - (_-1 k J) r T Btf1lCEJZc_-
FOR EACH CIRCUIT, WITH TO66LE'-WVLM THAT.IN016ATE M;e4
TRIPPED. PROVIDE A BARE UNIN5UL.ATED 6ROUNDIN6 BAR SUITABLE
FOR BOLTIN6 TO HNGL05URE. PROVIDE TYPED DIRECTORY. (PANELS
ARE EXISTIN6 /RELOCATED /REJSEDJ --
2. PROVIDE EN6RAvED NMB'LATE FOR..FAcm Pmp_boARU INVIGA'FIN6
VOLTA6E, PHASE, PANES_ NAME, ;SAND FIRMER OR16I N;
3. MANUFACTURER SHALL PROVIDE I4''.*23U TDZ XkT:tW-j FOR ALT; _ -
EQUIPMMENT BASED ON FAULT CLAaa!NT SHOWN ON PLANS. SERIES
RATED EQUIPMENT SHALL BE LABELED 05ERIE5 RAT® - REPLACE
WITH IDENTICAL COMPONENT PART5' WITH PERMANENT LABEL.
4. ALL CIRCUIT BREAKERS SERVIN6 HID LI6HTIN6 SHALL PROVIDE HID
CIRCUIT BREAKERS.
5. ALL CIRCUIT BREAKERS SERVING AIR CONDITIONING EQUIPMENT
SHALL BE 'HACR' RATED TO COMPLY WITH EQUIPMENT LI5TIN6.
6. PROVIDE NEW CIIRCUIT BREAKES IN EXISTIN6 PANELS FOR NEW
LOADS SHOWN. NEW CIRCUIT BRFAKER5 SHALL MATCH D(ISTIN6
PANEL U.L. LI5TIN6.
I. PROVIDE ARC -FLASH HAZARD LABEL ON ALL PAMNIELBOARDS.
8. REPLACE ALL DEFECTIVE GIRC)IT BREAKERS IN EXISTING PANELS.
6. 6ROUNDIN5
I . ENTIRE POWER SYSTEM SHALL BE EFFEGTI VELY 6ROUNVIE D, I NCLUD I N6
ALL EXPOSED NON - CURRENT GARRYIN6 PARTS OF ELECTRICAL
EGI)IP1ENr IN FULL ACCORDANCE WITH N.E.G. ARTICLE 250.
2. A 6REBN PI6TAIL SHALL 13E INSTALL FROM 6ROUINDIN6 SLOTS OF
6ROUNDINS OUTLETS TO OUTLET BOXES IN EACH INSTANCE WF$RE
RECEPTACLE ATTACHMENT BAR 15 NOT IN DIRECT CONTACT WITH THE
OUTLET BOX.
3. PROVIDE 6ROUND RODS AND GADWH_D 6ROUNDIN6 CONDUCTOR TO
BUILDIN6 STEEL N INDICATED ON PLANS.
4. EXTEND 6ROUND TO (DOMESTIC WATER MAIN.
5. THE IDX I5TI N6 BU I LD I N6 SYSTEM 61ROUND SHALL BE EXTENDED TO ALL
NEW WORK.
6. TEST 6ROUND SYSTEM AFTER INSTALLATION FOR A MAXIMUM 5 OHMS
TO 6ROUND AS MEASURED IN FEBRUARY. PROVIDE ADDITIONAL
GROUND RODS AS REQUIRED.
7. ALL METAL PIPING, SYSTEMS, DIJGTYNOTRK AND STEEL FRAMES SHALL
BE BONDED TO ELECTRICAL SYSTEMS IN COMPLIANCE WITH THE
N.E.G.
H. LI6HTINN6
1. FURNISH AND INSTALL LI614TINN6 FIXTURES WITH LAWS AS SHOWN
AND SCHEDULED ON THE DRAWINN65.
2. COORDINATE FIXTURE TYPE AND TRIM WITH GEILINN6 CONSTRUCTION.
3. ALL LAMPS SHALL BE RATED BY MANUFACTURER FOR INSTALLATION IN
SPWIFIED FIXTURE.
4. ALL FIXTURES IN LAY -IN CEILING SHALL BE SUPPORTED FROM THE
STRICTURE INDEPENDENT OF THE CEILIN6 5YSTIEM AT ALL I-" (4)
CORNERS AND ATTACH® WITH 6RID CLIPS.
5. THE MANUFACTURER OF EACH LI6HTIN6 FIXTURE SHALL MVIEW THE
APPLICATION OF HIS E:QJIPMENT AND CERTIFY AT THE TIME OF SHOP
DRAWIN6 SUBMITTAL THAT HIS FIXTURE HAS BEEN PROPE14 -Y APPLIED
AND CAN BE INSTALLED, MAINTAINE=D AND SERVICED WHERE SHOWN ON
THE DRAWIN65.
6. ALL FLUORIE5GENT LAMPS SHALL BE COLOR GORFE6111EP, TRI- PHOSPHOR
LAMPS OF COLOR TEMPERATURE SPECIFIED. ALL LAW'S SHALL BE BY
THE SAME MANUFACTURER AND BE 6.E. SYLVANIA- OSRA M, OR
PHILLIPS. IF NO COLOR 15 SPWIFIED, IT WILL BE SELECTED BY
THE ARCHIITECT.
I. E4ER6EJCY LI6HTIN6 AND EXIT 5I6N5
1. FN)RNNISH AND INSTALL BATTERY POWERED E•Ea5ENGY LI6HT5 AND
EXIT SI615 AS SHOWN AND SCEVULED ON THE DRAWIN65.
2. THE WIRIN6 AND INSTALLATION SHALL CONFORM TO THE
MQUIRB•ENT5 OF THE N.E.G. AND NFPA LIFE SAFETY CODE.
3. BATTERY PACKS I NTE6RAL TO FLUORESCENT FI MURE5 SHALL_ PROVIDE
A MINIMUM OF 1400 LUMENS AND OPERATE TWO LAMPS IN EACH
FIXTURE.
J. TEMPORARY '
1. THIS CONTRACTOR TO PROVIDE ALL TEMPORARY LI6HTIN6 AND POWER
AS R5QUIR13) FOR ALL TRADES. I I
2. ALL TEMPORARY WIRIN6 INSTA SHA 13E M14JVED BY. THIS. , '
L LL
CONTRA CTOR.
K. TELEPHONE �ERVICE '
I. SERVICE CONSISTS OF MROUTINf THE EXISTING CONDUIT SYSTEM
INCOMIN6 SERVICE AS INDICATED ON DRAWIN65. • ►
2. PROVIDE 3/4' FIRE RETARDANT TREATED PLYWOOD BACKBOARDS WHERE
INDICATED ON MNIN65 FOR USE BY TELEPHONE SYSTEM.
BACKBOARDS SHALL BE PAINTED BOTH SIDES WITH TWO (2) COATS OF
6RAY ENAMEL PAINT. PROVIDE 120 VOLT DUPLEX MCEPrAC.E
ADrA CENT TO THE RI6HT SIDE LOCATED 'V-62 A.F.F. , •
3. PROVIDE #6 AW5 COPPER WIRE OR 3/4' CONDUIT FROM BACKBOARD TO
MAIN BUILDIN6 6ROUND.
4. PROVIDE EMPTY CONDUIT SY5TE4 WITH PULL CORD FROM EACH NEW
OUTLET LOCATION TO TELEPHONE BOARD AS SHOWN ON DRAKIN165.
5. ALL OUTLET LOCATIONS SHOWN ON DRAKIN6 ARE TO BE VERIFIED
WITH THE OWNER PRIOR TO ROUGH -IN.
6. OUTLET BOXES TO BE 4' SQUARE WITH SIN6LE COVER PLATE AND
OUTLET NOTE=D ON DRAWIN65. .
L. POWER SERVICE
1. SERVICE SHALL BE AN EXTENSION OF THE EXISTING CONDUIT SYSTEM
FROM HALL SERVICE TO PANEL 'H.'
2. CONTRACTOR SHALL FULLY COORDINATE SERVICE INSTALATION WITH
MALL. AND PROVIDE AL FACILITIES REQLUIRED BY THE MALL TO
COMPLETE THE INSTALATION, INC_UDIN6 INDIVIDUAL M TERIN6 FOR
SPACE, CONDUIT AND WIRE.
3. E.EGTRIGAL CONTRACTOR SHALL VERIFY EXISTING CIRCUIT LOADS
PRIOR TO EXTENDIN6 OR CONNECTIN6 TO NEW MVICE5. MAXIMUM
CIRCUIT CAPACITY SHALL NOT E XC.EE PER D 1600 WATTS P 20 AMP
CIRCJIT. • " '
M. DEMOLITION
I. THIS CONTRACTOR SHALL PERFORM ALL DEMOLITION OF 1:XISTIN6
ELECTRICAL SYSTEMS AS INDICATED ON ELECTRICAL AND
ARCHITECTURAL PLANS OR NECE55ARY FOR THE PROJECT. REMOVE
FROM SITE AND PROPERLY DISPOSE OF ALL MATERIAL AND DEBRIS
FROM THIS WORK.
2. ALL EXI5TIN6 LI6HTS, CONDUIT, WIRE AND DEVICES IN PROJECT
AREAS SHALL L BE REMOVED AND D15PIOSO OF, EXCEPT AREAS LEFT TO
LANDLORD. REMOVE CONDUITS BEYOND NEW SURFACES. REMOVE ALL
EXI5TIN6 WIRE FROM CONDUIT BACK TO POINT OF COMMON USE OR TO
PANELS. LABEL EXISTIN6 CIRCUIT BRFJAKER5 'SPARE' IF NOT
RE)S. W FOR NEW WORK.
3. DISCONNECT EXISTIN6 EGUIPMENT IN BUIL.DIN6 THAT IS TO BE
RB40VED UNDER OTHER SECTIONS.
4. THE ELECTRICAL CONTRACTOR SHALL INSPECT EXISTING CONDITIONS
AND EWIPMENT FOR CURRENT CODE VIOLATIONS AND INCLUDE IN BID
THE AMOUNT TO CORRECT THESE VIOL .MOMS: • •
5. ALL DXISTIN6 CIRCUITS REQUIRED TQiREMAIN'ACTIVE SHALL bE' '
RHKORKED OR MAINTAIN® AS REQUIRED. -(-'.%! !'>;' .
6. ALL EXISTIN6 DATA, PHONE AND OTHER COMUNICATIONS SY57E S
GABLES NO LONGER REGVIRLD SHALL Bit ;REMOVE3D COMPLETELY BY
THIS CONTRACTOR. NO GABLES SHALL. BE CUT,-oR'R@MOVED UN.E56
a*435 COMMUNICATION SYSTEMS PERS 0WEL. HAVE-APPROVED
REMOVAL. , '' i, , ,
i I
t1,
""'h
;A, �,�'
f.
�� e /
1` , �'4 �
' ++�
.
,
41
1`.I
CONTRACTOR per,- .VERIFY
ALL CMS `
DIMEN510NS'IN FI, >t .,
,
1. I,
i i; r & &I,- , , '� " 1. ?� '
*AI t
McHENRY & ASSOCIATE' INC. i.' i'
CONSULTING. ENGINEERS
25001 EMERY ROAD, r10TE c4200'� *
WARRENSVILL�• HEIGHT101,,441 A
Phone: (216) •292- Q4696,4.'i '•' .»r;
Fax: (216) 292 "58ZR rr,'yr rr. f
Email: MAIL ®MCHENRYASSOCIATES,CO0v
FLORIDA BUSINESS #0005282
Design and Aonstiuotion documents
as instrumeAts of sorylos, are given
in conf, ce and4remaw the property
of Hers men Arehlticts. The use
of this design and these construction
documeV;b%lt,,*d%,' purposes other than
the spe t named herein Is
atActy ',Without exp ressed
written ooh�snt f Hsrsohman
Architects, Inoorpersteit
Date ,r 4` 1 sue
AA 4r
09 -28-05 BID/PERMIT
•
•
•
�"
Lb
f"1
•
. �'
1 `�
.
01.
1• 4,'_ 1
eR
a
"
.
. t�
•
,
*_ . - 4 .
Drawl
DAT A„'
Pro jfNo.:
9181.00
" , 1
'�
I "'�'-�
� ,_
'
vsrli�
'�...01
0 h
411�1;: : '
,
10, ,-#
6w-'�
"'
' .)
.` j.
011FA
HERS(
ARCF
I N C O R I
25001 EMERA ROM ATE 400
CLEVELAND, 44128
TEL (216) Z2 ,V 3200
FAX (216)%03-3210
www.herschmanarchitects.com
FLORIDA LICENSE
N0. AA0003208
ME1