05-676-018I� 4 NO O N 0 N a EQUIPMENT �fHFT�II F MNIU /1 - AIR HANDLING UNIT EXI5TIN6 HORIZONTAL UNIT RBOGATED, 3000 C-M a 1.2' S.P., 52.8 MEN TOTAL COOLING CAPACITY, 30.4 MBH SENSIBLE COOLIN6 CAPACITY, 74 F E7B, 70 F E3°B, 45 F E14TERIN6 CHILLED WATER TEMPERATURE, 10 F CHILLED WATER TEMPERATURE RISE, 11.0 6PM CHILLED WATER FLOW RATE, MAXIMUM WATER P.D. 15', 15.0 KW HEATIN6 CAPACITY, 874 RPM, 2.4 HP BLONER MOTOR, 46013160, 25.8 MCA, 30.0 HOOP. UNIT TO BE MOUNTED ON SUSPENDED STEEL_ FRAME, HEN SET OF FILTERS, PROVIDE FLEXIBLE DUCT CMECTIONS,6ALVANIZED DRAIN PAN, WITH PRIMARY AND SECONDARY DRAIN CONNECTIONS. REFi3R TO PLANS FOR MINIMUM OUTSIDE AIR SETPOINTS. REfEt TO 5PECIFICATIONS FOR CONTROL. R6QUIRIalENTS. OPERATIN6 WEI6HT = 400#. AHU /2 - AIR HANDLING UNIT ED(I5TIN6 HORIZONTAL UNIT RELOCATED, 6800 CFM 0 1.2' S.P., 265.1 MBH TOTAL COOLIN6 CAPACITY, 151.5 MBH SEI5IBLE COOLIN6 CAPACITY, 74 F EDB, 70 F E^B, 45 F E1IE IZIN6 CHILLED HATER TEMPERATURE =, 10 F CHILLED WATER TEMPERATURE RISE, 53.2 6PM CHILLED WATER FLOW RATE, MAXIMUM WATER P.D. 15', 30.0 KW HBkTIN6 CAPACITY, 468 RPM, 7.5 HP BLONER MOTOR, 460/3/60, 25.8 MCA, 30.0 MOCP. UNIT TO BE MOUNTED ON SUSPENDED STS FRAME, NEW SET OF FILTE3RS, PROVIDE FLEXIBLE DUCT CONNECTION5,6ALVANIZED DRAIN PAN, WITH PRIMARY AND SECONDARY DRAIN CONNECTIONS. TO PLANS FOR MINIMUM OUTSIDE AIR SETPOINTS. TO S EGIFICATIONS FOR CONTROL REQUIRBMENTS. OPERATING MEI6HT = 725 #. AHU/3 - AIR HANDLIN6 UNIT DU5TIN6 HORIZONTAL UNIT RELOCATED, 6120 GFM a 1.2' S.P., 215.7 MBH TOTAL COOLIN6 CAPACITY, 140.6 MBH SENSIBLE COOLIN6 CAPACITY, 74 F EDB, 70 F E3^B, 45 F E3NTERIN6 C IILLM WATER TEMPERATURE, 10 F CHILLS WATER TEMPERATURE RISE, 43.0 6PM CHILLED WINTER FLOW RATE, MAXIMUM WATER P.D. 15', 30.0 KW HFJITIN6 CAPACITY, 878 RPM, 5 HP BLAMER MOTOR, 460/3/60, 54.1 MCA, 60.0 MOCP. UNIT TO BE MOUNTED ON SUSPENDIEED STEEL FRAME, NE N SET OF FILTERS, PROVIDE FLEXIBLE DUCT COM6CTION5,6ALVANIZED DRAIN PAN, WITH PRIMARY AND SECONDARY DRAIN CONNECTIONS. REFER TO PLANS FOR MINIMUM OUTSIDE AIR SETPOINTS. REF62 TO SPECIFICATIONS FOR CONTROL.. RSWIREENTS. OPE3RATIN6 MEI6HT = 725 #. VT/I VOLUME CONTROL TERMINAL - TRAM= MODE_ V60F -08, 8' DINIETIER TERMINAL WITH MAX PRESSURE DROP FROM INLET TO OUTLET = DA5'. COMPLETE WITH FLOW LOGIC, CONTROLLER AND MATCHIN6 ELECTRONIC WALL MOUNTED THERV57AT, AIR® AND INSTALLED BY MSG., AND MATCHING 24 VAC, CONTROL TlWeFORMER. ED/1 AND 2 - TOILET ROOM EXHAUST FANS - PENN ZEPHYR MODE- Z5H, CENTRIFU6AL FAN, 130 CFM o 0.25' ESP, 74 WATTS, 120/1/60, WITH NHITE GEIL I N6 6RI I I E, 6RAV I TY BACKDRAFT DAMPER, AND FLEXIBLE DUCT COLLAR CONNECTION. ELECTRICAL CONTRACTOR SHALL INTERLOCK WITH REST ROOM 1-I6HTS. CD /I CEILING DIFFUSER - TITUS MODEL TMR, SURFACE MOUNTED, STEEL, PRIMED FOR FIELD PAINTING, WITH OPPOSED BLADE DAMPER. ALL TYPE CD /I DIFFUSF35 IN SALES ARFJI SHALL. BE 24' DIA. NErK (43 -1/4' OUTSIDE DIAMETER). NO 011-IER SIZE DIFFUSERS WILL BE PERMITTED. TYPICAL. 0/2 CEILIN6 DIFFUSER - TITUS MODEL PMG, 2024 MODULE, LAY -IN WITH TRM RAPID MOUNT FRAME, STEEL, MITE, WITH OPPOSED BLADE DAMPER. CD13 GEILIN6 DIFFUSER - TITUS MODE_ PMC, 24X24 MODULE, SURFACE MOUNTED, STEEL, WHITE, WITH OPPOSED BLADE DAMPER. SR/1 SUPPLY RE6IS TER - TITU5 MODE.. 30011_, DOUBLE DEFLECTION, SURFACE MOUNTED, STEEP., WHITE, WITH OPPOSED BLADE DAMPER. 611 FETUARN GRILLE - TITUS MODE- PAR, LAY -IN, STS., WHITE, 24x12 MODULE. 6/2 RETURN 6RILLE - TITUS MODEL 35ORL, SURFACE MOUNTED, STEEL, AND WHITE. NOTED FOR 6RILlE5 AND DIFFUS_ERSP: A. EG1l1IVALENT BY AHR40 TAT, PRICE, KRUE6Et OR NAIL.OR INDUSTRIES B. EQUUIVALENT DIFFUSERS SHALL HAVE MAX NG RATIN6 OF 22 FOR CR4 LISTED ON PLANS. G. 5UBMITTALS MUST IDENTIFY DIFFUSER LOCATIONS BY ROOM NUMBER, TYPE, 4 TYPE OF CEILINN6 CONSTRUCTION. D. ALL FRAME TYPES SHALL BE COMPATIBLE= WITH ADJACENT CONSTRUCTION. REFER TO ARC41TECTUAL PLANS FOR CONSTRUCTION DETAILS. E. PROVIDE SQUARE TO ROUND NECK TRANSITIONS WHERE ROUND DUCTS SERVE SQUARE HECK DIFFUSERS. - :. `XR OR - * - -x - * - FOISTING TO BE REMOVED 'X' OR - - - - - - - EXISTING TO REMAIN GTX C -a O I _. CHILLED WATER SUPPLY GHWS C GHHLLLD WATER RETURN C+IHR G C,D C CONDENSATE DRAIN r• ; • c � _ • e � - C COMBINATION SIWTOFF 4 BALANCE VALVE MODULATING TWO WAY CONTROL VALVE MAX DELTA P= 5 FT. 10' THERMOMETER PETES PLUGS MANUAL AIR VENT • a- a 11 ►1► :e • _ AIR TRAM DUCT EA E EXHAUST AIR OA O OUTSIDE AIR RA R RETURN AIR 5A S SUPPLY AIR MVD M MANUAL VOLUME DAMPER SENOR TD T THERMOSTAT ®V--i D DUCT SMOKE DETECTOR TO SHUT DOWN UNIT UNDER ALARM. DETECTOR SHALL BE LOCATED, INSTALLED AND MREED AS INDICATED ON FLOOR PLAN AND SPEC-- IFICATTONS. ALL WIRING TO BE M CONDUIT PER NEL. ® U UL L151® FIRE DAMPER TYPICAL DUCT TAKE -OFF DETAIL NTS 6ENERAL N= A WAiIWICAL CONTRACTOR SHALL VISIT SITE PRIOR TO BIDDIN6 PROCESS AND FIELD VERIFY EXISTING CONDITIONS. CONTRACTOR SHALL TAKE ALL I INTO CONSIDERATION. PROVIDE ALL NECESSARY OFFSETS OR TRANSITIONS WITH EQUIVALENT AREAS TO MATCH DUCT SIZES AS INDICATED ON DRAWINGS. B CONTRACTOR SHALL BE FAMILIAR WITH LANDLORD'S STANDARDS, RULES AND RE6ULATION5. ALL LANDLORD CRITERIA SHALL BE COMPLIED WITH AND INCLUDED IN THIS BID. G MAINTAIN ALL MANUFACTIRER'S RECOMMENDED SERVICE CLEARANCES FOR ALL EQUIPMENT. D ALL CEILING DIFFUSERr' SHALL HAVE MANUAL VOLUME DAMPERS IN G4RRESPONDIN6 SUPPLY AIR RUNOUTS. E CONTRACTOR SHALL- PAINT INTERIOR OF ALL DUCTS VISIBLE FROM SALES FLOOR TO MATCH THE UNDE-R5IDE OF FLOOR ABOVE. F ALL DUCThORK SHALL BE INSTALLED TI6HT TO UNDESIDE OF STRUCTURE ABOVE. 6 NO THERMOSTATS ARE TO 13E LOCATED OV 13Z HEAT PRODUG I N6 EQUIPMENT. H THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS, LICENSES, DOCUMENTS AND SERVICES RELATED TO INSTALLATION OF THE WORK. I HVAC DUCThORK SHALL BE FABRICATED AND ERECTED IN ACCORDANCE WITH ASHRAE AND LATEST SMAC.NA STANDARDS. PROVIDE TURNIN6 VANES IN ALL ELBONS. J SPRIHKIBR CONTRACTOR SHALL MODIFY EXISTING SPRINCLER SYSTEM AS REQLUIRED TO CONFORM TO NEH DUGTHORK, LI6HTIN6, AND PARTITION LAYOUTS. K R TO ARCHITECTURAL MMIN66 FOR EXACT LOCATIONS OF ALL CEILING DIFFUSEZS. L MEC.HANIC PROGES, SHALL TAKE AL NECESSARY 0 MATE MECHANICAL LEGEND `XR OR - * - -x - * - FOISTING TO BE REMOVED 'X' OR - - - - - - - EXISTING TO REMAIN GTX C CONNEGT TO EXISTING O I INDIGATE5 COD® NOTE CHILLED WATER SUPPLY GHWS C GHHLLLD WATER RETURN C+IHR G C,D C CONDENSATE DRAIN 5EGONDARY DRAM SD 5 - go-- S SHUTOFF VALVE - C COMBINATION SIWTOFF 4 BALANCE VALVE MODULATING TWO WAY CONTROL VALVE MAX DELTA P= 5 FT. 10' THERMOMETER PETES PLUGS MANUAL AIR VENT -III -- U UNION OR FLANGED COMlBCTION ATD A AIR TRAM DUCT EA E EXHAUST AIR OA O OUTSIDE AIR RA R RETURN AIR 5A S SUPPLY AIR MVD M MANUAL VOLUME DAMPER SENOR TD T THERMOSTAT ®V--i D DUCT SMOKE DETECTOR TO SHUT DOWN UNIT UNDER ALARM. DETECTOR SHALL BE LOCATED, INSTALLED AND MREED AS INDICATED ON FLOOR PLAN AND SPEC-- IFICATTONS. ALL WIRING TO BE M CONDUIT PER NEL. ® U UL L151® FIRE DAMPER WITH DUCT ACGE95 DOOR 7 OFFSET PIPING AND UNIONS FOR COIL REMOVAL DO NOT BLOCK AGCE % TO UNIT. O2 SEE PlAN5 FOR PIPE SIZES 0 PROVIDE REDUCERS TO COIL AND CONTROL VALVE CONNECTON5 A5 REGU IRE D - TYPICAL ® MAXIMUM CONTROL VALVE PRE55URE DROP 8A FT W.G. ` ©I F— AIR FLOW CHILLED WATER COIL PIPING DIAGRAM WITH 3 -WAY VALVE NT5 I REMOVE EXISTING I X - I F04OVE EXISTING AT D RELOGATTE T I ' 'I`- 2 AND RELOCATE -I � * * -1 � �C 2-In' -X -X -X r 14 EB I �I SCI III I I I I I i I i INDICATES I AM TO � CAPPED REMOVE EiS'nN& � I i I sD I i QgI TYPICAL AIR RlWDLLINS UNIT 3 I YI T AND RELOCATE I I bb I I I I m —J �D 1 -1/4' i ( I i 2 i STOCKROOM _ _ II III i Iv Ow I ft M WATER PIPING EXISTING CHILLED X -5' CHW54R �- 7 –1-4 -- - - - - -- ----- - - - - -- — b' X-.CAH1N5 — — — — b' X-C+M l i , H /4' i -�2> OFFICE I-N/4 MEN MEN PITCH WO - - j, O 1 I I CORRIDOR F2 I I CLEANOUT TYPICAL � 5 IIA GPM I Y GORED NOTE 5L 0 1 4' DES SEAL CONDENSATE TRAP WITH U-EANOUT AT PRIMARY AND SECONDARY CONDENSATE DRAIN CONNECTIONS - PITCH DRAIN LINES IN DIRECTION OF PLOW AT 2% SLOPE MINIMUM. (SEE PLANS FOR CONTINUATION) 2 UNIT TO BE SUPPORTED ON STEEL FRAME PROVIDED 13Y 6.6. UNIT TO 13E MOUNTED ON SPRIN5 ISOLATORS. 3 PIPE SECONDARY CONDENSATE DRAIN INDEPENDANT OF AND AD_IAGENT TO PRIMARY CONDENSATE DRAIN. Rt3=H2 TO PLANS FOR CONDENSATE: PIPE SIZES. 6BNERAL HOTES t O FAN SECTION ® COOLING COIL SECTION -- SEE CHILLED WATER COIL PIPING DIAGRAM O FLEXIBLE C 4ECTION DO ELECTRIC, HFJITING SECTION O FILTER SECTION WITH 2' THROWAWAY FILT19Z5 WITH SPARE SET. NOTE:_ THE ABOVE EQUIPMENT 15 DQ5TIN6 RELOCATED TO NE N AREA. LINE OF STRUCTURE � .I 10l lol Iro I'I �^�• I' STS. FRAME BY 6G'I `'J \-CONTRACTOR SHALL PROVIDE A 2' DEEP 6ALVANIZED STEEL SECONDARY SLOPED DRAIN PAN WHICH 15 INDEPEN!>ENTL.Y PIP® TO THE BUILDING CONDENSATE �,;MAIN. PAN SHALL BE FULL SIZE OF UNIT. AIR HANDLING UNIT DETAIL 5CALFS NOME 0 0 2-In' - - - - - - - - - - - - -- 1 11 I— —I - -I- 'TYPI L_ X- -I 1 44 I II I I I II 1 I I INDIGATE 5 I i PIPIN6 TO BE GAPPED k' I I 6' X- CHN54R I I i MECHANICAL PIPING FLOOR PLAN 1/8' = I' -0" 4) MECHANICAL PIPING FLOOR PLAN CODED NOTESr O 1 INDICATES EXI5TIN6 AIR HANDLING UNITS TO 13E REMOVED AND RELOCATED. DISGOMN� -CT PIPN6 BACK TO MAIN5 AS REQUIRED AND CAP. CARE I5 TO 13E TAKEN WITH PIPIN6 AT CHILLED WATER COILS. RE LOCATE ALL VALVE-SP AND APPURTENANCES .VINN6 COIL. 2 PRIMARY AND SECONDARY CONDENSATE PIPING TO BE COMECTED TO BUILDING CONDENSATE DROPS. 3 PITCH CONDENSATE DRAINS DOWN TOWARD BUILDING CONDENSATE DRAINS AT 1 /8' PER FOOT. 4 CONNCGT 3' CHILLED HATER SUPPL AND RETURN PIPING TO E XISTIN6 5' MAINS WHit3RE DIRECTED BY THE MALL MAINTENANCE DEPT. 5 EXISTIN6 AIR HANDLIN6 UNIT IN NENLOCATION. RECOMIEGT PIPING, VALVES, ETC. FOR A FULLY AUTOMATIC AND FUNCTIONAL SYSTEM. REMOVE EXI5TIN6 AIR HANDLING UNIT REMOVE PIPIN5 BACK TO WALL 4 GAP GONTRAGTOR t4JST VERIFY ALL GLEARANGt9 AND 0IMEN510NS IN FIELD C • McHENRY & ASSOCIATES, INC. CONSULTING ENGINEERS 25001 EMERY ROAD, SUITE #200 WARRENSVILLE HEIGHTS, OHIO 44128 Phone: (216) 292 -4696 Fax: (216) 292 -5874 Email: MAIL@MCHENRYASSOCIATES.COM FLORIDA BUSINESS #0005282 Design and construction documents as Instruments of service are given In confidence and remain the property of Herschmen Architects. The use of this design and these construction documents for purposes other than the speolflo project named herein Is strictly prohibited without expressed written consent of Hersohman Architects, Incorporated. Date I Issue 03 -28-05 BID/PERMIT • • • • • • • Drawn By. XXX Project No.: 9181.00 7/ W V Q J CL W Z D CO) J LL w M CO Q O CL p� CO) W,_- -Q F- it IN HERSCHMAN ARCHITECTS I N C O R P O R A T E D 25001 EMERY ROAD, SUITE 400 CLEVELAND, OH 44128 TEL (216) 223 -3200 FAX (216) 223 -3210 www.herschmanarchitects.com FLORIDA LICENSE N0. AA0003208 M2 (V� l - - 1