EXISTING 2000 A. BUS DUCT
208Y 120V. 3PH. 4W.
FROM FPL.- --i
O EXISTING
PANEL
"MDP"
METER FXIRTING 3 I
2000 I) —MAIN
of 1
65000 Al
1
I- -1 #3/0 THWN - 3/4" GND.
NOTE: FOR CONDUIT WIRE SIZES
SEE PANEL SCHEDULES. (TYP.)
NOTE: FOR CONDUIT WIRE SIZES
SEE PANEL SCHEDULES. (TYP.)
200A -3P
200A 3P 200A -3P =
PANEL PANEL PANEL PANEL PANEL PANEL
L1 L2 RPA CL RPB PA
7
1 CONNECT TO TWO 5/8" x10' GND. RODS
SPACED 6' FT. BOND TO A 3/4" COPPER
WATER PIPE STUB -OUT.
REF: ELECTRICAL SYMBOL
LEGEND SYMBOL
GENERAL NOTES
1. ALL CONDUCTORS SHALL BE 98% COPPER (NO ALUMINUM CONDUCTORS WILL BE ACCEPTED).
2. ALL PANEL CANS SHALL BE A MINIMUM OF 6" IN DEPTH (EXCEPT "CPA- AND "CPB' PANELS).
3. COORDINATE WITH OTHER TRADES AND PROVIDE AS REQUIRED PER EQUIPMENT SUPPLIED.
4. WHEN MAIN DISCONNECT IS REQUIRED,BY AGENCY HAVING JURISDICTION CONTRACTOR SHALL FURNISH AND
INSTALL A QUICK MAKE, QUICK BREAK UNFUSED DISCONNECT OF PROPER RATING.
5. ALL CONTACTORS SHALL BE ELECTRICALLY HELD.
6. ELECTRICAL CONTRACTOR SHALL VERIFY THE COMPRESSOR UNIT LOADS WITH WINN- DIXIE'S MAINTENANCE
SUPERINTENDENT BEFORE ORDERING RDP PANELS & BREAKERS.
7. SHORT CIRCUIT PROTECTION: ENGINEER SHALL DESIGN THE ENTIRE ELECTRICAL DISTRIBUTION SYSTEM IN ACCORDANCE
WITH THE 1999 NEC INCLUDING ARTICLES 110-9, 110 -10, AND ALL STATE , LOCAL AND NEC REQUIREMENTS.
8. SWITCHBOARD "MDP" SHALL HAVE PERMANENT LABELS ATTACHED TO BREAKERS 1 -6 AS "MAIN DISCONNECT #1,
BREAKERS 1 -6 AS "MAIN DISCONNECT #1, MAIN DISCONNECT #2, ... ETC.
9. WHEN CHECK METERING POINTS ARE REQUIRED BY THE ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION,
CONTRACTOR SHALL INCLUDE PROVISIONS FOR METERING OF ELECTRICAL ENERGY CONSUMPTION
AS REQUIRED AT NO ADDITIONAL COST.
10. SEE MECHANICAL DRAWINGS, COORDINATE WITH MECHANICAL CONTRACTOR, AND PROVIDE /INSTALL AS
INDICATED AND /OR REQUIRED PER MECHANICAL EQUIPMENT SUPPLIED.
11. PROVIDE A PULLBOX BELOW PANEL. SIZE BOX IN ACCORDANCE WITH N.E.C. REQUIREMENTS. CONTRACTOR
12, SHALL VERIFY WIRE SIZES WITHIN PULLBOX PER DERATING REQUIREMENTS OF THE N.E.C.
ALL MAIN SERVICE ENTRANCE EQUIPMENT TO BE U.L LABELED I.E.R. (INTERGRATED EQUIPMENT RATINGS)
LABELED I.E.R. (INTERGRATED EQUIPMENT RATINGS) LISTED TO MEET AND PROTECT AVAILABLE FAULT CURRENT
FROM LOCAL UTILITY COMPANY. REFER TO N.E.C. ARTICLES 110 -9. 110 -10. 240 -11 AND 240 -82. VERIFY
AVAILABLE FAULT RATING WITH POWER COMPANY PRIOR TO ORDERING PANELS. THE AVAILABLE FAULT CURRENT
CANNOT BE SET AT THE TIME OF DESIGN BUT WILL BE AVAILABLE AFTER POWER CO. SELECTS TRANSFORMER. CALL
LOCAL POWER CO. PRIOR TO BID FOR AVAILABLE FAULT CURRENT AND PROVIDE AS REQUIRED AT NO ADDITIONAL COST.
13-ELECTRICAL SHOWN DASHED SHALL BE FURNISHED AND INSTALLED BY OTHERS.
14.THE TWO TRANSFER SWITCHES SHALL BE RATED 125 AMP, 30, 4 WIRE SUITABLE FOR EMERGENCY
GENERATOR SERVICE. COMPLETE INSTALLATION SHALL COMPLY WITH MANUFACTURER AND
ALL 1999 NEC, STATE, AND LOCAL REQUIREMENTS.
15-ALL BUSSING IN SWITCHBOARDS AND PANELBOARDS TO BE COPPER.
CWITC`NR(1AR11 k CFRVIf`P nprm 1NIUAIn
F----*---'�%%'-%'-'-*-'-, .... .................... ................................... NEIl TRAL'.'............... ............................................. ...............................
SIZE PER NEC TO TRANSFORMERS
AND PHONE BACKBOARDS
LINK............................
... ................. ....GROUND - BUS..............
GRADE
i +
I B ND T , ,_
SYSTEM
CADWELD
(TYPICAL)
3/4" x 10'
GROUND ROD
(TYPICAL)
VALVE,
SERVICE METER SUPPLY
,NCE OR UNION SIDE
JUMPER
BRANCH CIRCUITS
SIZE PER NEC
(TYPICAL)
TO SWITCHBOARD
ENCLOSURE -SIZE
PER ART 250 -95
I N BUILDING
R STRUC. STEEL
CADWELD
GROUND CLAMP
UL APPROVED
NOTE:
ALL GROUNDING CABLES SHALL BE SIZE #4/0 MINIMUM
UNLESS OTHERWISE SPECIFIED OR INDICATED OTHERWISE.
NIP-1 ITRQI /(:R(11 INlfllNl(` CYqTP-NA f1P-TAll
NOT TO SCALE
NOTE: FOR CONDUIT WIRE SIZES
SEE PANEL SCHEDULES. (TYP.)
FIRE S IN EXHAUST
HOODS. . SWITCH BY OTHERS.
r WIRE BY CONTRACTOR.
PANEL
PD
SHUNT TRIP STATIONS TYPICAL OF 2
LOCATED IN DEU /BAKERY
225 A.
2-3P I I AUTOMATIC TRANSFER
SWITCHES (REF: E -607)
PANEL PANEL PANEL PANEL PANEL PANEL
PH PB PM PMA PLN CR
REF: GENERAL
NOTE 14.
ELECTRICAL RISER DIAGRAM
NOT TO SCALE
NOTES: (FOR RDP PANEL)
I. BALANCE ALL LOADS BETWEEN PHASES,
2. VERIFY BREAKER SIZES WITH WINN DIXIE REPRESENTATIVE BEFORE
ORDERING' RDP' PANEL AND BREAKERS,
3. * ** CIRCUIT SHALL BE MODIFIED PER MECHANICAL EQUIPMENT SUPPLIED.
SEE MECHANICAL DRAWINGS AND COORDINATE AS REQUIRED.
DISTRIBUTION EQUIPMENT LEGEND
PANEL
DESCRIPTION
PANEL
DESCRIPTION
LL
LANDLORD LIGHTS PANEL
PHA
120 V. REFRIGERATED CASE CONTROL CIRCUITS
CC
I REFRIGERATED CASE CONTROL CIRCUITS
PL
120 V. LIGHTING PANEL
CL
120 V. CASE LIGHTING PANEL
PLL
120 V. LIGHTING PANEL
CPA,CPB
COMPUTER PANEL (EMERGENCY POWER)
PM
POWER PANEL
CR
CUTTING ROOM PANEL
PMA
POWER PANEL
EM
EMERGENCY POWER PANEL
PS
EXTERIOR SIGN PANEL
MDP
MAIN DISTRIBUTION PANEL (SWITCHBOARD)
RDP
REFRIGERATION DISTRIBUTION PANEL
PD
DELICATESSEN /BAKERY PANEL
PH,PHA
120 V. REFRIGERATED CASE CONTROL CIRCUITS
SS
SURGE SUPPESSOR
-MAINTENANCE NOTE: FOR CONDUIT WIRE SIZES
BY -PASS SWITCH SEE PANEL SCHEDULES. (TYP.)
REF: E -607
SS SS
PANEL PANEL PANEL LOCATED IN
EM CPA CPB COMPUTER ROOM
REF: E -607
REF: E -607 REF: E -607
lb-�- -SHUNT TRIPS LOCATED IN MEAT
CUTTING ROOM dt SEAFOOD DEPT STARTING
WIRING
LMANAG R'S I� 3
OFFICE
NOTE: VERIFY REQUIREMENTS FOR
GENERATOR INSTALLATION WITH MANUF.
SPECS. AND INSTALL AS REUIRED.
NEW EMERGENCY GENERATOR 70 KW
120/208V, 30, 4W
BY KATOLIGHT CORPORATION
MODEL 70FPG4
MANUF. TELE. (507) 625 -7973
INTERNET: http: / /www.Katolight.com
OR EQUAL MUST BE APPROVED BY "W.D."
�.-1 #4 - 1 1/2' GND.
i
TO COLD WATER PIPE
/y) 6 '4 SYSTEM TO 6t
ALLED IN ACCORDANCE �� VG -L 2
fAlAWtQkF
VVATCR All A IN t fid
DA r
1
a�
N
r� W
r1 �
t\ �
O
O W O
r1 W
O On
U) W
H Q o0
• �� �`
v In
o w
U �Y o
• o z g �,
O �.
U
I\ J
0) Q — W
L F-:
(r �
ENGINEERS
W N o Ln
CL: _
O M Lo � M
N CN
Lo
tV fii� v
Za cnMo
M
o
r �v
wig W`
�+—
w 0
c�5 g
8
REVISIONS:
coo,
E� z.
W N,' o
o
co ` A
W � W M
J W LLJ
U cc
\ 0 L
� W
O G
Q
®o
v
0
V
A
® �W
0
ko
0
w
W
O
I
O
W
rY
F
�
o
'0
W
`_
X
U. CL
Q
Z
Z
O
t!7
F-
o
DATE:
;fJUNE 17„ 2002
,. -R AWN BY..
CA% Q.
• � ... � - � _•LAN
CT +NO.
#
0704
04 �,, .0
DRAWING NO.
E -602 of
SHEET NO.
OF