02-830-0831
i
r
2" DRAIN FROM 2 OR
3 COMPARTMENT SINK
"SFS" INDIRECT CONNECTION
AIR ADMITTANCE VALVE
(STUDOR MINI -VENT)
AIR ADMITTANCE VALVE DETAIL
FLOOR CLEANOUT
HUB OR FLOOR
TO SINK
- - - - -- - - - -' -'"" ' -T WITH LOCK DOOR
DIAL THERMOMETER
VOLUME CONTROL \SHUTOFF
VALVE
--THERMOSTATIC MIXING VALVE
NOTE:
LEONARD TA- 300- STSTL- REC/TA- 300- STSTL- EXP (FOR APPLICATIONS
IN THE PRE -FAB MEAT CUTTING ROOM)
THERMOSTATIC MIXING VALVE
FOR EWS /HS STATION
1" I.D. MINIMUM COPPER - OPEN TYPE
CONNECTION FROM REFRIGERATION COILS
A2 'In ^ FINISH FLOOR
MINIMUM 3" WASTE PIPE & FITTINGS
OUTFALL
"P" TRAP
"CD" COIL DRAIN DETAILS
FINISH FLOOR
RUNNING TRAP
VCE
(25 FEET)
N OTE:
ALLOWABLE PER STANDARD BUILDING CODE,
1994 EDITION, APPENDIX 7', FIGURE 7.
COMBINATION WASTE AND VENT
SAFE WASTE DETAIL
HEAT TRAP
1/2' PRESSURE RELIEF PIPE RUN
TO OUTSIDE OF BLDG. TURN ON. DISCHARGE
6' ABOVE FINISHED GRADE
P.& T. VALVE
SPRING LOADED
ASME RATED
HOT WATER
1
COLD WATER
_\- GATE VALVE
NUNION (TYP.)
.- ELECTRIC WATER HEATER
DRAIN
t -DRAIN PAN
SHELF
ELECTRIC WATER HEATER DETAIL
N.T.S.
HARD DRAWN TYPE "L" COPPER
OR PVC (BY CONTRACTOR)
DRAIN LINE 1 "0 I.D. MINIMUM
(DO NOT REDUCE FROM CASE SIZE)
"P" TRAP J OUTFALL
"DCD" CASE DRAIN
FINISHED FLOOR
SLEEVE &SEAL
SEAL THRU SLAB
COLD WATER SUPPLY
FROM NEAREST
LAVATORY OR SINK
TRAP PRIMER VALVE
FLOOR DRAIN W/
ADJUSTABLE
STRAINER
TRAP PRIMER
CONNECTION
MIN. 3" P -TRAP
WASTE
PIPING
FLOOR DRAIN DETAIL W/ TRAP PRIMER
WATER HAMMER ARREUER SCHEDUI E
PDI
WE
MPS TFFEAD
DL#A348M
CFA
FMW UNT
CAPACITY
L
W
A
1/2-
5 1/4"
1 1/8"
3.5"
1 -11
B
3/4"
6 1/8"
1 3/8"
4.3"
12 -32
C
1"
8"
1 3/8"
6.5"
33 -60
D
1.
10 5/8"
1 3/8"
10"
61 -113
E
1"
9 7/8"
2 1/8"
22.36"
114 -154
F
1 "
13 7/8"
2 1/8'
34.4"
155-330
-' -W"
WATER HAMMER ARRESTER DETAIL
WALL
CEILING
WATER HEATER
WEIGHT FULL OF WATER
APPROX, 5+00 POUNDS
VERIFY WEIGHT UJITH SPECS
ADJUST IF REQUIRED.
ANGLE FRAME
BOLT REAR ANGLES TO UJALL
CONSTRUCT SUPPORT RACK OF 4
3 "x 3 "x '/4' GALVANIZED ANGLE
IRONS UJITH TOP OF '44" SHEET
STEEL OVER ANGLE IRONS.
AND BOLTS AND WELDING FOR A
- SATISFACTORY SUPPORT.
8
FAUCET
MOP SINK
BOLT COLUMNS TO FLOOR WITH
TO ANGLE IRONS
EXISTING FLOOR SLAB
FINISH FLOOR
UJATEfR NEATEfR MOUNTING:z E)ETAIL
SCALE: NOT TO SCALE
FINISH FLO
BLOWER TYPE
REFRIGERATION COIL
TEE W/ SCREENED
PLUG
DRAIN LINE SHALL BE
cy-
o
WRAPPED W/ HEATING
BAND INSULATION
WHERE EXPOSED IN
0
FREEZER /COOLER ROOM AND
N
PIERCE FREEZER /COOLER WALL
w
@ 45 ANGLE AND
uj
CONNECT TO DRAIN
I
'1
1" I.D. MINIMUM COPPER
BY PLUMBING CONTR.( HOLD
PIPE TIGHT TO PIPE WALL W/
PIPE STRAPS) TYP. COOLER
AND FREEZER. FOR ALTERNATE LO(
OF COIL DRAIN,
SEE NOTES BELOW.
HORIZONTAL P TRAP
AND DRAIN OUTSIDE
OF FREEZER
—1" I.D. MINIMUM
COPPER DRAIN LINE ALL
COOLERS /FREEZERS
3" MIN. LINES
OUTFALL
TYPICAL COOLER AND FREEZER DRAINS
NOTES:
1. SLOPE FLOOR FROM INSIDE COOLER WALLS TO FLOOR DRAINS OUTSIDE COOLERS.
2. SEE PLUMBING PLAN FOR NUMBER AND LOCATION OF BLOWER TYPE REFRIGERATION
COILS, REFRIGERATION COILS ARE FURNISHED AND INSTALLED BY TENANT. PLUMBING
CONTRACTOR SHALL MAKE ALL PLUMBING CONNECTIONS.
3. CONDENSATE DRAINS FOR FREEZERS SHALL BE LOCATED OUTSIDE
FREEZER.
-� COIL OR
CASE DRAIN
"CD" DRAIN
COIL OR
CASE DRAIN
"DCD" DRAIN
HOUSING
L)
MUM)
PPLY BELL HOUSING
JD (TYPICAL)
MUM)
Ff
STOCK FLOOR DRAIN
NOTE: FLOOR FINISH TO
BE FLUSH W /TOP
OF DRAIN.
PLAN
SLOPE FLOOR TO DRAIN
WITHIN 5' OF FLOOR DRAIN,
UNLESS OTHERWISE NOTED
I
3" WASTE PIPE & FITTING
OUTFALL
INSTALLED BY CONTRACTOR
"FD" FLOOR DRAIN
nrrninrn • Trn
ZONTAL
TRAP
DOWN TO
DRAIN
HORIZONTAL
"P" TRAP
FURNISHED &
ALLED BY CONTRACTOR
MINIMUM 3" WASTE PIPE & FITTINGS
"DCD" CASE DRAIN SEOTION
REMOTE BULB: CLAMP ON DISCHARGE
OF TEMPERED WATER LINE AS CLOSE
TO HEAT RECLAIM TANK AS POSSIBLE
O
A ASTAT: HONEYWELL L6006C -10 ,
FUR SHED AND INSTALLED BY P BING
SUBCO TRACTOR. MOUNT ON L NEXT TO
HEAT RE AIM TANK AND S AT 160'F.
3 -WAY VAL
AT COMPR SOR RA BY
REFRIGE TION SUBCO RACTOR.
L WIRING BY ELECTRICAL SU ONTRACTOR
NOTE: RECIRCUL ING PUMP SHALL RUN CONTINUOUSLY,
HEATIN AT RECLAIM TANK CYCLED ON AQUASTAT AND
HEA G AT ELECTRIC WATER HEATERS CYCLED ON
IN RNAL THERMOSTATS.
FOR HOT WATER HEAT RECLAIM
W I
V1 c
u � ° r*_1
W 0 W
w
O fY Q Ln
V) LL M
H Q 03
in
• �' Ln
" W r�
U° �Y o
• o z r�
U 0)
Q 0) J
0) — W
Ln H .
ENGINEERS
W p
a�!oLM
N N I
N
W ,.fir n
D W I'7
C/7 M o
d M Iz o"
W 0
o
z Z E
111.2 N
N cog Lo
W v M
&WINN IBIXIE - COMMENTS
RED LINES CLARIFICATIONS
�BUILDING DEPT.
SEPT. 2002
(3" AIR GAP)
ko
N
Y M
L
cc E r z
a� °
Q. oo
A Lo
(o co
co
A�
z � o
W ° W'.
J c
Lm
o I
E
Q a
® °
A
W
A
0
ko
0
ko
DRAWING TITLE
PLUMBING
DETAILS
D ATE:
JUNE 17, 2002
DRAWN BY:
CHECKED BY:
DIVISION
MIAMI
LOCATION NO.
285
W.D. GUIDE PLAN
PROJECT NO.
WD #0704
DRAWING NO.
P -402 of
SHEET NO.
OF
FF
w
0
0
F_
W
–
o
v
W
X
Q
Z
Z
0
In
I-
D
m
O
DRAWING TITLE
PLUMBING
DETAILS
D ATE:
JUNE 17, 2002
DRAWN BY:
CHECKED BY:
DIVISION
MIAMI
LOCATION NO.
285
W.D. GUIDE PLAN
PROJECT NO.
WD #0704
DRAWING NO.
P -402 of
SHEET NO.
OF