02-830-076Y i 1 r. L Z r' i .c r zz 1. DRAWING NOTES O TEMPERATURE AND RELIEF DRAIN PIPE AND DRAIN PAN PIPE FROM WATER HEATERS TO TERMINATE OVER FLOOR DRAIN. 20 COORDINATE DRAIN LOCATION W/ EQUIPMENT PRIOR TO INSTALLATION. O3 PHARMACY SINK FURNISHED BY TENANT AND INSTALLED BY CONTRACTOR, PIPE TO DRAIN TO CD W/ INDIRECT CONNECTION. O ROUTE 3" VENT UP W/I WALL AND OFFSET ABOVE FINISH CEILING CEILING. GENERAL NOTES 1. CONTRACTOR SHALL NOT POUR ANY PORTION OF CONCRETE FLOOR SLAB UNTIL UNDERGROUND UTILITIES ARE CHECKED BY WINN- DIXIE'S MAINTENANCE SUPERINTENDENT. ALLOW A MINIMUM OF TWO (2) WEEKS NOTICE PRIOR TO CHECKING. 2. IT IS RECOMMENDED THAT THE SUB - CONTRACTOR ARRANGE A PRE -JOB CONFERENCE W /WINN- DIXIE'S CONSTRUCTION SUPERVISOR FOR REVIEW AND CLARIFICATION BEFORE STARTING WORK. CALL: PETE ONORATI (954) 783 -2836 3. THE DRAINAGE SYSTEM AS SHOWN IS FUNCTIONAL AND MOST DESIREABLE. IF SUCH IS NOT LOCALLY ACCEPTABLE, THE CONTRACTOR SHALL INSTALL OTHER DRAINS AS REQUIRED. HE SHALL INSTALL ANY VENTS WHICH ARE REQUIRED BY CODE (WHETHER SHOWN OR NOT). ANY PROPOSED SYSTEM OR CHANGES SHALL BE APPROVED BY WINN -DIXIE BEFORE ANY WORK IS STARTED. THE ENTIRE PLUMBING SYSTEM SHALL CONFORM WITH ALL STATE AND LOCAL CODES. 4. PVC SHALL BE USED FOR SALES AREA DISPLAY CASE CONDENSATE DRAIN LINES. CARE SHALL BE USED WHEN LAYING PIPE OVER FILL. FILL SHALL BE MECHANICALLY COMPACTED. 5. PIPE NOTE: A. INSTALL 1/2" C.W. AT RIGHT SIDE OF FIXTURE. B. RUN 1 1/2" PIPE 0 1 /4 " /FT. FIXTURE ARM. C. RUN 2" PIPE @ 1 /4 " /FT. D. RUN 3" PIPE @ 1 /8 " /FT. E. RUN 4" & 6" PIPE 0 1 /8 " /FT. F. PROVIDE CLEANOUT AT BASE OF EACH SOIL AND WASTE STACK. 6. ALL DRAINS SHALL BE P- TRAPPED AT THEIR ORIGIN (WHERE CODES PERMIT). 7. DO NOT POUR CONCRETE WITHIN 2' OF FLOOR DRAINS UNTIL DRAINS ARE INSTALLED. 8. TOP OF FLOOR DRAINS IN AREAS WITH SLOPED FLOORS SHALL BE SET BY FLOOR SLOPE OF 1/16" MIN. PER FOOT IN THOSE AREAS. 9. ALL EXPOSED COPPER IN FOOD PREP AREAS (PRODUCE, MEAT, SEAFOOD, DELI BAKERY, ETC.) SHALL BE POLISHED WITH EMERY CLOTH AND ONE COAT CLEAR LACQUER APPLIED. 10. ALL CASE HUB DRAINS SHALL BE 3" BELL FITTINGS. 11. HUB DRAINS FOR COOLER CONDENSATE SHALL BE INSTALLED TIGHT TO WALL AND IN CONCRETE CURB. 12. SLEEVES IN CONCRETE BLOCK WALLS, FOUNDATIONS AND FLOORS TO BE PROVIDED BY PLUMBING CONTRACTOR. 13. ALTERATIONS TO EXISTING WORK BEING OF SUCH NATURE THAT ALL FACETS OF THE WORK BEING IMPOSSIBLE TO DETAIL AND SPECIFY,IT IS THEREFOR. THE RESPONSIBILITY OF THE CONTRACTOR TO CAREFULLY EXAMINE THE BUILDING AND FAMILIARIZE HIMSELF WITH THE CONDITIONS AND RELATE THESE CONDITIONS TO THE SCOPE OF THE PROPOSED WORK. 14. CONTRACTOR SHALL VERIFY LOCATION OF EXISTING DRAIN LINES AND SEWER LINE. HE MAY ROUTE NEW WORK THROUGH THEM IN THE MOST ECONOMICAL MANNER . IN THE EVENT THE PLUMBING SYSTEM SHOWN CANNOT BE INSTALLED PROPERLY . IT IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO INSTALL A WORKABLE SYSTEM WITHOUT EXTRA COST TO WINN DIXIE AND CONFORMS TO ALL STATE AND LOCAL CODES. 15. ANY PROPOSED SYSTEM OR CHANGES SHALL BE APPROVED BY WINN -DIXIE BEFORE ANY WORK IS STARTED. 16 ALL DIMENSIONS ON THIS DRAWING ARE CUMULATIVE AND ARE TAKEN FROM FINISH FACE OF MASONRY AND FINISHED WALLS, UNLESS NOTED OTHERWISE. DIMENSIONS INDICATED FROM THE WALL SEPARATING THE SALES AREA FROM THE STOCKROOM AREAS ARE TAKEN FROM THE FINISHED FACE OF WALL ON THE SALES AREA SIDE. THE WALL ON EACH SIDE OF CUTTING ROOM IS FIGURED AT 7" INCLUDING FINISHES. CONTRACTOR SHALL VERIFY DIMENSIONS W /DRAIN DETAIL AND ACTUAL JOB CONDITIONS. 17. ANY EXISTING DRAINS IN SALES AREA AND BACK ROOM NOT TO BE RE- USED, SHALL BE PLUGGED BELOW FLOOR AND FINISHED PER FINISH SCHEDULE. 18. CONTRACTOR TO CLEAN OUT ALL EXISTING DRAIN LINES TO INSURE PROPER FLOW, FLUSH DRAIN AS REQUIRED. 19. ALL NEW AND EXISTING SOIL LINES SHALL BE PROPERLY VENTED AND HAVE A FLOOR CLEAN OUT (F C /O) AT THE END OF ALL RUNS. 20. ALL NEW DRAIN LINES TO BE A MINIMUM OF 4" IN DIAMETER. 21. ALL DRAINAGE PIPING SHALL BE PVC. DWV SCH. 40 IF ALLOWED BY CODE. CAST IRON SOIL PIPE WITH PUSH JOINTS UNDERGROUND AND NO -HUB JOINTS ABOVEGROUND MAY BE USED. CARE IS TO BE COMPACTED MECHANICALLY. 22. CONTRACTOR SHALL FURNISH AND INSTALL ANY NECESSARY CLEANOUTS NOT SHOWN ON PLANS. CLEANEST SHALL NOT EXCEED 50' -0" UN CENTERS. 23. CONTRACTOR SHALL VERIFY DIMENSIONS W/ DRAIN DETAILS ACTUAL JOB CONDITIONS, AND ACTUAL CASE ROUGH -IN REQUIREMENTS. 24. CONTRACTOR SHALL VISIT JOB SITE PRIOR TO BIDDING, TO FULLY FAMILIARIZE HIMSELF WITH SCOPE OF WORK, WORKING CONDITIONS, AND EXISTING UTILITIES. 25. ANY CONFLICT NOT ADDRESSED IN THESE DRAWINGS SHOULD BE BROUGHT TO THE ENGINEERS ATTENTION IN A TIMELY MANNER TO LET THE ENGINEER MAKE AN ASSESSMENT OF THE PROBLEM AND MAKE A DECISION ON THE COURSE OF ACTION TO TAKE. 26. CONTRACTOR SHALL COORDINATE ALL WORK WITH ALL TRADES, AND WITH EXISTING CONDITIONS. 27. CONTRACTOR SHALL COORDINATE ALL WORK WITH WINN -DIXIE AUTHORITIES TO MINIMIZE DISRUPTION OF NORMAL STORE OPERATIONS. 28. CONTRACTOR SHALL SAW CUT OR CORE DRILL EXISTING SLABS TO INSTALL NEW WORK. PATCH SLAB TO MATCH EXISTING ONCE PLUMBING IS INSPECTED, AND FIRE SEAL ALL PENETRATIONS THROUGH FIRE RATED WALLS TO MAINTAIN FIRE RATING. LOCATION SHOWN FOR EXISTING PLUMBING FIXTURES, DCD, FLOOR DRAINS, ETC. ARE APPROXIMATE. R IS CONTRACTOR RESPONSIBILITY TO VERIFY EXIST. LOCATIONS IN FIELD, ADJUST OR RELOCATE IF REQUIRED FOR NEW LAYOUT OR EQUIPMENT. IF EXISTING IS NOT THERE PROVIDE NEW. VERIFY ALL EXISTING CONDITIONS IN FIELD AND INCLUDE IN BID ANY NECESSARY ADJUSTMENTS. INFORM ENGINEER AND ARCHITECT IF ANY MAJOR DISCREPANCIES ARE FOUND.. NEW DCD ............................................................................... ............................... EXISTING 4" SANITARY PIPE EXISTINQG CO. _ EXISTING GREASJ J TRAP G REMAIN 1200 GALLONS I ONNEGT J PIPE TO `XISTING 4�" SANITARY PIPE SANITARY L EXISTING 4" SANITARY PIPE STUB UP NOTE 1. ALL NEW UTILITIES (DRAINS, WATER, ETC.) FOR NEW EQUIPMENT MUST BE VERIFIED WITH EQUIPT. SPECS AND OR TEMPLATES PRIOR TO COMMENCING ANY WORK. ADJUST IF REQUIRED. INFORM ARCH /ENG. OF DISCREPANCIES AND INCLUDE IN BID. 2. IF EXISTING UTILIIES BEING CALLED TO BE REUSED OR RELOCATED. CAN NOT BE REUSED CONTRACTOR TO PROVIDE NEW AS REQUIRED. 3. CONTRACTOR MUST CONTACT EQUIPMENT REP OF REFRIG. CASES AND EQUIPMENT AND OBTAIN SPECS AND SHOP DRAWINGS OF THE ACTUAL EQUIPMENT BEING DELIVERED TO BE USED IN THE STORE AND COORDINATE LOCATION OF EQUIPMENT WITH ARCHITECT. ARCHITECT WILL PROVIDE TAKE OFF POINTS FOR CONTRACTOR TO LOCATE EQUIPMENT AND COORDINATE FINAL AND EXACT LOCATION OF UTILITIES (ELECTRICAL, PLUMBING REFRIG. ETC.). PLEASE CONTACT ARCHITECT AND ENGINEER WITH AND PROVIDE A WEEK NOTICE FOR MEETING. GREASE INTERCEPTOR SIZING: AS PER FBC 2001 - 1003.5 & 1003.5.1. SYSTEM #1 2) 3 COMP. SINK = 2x22,5 GPM = 45 GPM 55) DCD 0 3 FU= 55x3x7 GPM= 1155 GPM 1) 1 HAND SINK = 1 x4.2 GPM = 4.2 GPM 1204.2 GRM A 50% EQUIPMENT LOAD REQUIRED 1204.2x0.5 = 602.1 GALLONS PROVIDE 1200 GALLON GREASE INTERCEPTOR. EXISTING 1200 GALLON GREASE INTERCEPTOR TO BE REUSED. LEGEND ABBREVIATION SYMBOL DESCRIPTION GW IG DRAIN ALL EXIST! G SANITARY STORM PS NOT BEIN REUS D SECONDARY DRAINAGE PIPING LOCA ® X - TRAP TO REMAIN w TRO GH TH STOR NEW FLOOR DRAIN (TYP.) TO REMAIN VERIFY LEGEND ABBREVIATION SYMBOL DESCRIPTION GW IG DRAIN GREASE WASTE SAN p SANITARY STORM PRIMARY DRAINAGE PIPING OVERFLOW Z SECONDARY DRAINAGE PIPING EXISTING ® X - TRAP TO REMAIN w EXISTING FLOOR DRAIN TO REMAIN SFD ® NEW FLOOR DRAIN (TYP.) GREASE INTERCEPTOR SIZING: AS PER FBC 2001 - 1003.5 & 1003.5.1. SYSTEM #2 1 3 COMP SINK= 1 x22.5 GPM =22.5 GPM 3 HAND SINK = 3x4.2 GPM = 12.6 GPM 1 MOP SINK = 1 x9.4 GPM = 9.4 GPM 5 FD (3FU) EACH = 5x3x7 = 10.5 GPM 2 8 DCD 0 3FU = 8x3x7 = 168 GPM 317. GPM 50% EQUIPMENT LOAD REQUIRED 317.5 GPMxO.5 = 158.75 GALLONS PROVIDE 1200 GALLON GREASE INTERCEPTOR EXISTING 1200 GALLON GREASE INTERCEPTOR TO BE REUSED. EXISTING TO BE REMOVED CONTRACTOR TO MANIFOLD TWO CASE DRAINS PER ONE FLOOR DRAIN. VTR 0 O O 0 PLANS WERE PREPARED FROM EXISTING DRAWINGS BY F. EARL LEGGET ARCHITECT - TAMPA (UNDATED) GLASSER ASSOC. ARCH. DATED 6/30/72 IT IS CONTRACTOR RESPONSABILITY TO VERIFY AND COORDINATE ALL EXISTING CONDITIONS IN FIELD AND ADJUST OR PROVIDE NEW AS REQUIRED. 1 1 (D aN to W (D O W O W 00 � J O In C/) LL- rn H Q 00 • �� �� In N W U° • O ZJ to O �W1 U � 0)Q In bi �EQE .. .-... . I t _ co N �N I Lo o Lo Lo 0- M z o" wDo W d W L ly r" O Cnly M_ w ^ � IZ ZE rn � zZ UI � v r7 M W REVISI N WINN IXI - COMMENTS RED LINES CLARIFICATIONS ($-2/-U2 FUN BIU) ABUILDING DEPT COMMENTS SEPT. 2002 GREASE TRAP CALCS. IS Z Li IG DRAIN Li VERIFY p W W E�z z 1L. Z 0 ° A [EXISTING GREASE X - TRAP TO REMAIN w 2200 GALLONS J EXISTING 4 "0 00 A� TO REMAIN VERIFY !S IN FIELD. (TYPICAL) . _I � U VTR 0 O O 0 PLANS WERE PREPARED FROM EXISTING DRAWINGS BY F. EARL LEGGET ARCHITECT - TAMPA (UNDATED) GLASSER ASSOC. ARCH. DATED 6/30/72 IT IS CONTRACTOR RESPONSABILITY TO VERIFY AND COORDINATE ALL EXISTING CONDITIONS IN FIELD AND ADJUST OR PROVIDE NEW AS REQUIRED. 1 1 (D aN to W (D O W O W 00 � J O In C/) LL- rn H Q 00 • �� �� In N W U° • O ZJ to O �W1 U � 0)Q In bi �EQE .. .-... . I t _ co N �N I Lo o Lo Lo 0- M z o" wDo W d W L ly r" O Cnly M_ w ^ � IZ ZE rn � zZ UI � v r7 M W REVISI N WINN IXI - COMMENTS RED LINES CLARIFICATIONS ($-2/-U2 FUN BIU) ABUILDING DEPT COMMENTS SEPT. 2002 GREASE TRAP CALCS. IS w Y M W I` C A W W E�z 1L. L_ 0 ° A o i' w 00 A� z (o) w_ �O rn . _I � U � V) MW h+�l Lil \ , 0Ld W Lm N = E-I o w 0 ®o V A W V Q 0 w W 0 0� 0 W W - 0 LL_ L_ W Q � V) Q z Z 0 = w 0 OF PROJECT NO. WD #0704 DRAWING NO. P-102 OF _ SHEET N0. OF