02-830-072HANGER STRAPS: 1 "x 22 GAUGE, SUPPORTED FROM STRUCTURE ABOVE, (3) SHEET METAL SCREWS BELOW. WRAP INSULATION: OVER- LAP 4" MINIMUM, STAPLE & TAPE FOR VAPOR SEAL SIZES SHOWN ARE FREE AREA SECURE INSULATION WITH STICK -PINS AT 18" O.C. AND ADHESIVE ON BOTTOM, FOR DUCTS 24' AND LARGER I TAPE AND MASTIC OUTER JACKET (TYPICAL) MINIMUM RADIUS EQUAL TO THE FLEX DUCT DIAMETER 24' SPIN -IN FITTING: MAXIMUM WITH SCOOP AND VERTICAL DAMPER, EXCEPT IN DUCT RUN GYP. BOARD CEIUNGS, DAMPER IN NECK ROUND 'SNAPLOCK' SHEET METAL FOR RUN -OUTS GREATER THAN 8', WITH 2" WRAP INSULATION. AN APPROVED EQUAL IS 'SPIRO -PIPE' ROUND "SNAPLOCK' (FLEX ONLY IN VERTICAL) BAND CLAMP AND THREE SHEET METAL SCREWS THROUGH HELIX OF FLEXIBLE DUCT LINER (TYPICAL) FLEXIBLE DUCT: INSULATED, ONLY IN VERTICAL WRAP INSULATION ABOVE CEILING DIFFUSER WITH OPPOSED BLADE s FLEX DUCT TO BE SAME SIZE AS DIFFUSER NECK THE CEILING DIFFUSERS VOLUME DAMPER: SET THROW AS SHOWN ON PLANS SHEET METAL DUCT DETAIL 1. SHEET METAL DUCTS SHALL BE FABRICATED do INSTALLED PER THE LATEST EDITION OF SMACNA, AND THE LOCAL ENERGY CODE WITH THE FOLLOWING CRITERIA BASED ON 4 FOOT SECTIONS. DUCT SIZE DUCT MATERIAL HANGERS REINFORCEMENT 0 - 12' 26 GA FLAT 8' O.C. NONE 13 - 18' 24 GA BEAD 8' O.C. NONE 19 - 30' 24 GA BEADED 8' O.C. STANDING SEAM 31 - 48' 22 GA BEADED 6' O.C. STANDING 1' S. 49 - 54' 22 GA BEAD 6' O.C. STANDING 2' S., 20 GA 55 - 80' 20 GA CROSS -BREAK 5' O.C. STANDING 2" S. 84' + 20 GA CROSS -BREAK 5' O.C. STANDING SEAM, 20 GA 2, ALTERNATE INTERPRETATIONS OF SMACNA DUCT MATERIAL, HANGERS AND REINFORCEMENTS ARE SUBJECT TO ENGINEER APPROVAL, AND REQUIRE SEPARATE SUBMITTAL OF THE ALTERNATES. 3. FLEXIBLE DUCT CONNECTORS SHALL BE PROVIDED WHERE SHOWN ON THE PLAN. 4. SUPPLY AIR DROPS FROM ROOFTOP UNITS SHALL TRANSITION FROM THE UNIT OPENING SIZE TO SQUARE NECK ELBOWS, WITH SIZES AS SHOWN ON THE PLAN. IF TWO SUPPLY AIR DUCT RUNS ARE AT THE UNIT, THEN TWO SEPARATE DROPS & ELBOWS SHALL BE PROVIDED. 5. RETURN AIR DROPS FROM THE ROOFTOP UNITS SHALL BE FULL SIZE OF THE UNIT OPENING. 6. ELBOWS SHALL BE SQUARE NECK (SAME IN OUT DIMENSION) WITH 2" DOUBLE THICKNESS TURNING VANES. 7, OFFSETS SHALL NOT REDUCE THE FREE AREA, AND SHALL NOT EXCEED 30. A RADIUS HEEL HEEL SHALL BE PROVIDED ON 30' OFFSETS. SMALLER OFFSETS SHALL BE MITERED AT BOTH THE HEEL do THROAT. 8, TRANSITIONS SHALL NOT EXCEED 1:3 RATIO (4' TRANSITION PER FOOT SINGLE SIDED TRANSITION, AND 8" PER FOOT DOUBLE SIDED TRANSITION), 9, INSULATION SHALL BE NFPA 90 APPROVED, WITH MINIMUM 4.2 R VALUE. WRAP INSULATION SHALL BE 2" THICK WITH ALUMINUM FOIL FACING. 10. RECTANGULAR BRANCH CONNECTIONS SHALL BE 45' ENTRY TYPE PER SMACNA FIGURE 2 -10. 11. ROUND DUCT CONNECTIONS SHALL BE WITH 'METAL MANUFACTURING COMPANY" MSI -6 SPIN -IN FITTINGS. WITH 90' SCOOP, DAMPER AND HANDLE. SPRAY PAINT LOCATIONS OF HANDLES. 12. FLEXIBLE DUCT SHALL INCLUDE AN INNER POLYETHYLENE LINER, A SPRING HELIX, 1 -1/4" BLANKET INSULATION, A FOIL OUTER VAPOR BARRIER, AND BE UL -181 APPROVED. 13. ALL TAPE SHALL BE FASSON 0810 (NO SUBSTITUTIONS), SMACNA APPROVED. 14. SEAL ALL SUPPLY, RETURN do OUTSIDE AIR DUCTS IN THE CEILING PLENUM WITH TAPE AND MASTIC. 15. REFER TO SPECIFICATIONS FOR ADDITIONAL SEALING INFORMTION. F N Nt X O M . I W s i Q CL rn N O 0 N O 0 rn 3 v N O L0 I 00 N 0 00 N 3 w BURGLAR BARS: 3/4' 6" OVER CENTERS, WELDED TO FRAME & EACH OTHER OUTLINE OF SUPPLY do RETURN AIR DUCTS DUCT PENETRATION OF BARS: NOTCH DROP FROM ROOFTOP, SEAL WITH "UNITED DUCT SEALER" AND INSULATE BARS 6" OUT WITH FLEXIBLE FOAM INSULATION SUPPORT FRAME FOR BURGLAR BARS: MAY BE PART OF CURB SUPPORT OR MAY BE SEPARATE FRAME. FLEXIBLE CONNECTOR: "DURO -DYNE" OR EQUAL 110ROOFFTrOP UNIT ■� �r{� ■ ■�i ■ ■ ■■ FACTORY PLAN �- ROOFTOP UNIT FACTORY i i i I ROOF '7 °�= 1•. =� °�^- = .= =r °r•1 P=P=P =�= \ STRUCTURAL STEEL Q' SUPPORT FRAME BENEATH ALL SOPPY do RETURN SECTION PORTIONS OF THE AIR DUCTWORK FACTORY CURB. FACTORY CURB: SEE DETAIL SUPPLY AIR DUCT z I- DISCONNECT SWITCH: BY ELECTRICAL SUBCONTRACTOR DO NOT MOUNT OVER NAME PLATE - RETURN AIR DUCT ROOF IRESTAT. 136'F 0 SECTION 4 RTU -2 + 3 ROOFTOP UNIT DETAIL • ROOFTOP UNIT: * FASTEN TO CURB WITH STRAP * GASKET AND SILICONE SEALING • PRESSURE - TREATED WOOD NAILER STRIP CURB HEIGHT = 1 • FACTORY CURB: NRCA APPROVED, 18 GAGE, SQUARE WITHIN 1/8- ON DIAGONAL MEASUREMENT, WITH A MINIMUM OF 8" ABOVE TOP OF j ROOF CURB SET DIRECTLY ON STEEL ' HI MECHANICAL. SUBCONTRACTOR SHALL PROVIDE ITEMS NOTED WITH • GENERAL CONTRACTOR SHALL PROVIDE ITEMS NOTED WITH •• "COUNTER FLASHING STRIP ++ 1' RIGID INSULATION ++ 3' CANT STRIP ** ROOFING ROOF IN •• METAL DECKING STRUCTURAL SUPPORT FRAME FOR UNIT do DECKING AT FULL PERIMETER OF FACTORY CURB CURB DETAIL: ROOFTOP UNIT 1. MECHANICAL SUBCONTRACTOR SHALL FURNISH ROOF OPENING SIZES & LOCATIONS, FOR STRUCTURAL SUPPORT FRAMING BY GENERAL CONTRACTOR. 2. THIS CURB DETAIL WILL ALLOW THE UNIT TO SLOPE WITH THE SLOPE OF THE ROOF PITCH. THIS DETAIL CAN ONLY BE USED (A) IF THE CONDENSATE DRAIN PAN OUTLET IS ON THE LOW SIDE OF THE UNIT, OR (B) IF THE CONDENSATE DRAIN PAN IS NOT AFFECTED BY SLOPE. THIS DETAIL CAN NOT BE USED IF THE CONDENSATE DRAIN CONNECTION IS ON THE HIGH SIDE OF THE UNIT. 3. REFER TO TYPICAL RTU MOUNTING DETAIL FOR BOLTING REQUIREMENTS RN-2 + 3 BURGLAR BAR DETAIL OUTSIDE AIR INTAKE FAN NO. 3/4" P -TRAP do SERVICE CFM CONDENSATE DRAIN ROOFTOP UNIT r -T I I ROUTE AS INDICATED ON PLAN MFR. I I I I RETURN OPENING: SUPPLY OPENING: _ _ _ _ _ �F- - '-j' - - 14- 5/8'X11 -1/6" 13 -5/16 "X10 -3/4" �� FULL SIZED DROP 800 0.15 1375 FULL SIZED DROP v II ACME PDU 11ORG I CONTROL CONDUIT: ROUTE UP INSIDE THE PROVIDE BURGLAR BARS I ( I L�-_ LL CURB. FOR ROOFTOP UNIT 1.0 ELECTRICAL DATA VOLTAGE PLAN v ROOF PENETRATION: FAN MOTOR H.P. "PATE" PIPE SEAL FACTORY CURB: SEE DETAIL SUPPLY AIR DUCT z I- DISCONNECT SWITCH: BY ELECTRICAL SUBCONTRACTOR DO NOT MOUNT OVER NAME PLATE - RETURN AIR DUCT ROOF IRESTAT. 136'F 0 SECTION 4 RTU -2 + 3 ROOFTOP UNIT DETAIL • ROOFTOP UNIT: * FASTEN TO CURB WITH STRAP * GASKET AND SILICONE SEALING • PRESSURE - TREATED WOOD NAILER STRIP CURB HEIGHT = 1 • FACTORY CURB: NRCA APPROVED, 18 GAGE, SQUARE WITHIN 1/8- ON DIAGONAL MEASUREMENT, WITH A MINIMUM OF 8" ABOVE TOP OF j ROOF CURB SET DIRECTLY ON STEEL ' HI MECHANICAL. SUBCONTRACTOR SHALL PROVIDE ITEMS NOTED WITH • GENERAL CONTRACTOR SHALL PROVIDE ITEMS NOTED WITH •• "COUNTER FLASHING STRIP ++ 1' RIGID INSULATION ++ 3' CANT STRIP ** ROOFING ROOF IN •• METAL DECKING STRUCTURAL SUPPORT FRAME FOR UNIT do DECKING AT FULL PERIMETER OF FACTORY CURB CURB DETAIL: ROOFTOP UNIT 1. MECHANICAL SUBCONTRACTOR SHALL FURNISH ROOF OPENING SIZES & LOCATIONS, FOR STRUCTURAL SUPPORT FRAMING BY GENERAL CONTRACTOR. 2. THIS CURB DETAIL WILL ALLOW THE UNIT TO SLOPE WITH THE SLOPE OF THE ROOF PITCH. THIS DETAIL CAN ONLY BE USED (A) IF THE CONDENSATE DRAIN PAN OUTLET IS ON THE LOW SIDE OF THE UNIT, OR (B) IF THE CONDENSATE DRAIN PAN IS NOT AFFECTED BY SLOPE. THIS DETAIL CAN NOT BE USED IF THE CONDENSATE DRAIN CONNECTION IS ON THE HIGH SIDE OF THE UNIT. 3. REFER TO TYPICAL RTU MOUNTING DETAIL FOR BOLTING REQUIREMENTS RTU -3 EQUIPMENT SCHEDULES FiTU -3 FAN SCHEDULE FAN NO. LOCATION SERVICE CFM STATIC PRESS. IN.W.G. RPM OUTLET VELOC. FPM TYPE MFR. MODEL NO. BHP MOTOR HP VoIVPh /Hz REMARKS EF -2 ROOF STM HOOD 800 0.15 1375 960 UPBLAST ACME PDU 11ORG - 0.25 115/1/60 1,2,3 EXT STATIC PRESS in. w.c. 1.0 ELECTRICAL DATA VOLTAGE 300 208V/30 FAN MOTOR H.P. .60 COMP. POWER R.L.A. 18.6 COND. FAN F.L.A. 2l.0 ELECT. HEAT 4.5KW MCA/ FUSE 25/40 MISC. SYSTEM EFFICIENCY SEER 10.5 WINTER OUTSIDE TEMP ELECTRIC HEATER (KW) Q ABOVE 35'F 9.0 31'F - 35'F 9.0 26'F - 30'F 9.0 21'F - 25F 13.0 16'F - 20'F 1. USE SOUD STATE CONTROLLER 11'F - 15F 21NTERLOCK FANS WITH THEIR RESPECTIVE ZONE A/C 13.0 I PROVIDE PRE - FABRICATED ROOF CURB, BACKDRAFT DAMPER, DISCONNECT AND BIRD SCREEN 4. FOR HOOD EXHAUST do SUPPLY FANS SEE SCHEDULE ON DWG M -501 RTU -3 EQUIPMENT SCHEDULES FiTU -3 DESIGNATION DESCRIPTION MANUFACTURER: TRANE CFM NOTED MODEL NUMBER WCD048 14'0 CDt CEILING DIFFUSER DE3M DATA ff U-3 METALAIRE 5800 -6, STEEL COOLING COIL COOLING CAPACITY ® 95'F BTUH TOTAL BTUH SENS 49,900 ENTERING AIR DB /WB 80/67 LEAVING AIR DB /WB 57/54 FAN SECTION SUPPLY AIR CFM 1600 OUTDOOR AIR CFM 200 EXT STATIC PRESS in. w.c. 1.0 ELECTRICAL DATA VOLTAGE 300 208V/30 FAN MOTOR H.P. .60 COMP. POWER R.L.A. 18.6 COND. FAN F.L.A. 2l.0 ELECT. HEAT 4.5KW MCA/ FUSE 25/40 MISC. SYSTEM EFFICIENCY SEER 10.5 WINTER OUTSIDE TEMP ELECTRIC HEATER (KW) Q ABOVE 35'F 9.0 31'F - 35'F 9.0 26'F - 30'F 9.0 21'F - 25F 13.0 16'F - 20'F 13.0 11'F - 15F 13.0 1'F - 10'F 13.0 QQ PROVIDE SINGLE POINT ELECTRICAL CONNECTION Q EXTERNAL PRESSURE DROP INCLUDES THE FOLLOWING ITEMS: DUCTWORK, FILTER, WET COIL, AND ELECTRIC HEATER. THE PRESSURE DROP FOR THE WET COIL, FILTER AND ELECTRIC HEATER FOR EACH ROOFTOP UNIT IS AS FOLLOWS: RTU -3: 1.0" O.A. CALCULATIONS 10 PERSONS AT 20 CFM = 200 CFM 36x2 SR1 140 CFM 48x2 SR2 280 CFM PLENUM SLOT DIFFUSER SR1 LENGTH AND WIDTH NOTED 36X2 CFM NOTED 140 PLENUM SLOT DIFFUSER SR2 LENGTH AND WIDTH NOTED 48X2 CFM NOTED 280 22x22 W AIR DISTRIBUTION DESIGNATION DESCRIPTION LEGEND SPECIFICATION CFM NOTED EXAMPLE 12X12 ER2 14'0 CDt CEILING DIFFUSER CD1 METALAIRE 5800 -6, STEEL 750 CFM NECK DIAMETER NOTED 14 "0 STAMPED, LOUVERED, DROPPED CONE Z Z CFM NOTED 750 CORE, 24 0X24', LAY -IN FRAME STYLE, 00 0 in DAMPER AT SPIN -IN, OFF -WHITE COLOR 120 CD2 CEILING DIFFUSER CD2 METALAIRE- 9000, ALUMINUM, 300 CFM NECK DIAMETER NOTED 120 MODULAR, ADJUSTABLE(4) CORE, CFM NOTED 300 LAY -IN FRAME STYLE, DAMPER 36x2 SR1 140 CFM 48x2 SR2 280 CFM PLENUM SLOT DIFFUSER SR1 LENGTH AND WIDTH NOTED 36X2 CFM NOTED 140 PLENUM SLOT DIFFUSER SR2 LENGTH AND WIDTH NOTED 48X2 CFM NOTED 280 22x22 W RLIURN GRILLE RR1 1800 CFM NECK SIZE NOTED 12X12 CFM NOTED 400 12X12 ER2 EXHAUST REGISTER ER2 415 CFM NECK SIZE NOTED 12X12 � CFM NOTED 415 OB DAMPER AT NECK, OFF -WHITE COLOR METALAIRE PD, STEEL SLOT DIFFUSER, W /INTEGRAL STEEL BOOT PLENUM. 2 - ONE INCH WIDE SLOTS, VERTICAL FLOW METALAIRE PD, STEEL SLOT DIFFUSER, W /INTEGRAL STEEL BOOT PLENUM. 2 - ONE INCH WIDE SLOTS, VERTICAL FLOW METALAIRE CC5, ALUMINUM, CUBE CORE 1 /2x1 /2xGRID OFF WHITE METALAIRE RH -D, ALUMINUM, LOUVERED CORE, OB DAMPER SURFACE MOUNT FRAME STYLE OFF -WHITE COLOR 18X12 DG DOOR GRILLE DG METALAIRE DG -DF, ALUMINUM SIZE AS NOTED 18X12 DOOR GRILLE, SURFACE MOUNT NOTES: 1. SIZES AND CFM SHOWN ON THE LEGEND ABOVE ARE FOR EXAMPLE ONLY. SEE PLAN FOR ACTUAL SIZES AND CFM VALUES USED ON THIS PROJECT. 2. LOCATE ALL AIR DISTRIBUTION PER THE ARCHITECTURAL REFLECTED CEILING PLAN. 3. ALL CEILING DIFFUSERS SHALL BE FOUR -WAY THROW. WHERE THREE -WAY THROW IS INDICATE ON THE PLAN, PROVIDE AN INTERNAL BAFFLE TO BLOCK THROW IN DIRECTION NOT REQUIRED. 4. APPROVED MANUFACTURERS: CARNES, KRUEGER, METALAIRE, TITUS. & ALL DIFFUSERS TO HAVE OPPOSED BLADE VOLUME DAMPERS. -Y a� N �^ W vl ~ W U `- o cD H- M O W O W O Q g � W W M HQ� DO • 04 W to N U° • O ZJ no � U 0) v I I` Q J �I n2 EAL E�'GINEERS n W � i N DX". a v7M � v Li fr- o on E go W M� M v REVISIONS: d W�+ N 04 I`•, 00 F_ �.0 0 w i'w J u' � i W o (D I a ®o v A W c� A ® �W 0 to I 0 40 W W 0 (Y- 0 W � cn 0 � v = W_ l,QIMSION MIAMI X 1-LOCATION NO. � � g Z Z In = 00 0 in DRAWING TITLE HVAC SCHEDULES & DETAILS er"DRAWING NO. M -502 OF - SHEET NO. OF __ DATE: JUNE 17, 2002 DRAWN BY: CHECKED BY: = l,QIMSION MIAMI 1-LOCATION NO. * z. 285 r.--`- W: D: ' GUtDE PLAN �,... •-- .-- :��"` CCPROJECT NO. #0704 er"DRAWING NO. M -502 OF - SHEET NO. OF __