5/8' TYPE 'X" GYP.
BOARD
1" FIRE CODE GYP.
BOARD SHAFT WALL
LINER
CORNER SUPPORT
CORNER SUPPORT
2 -1/2" 22 GAUGE
METAL C -H STUDS
VERTICAL AT 16" O.C.
ArCf_TV ED ALTERNATE
SH*7 CORNER SUPPORT-
3-1/2- METAL
DUCT DIMENSION PLUS STUD (TYPICAL)
12" MIN
SHEET ROCK SCREWS:
iO z (TYPICAL), INSTALL
(n INTERIOR SCREWS
a XEXHAUSTT- FIRST
SHEET ROCK: 5/8"
TYPE X, GYPSUM
(°-n 6" 6" BOARD (2) LAYERS,
MIN MIN (4) SIDES
CCESS PANELS; IN BOTH
�' DUCT do ENCLOSURE
U
o FIRE STOP: UL
' Z APPROVED SEALANT
(TYPICAL)
CORNER SUPPORT
GREASE DUCT ENCLOSURE DETAIL
(WHERE REQUIRED BY LOCAL AUTHORITY)
1. GYPSUM DUCT ENCLOSURE BY GENERAL CONTRACTOR.
2. ACCESS PANEL SHALL BE LOCATED AT EVERY CHANGE IN
DIRECTION. PANELS SHALL BE 16 GAGE, WITH 1/4 -20
BOLTS WELDED ON INSIDE WITH WING NUTS ON THE
OUTSIDE, WITH HIGH TEMPERATURE GASKET. PROVIDE
"KARP" FIRE -RATED ACCESS PANEL IN THE SHEET ROCK
PER UL APPROVED MANUFACTURERS INSTALLATION
INSTRUCTIONS.
3. REQUIRED AT HOODS /2. 3
4. GREASE DUCT ENCLOSURE SHALL ONLY BE PROVIDED
WHERE REQUIRED BY AUTHORITY HAVING JURISDICTION.
DISCONNECT SWITCH (U.L)
WOOD NAILER
SECURE FAN TO
CURB W/ 1/8 "0 BOLTS,
18" ON CENTER ALL
AROUND. (MIN 2
PER SIDE)
PREFABRICATED
CURB
ROOFING EXTENDED
UP & OVER
TOP OF CURB
SECURE CURB TO
ROOF USING 3/16"
THRU BOLTS W/
WASHERS do NUTS,
18" ON CENTER
ALL AROUND (MIN.
2 PER SIDE)
STEEL PLATE
BACKDRAFT DAMPER
DUCTWORK
TYPICAL ROOF
FAN MOUNTING DETAIL
NTS
FAN
1/4" RUBBER GASKET
BETWEEN CURB AND
NAILER
PRESSURE TREATED
WOOD (ALL AROUND
OPENINGS)
ROOF CONSTRUCTION
ROOF STRUCTURE
2x2x1/4" STEEL ANGLE
FRAME ALL AROUND
ROOF OPENING
EXTENDED TO ROOF
JOISTS AND WELDED
TO JOISTS AND METAL
DECK
TOP JOIST CLAMP
GRINNELL FIG. 227
(R TnTAI l
HOOD HANGING DETAIL
FAN MOTOR
FAN WHEEL
:I[:Ir>�aN�Oi
z_ o
L) HINGED
W FAN BASE—
CL
COMBINATION ROOF
CURB UNIT BY M.C.
INSTALLATION/WATER-
PROOF'G BY G.C. —
ALUMINUM HOUSING
� I
EXHAUST
� I
10'-O"-MIN
REMOVABLE TOP -�
ELECTRICAL CONTROL PACKAGE W /CONTACTORS
AND TERMINAL BLOCKS FOR POWER AND
CONTROL (120/1/60) FACTORY INSTALLED.
ALARM SHALL SHUT DOWN FAN AND RUN
EXHAUST FAN CONTINUOUSLY
( I
I SUPPLY /
I /
I �
i
- - - - -�
/ I
/ I
—
STRUCTURAL
SUPPORT BY G.C. I I
I I
J "I- BURGLAR BARS WOOF
16 GA CONT WELDED OPENINGS TYP. BY G.C.
DUCT FROM HOOD COORDINATE w/M.C.
(SEE PLAN FOR SIZE)
HOOD SUPPLY /EXHAUST FAN DETAIL
NTS
EXHAUST AIR DUCT'
GALVANIZED SHEET METAL
SEALED WITH MASTIC
MA
EXHAUST AIR
PLENUM
TRUNKLINE LENGTH
AS REQ'D BY CODE
TRUNKLINE
W /FILTERED INLET
SUPPORT RAILS AS
REQ'D BY M.C.
WATERPROOFING
BY G.C.
GALVANIZED
TRUNK LINE
/a
/ FILTERS:
/ WASHABLE
ALUMINUM
/
ELECTRIC DUCT HEATER, THERMOSTAT
CONTROLLED TO MAINTAIN 707
SUPPLY AIR TEMPERATURE.
DUCT HEATER SHALL BE INTERLOCKED
WITH MAKE -UP AIR FAN
1. PROVIDE EACH FAN W /INTERNALLY PROTECTED MOTOR
2. PROVIDE EACH FAN W /FACTORY MOUNTED AND WIRED
DISCONNECT SWITCH
CEILING (SEE ARCH. DWGS FOR HEIGHT)
L
LL -IN PANEL, FROM TOP OF
HOOD THRU CEILING. ALL
EXPOSED SIDES
'---1 /2 "HANGER RODS
TO STRUCTURE ABOVE
HOOD SUPPORT: PROVIDE BACKING
IN WALL, TO FLOOR. (2) STAINLESS
STEEL. 1/2" BOLT SETS INTO INSERTS,
6" BELOW TOP OF HOOD.
HOOD 2
NTS
NOTES:
1. HOOD SHALL BE BY THE SAME MANUFACTURER AS THE GREASE HOODS.
FINISH SHALL MATCH THE GREASE HOODS. CONSTRUCTION SHALL BE
TO NSF STANDARDS.
HVAC DESIGN REQUIRES: YES NO
NOTE:
* FAN, OUTSIDE AIR INTAKE,
-
OR ROOF EXHAUST CAP:
MECHANICAL SUBCONTRACTOR SHALL
FASTEN TO CURB WITH
PROVIDE ITEMS NOTED WITH *
SCREWS
GENERAL CONTRACTOR SHALL
FIRE RATED ENCLOSURE
-
PROVIDE ITEMS NOTED WITH **
* RESSURE- TREATED
-
** COUNTER FLASHING STRIP
WOOD NAILER STRIP
-
I/
SMOKE CONTROL
-
I/
** Y CANT STRIP
* HEIGHT OF CURB ABOVE
HEAT
z
** ROOFING
ROOF DECK:
B ALL FANS SHALL BE COMPLETE WITH DISCONNECT SWITCH AND CURB.
EXHAUST FAN MFG OD I
8" FOR STANDARD FANS
DU30HFA
CURB FOR BOTH THE EXHAUST AND MAKE -UP AIR FANS AND INTAKE TRUNKUNE
do HOODS
WITH RAIL AND FILTERS.
;,•
18" FOR GREASE EXHAUST
0
:.<<_..�. ''�''"'
;..�..��:;:;.;��;�:: >M�.; ---�'* ROOF INSULATION
FANS
-- ** METAL DECKING
* CURB:
DUCT SIZES SHOWN ON PLAN.
18 GAGE GALVANIZED STEEL,
** STRUCTURAL SUPPORT FRAME,
WELDED. RIGID
D INSULATION.
UNIT do DECKING, AT
3624 VH -1
FULL PERIMETER OF FACTORY
CURB
* CURB SET ON TOP OF METAL DECKING
Al
CURB DETAILS FAN OR GRAVITY VENTILATOR
1. CURBS NOTED ABOVE DO NOT NEED TO BE SET LEVEL, AND CAN BE SET
WITH THE PITCH OF THE ROOF.
2. REFER TO FAN DETAIL FOR BOLTING REQUIREMENTS
TOP JOIST CLAMP
GRINNELL FIG. 227
(R TnTAI l
HOOD HANGING DETAIL
FAN MOTOR
FAN WHEEL
:I[:Ir>�aN�Oi
z_ o
L) HINGED
W FAN BASE—
CL
COMBINATION ROOF
CURB UNIT BY M.C.
INSTALLATION/WATER-
PROOF'G BY G.C. —
ALUMINUM HOUSING
� I
EXHAUST
� I
10'-O"-MIN
REMOVABLE TOP -�
ELECTRICAL CONTROL PACKAGE W /CONTACTORS
AND TERMINAL BLOCKS FOR POWER AND
CONTROL (120/1/60) FACTORY INSTALLED.
ALARM SHALL SHUT DOWN FAN AND RUN
EXHAUST FAN CONTINUOUSLY
( I
I SUPPLY /
I /
I �
i
- - - - -�
/ I
/ I
—
STRUCTURAL
SUPPORT BY G.C. I I
I I
J "I- BURGLAR BARS WOOF
16 GA CONT WELDED OPENINGS TYP. BY G.C.
DUCT FROM HOOD COORDINATE w/M.C.
(SEE PLAN FOR SIZE)
HOOD SUPPLY /EXHAUST FAN DETAIL
NTS
EXHAUST AIR DUCT'
GALVANIZED SHEET METAL
SEALED WITH MASTIC
MA
EXHAUST AIR
PLENUM
TRUNKLINE LENGTH
AS REQ'D BY CODE
TRUNKLINE
W /FILTERED INLET
SUPPORT RAILS AS
REQ'D BY M.C.
WATERPROOFING
BY G.C.
GALVANIZED
TRUNK LINE
/a
/ FILTERS:
/ WASHABLE
ALUMINUM
/
ELECTRIC DUCT HEATER, THERMOSTAT
CONTROLLED TO MAINTAIN 707
SUPPLY AIR TEMPERATURE.
DUCT HEATER SHALL BE INTERLOCKED
WITH MAKE -UP AIR FAN
1. PROVIDE EACH FAN W /INTERNALLY PROTECTED MOTOR
2. PROVIDE EACH FAN W /FACTORY MOUNTED AND WIRED
DISCONNECT SWITCH
CEILING (SEE ARCH. DWGS FOR HEIGHT)
L
LL -IN PANEL, FROM TOP OF
HOOD THRU CEILING. ALL
EXPOSED SIDES
'---1 /2 "HANGER RODS
TO STRUCTURE ABOVE
HOOD SUPPORT: PROVIDE BACKING
IN WALL, TO FLOOR. (2) STAINLESS
STEEL. 1/2" BOLT SETS INTO INSERTS,
6" BELOW TOP OF HOOD.
HOOD 2
NTS
NOTES:
1. HOOD SHALL BE BY THE SAME MANUFACTURER AS THE GREASE HOODS.
FINISH SHALL MATCH THE GREASE HOODS. CONSTRUCTION SHALL BE
TO NSF STANDARDS.
HVAC DESIGN REQUIRES: YES NO
DUCT SMOKE DETECTOR
I/
-
FIRE DAMPER(S)
-
HEAT
SMOKE DAMPER(S)
-
I/
FIRE RATED ENCLOSURE
-
I/
FIRE RATED ROOF /FLOOR
CEILING ASSEMBLY
-
✓
FIRE STOPPING
-
I/
SMOKE CONTROL
-
I/
HOOD NOTES:
1. SUPPLY AND EXHAUST FANS ARE INTERLOCKED WITH PILOT LIGHT
IN KITCHEN.
2. FIRE MODE REQUIRES EXHAUST FAN TO CONTINUE TO OPERATE AND
SUPPLY FAN TO STOP.
3. HOOD EXHAUST FANS SHALL OPERATE WHENEVER THE EXTINGUISHING
SYSTEM IS ACTIVATED.
4. PROVIDE AN ALARM INDICATING OPERATION OF THE HOOD
AUTOMATIC FIRE SUPPRESSION SYSTEM.
5. PROVIDE A HOOD AUTOMATIC FIRE SUPPRESSION SYSTEM
UNDER SEPARATE PERMIT BY OTHERS.
6. FIXED PIPE EXTINGUISHING SYSTEMS IN A SINGLE HAZARD AREA
SHALL BE ARRANGED FOR SIMULTANEOUS AUTOMATIC OPERATION
UPON ACTIVATION OF ANYONE OF THE SYSTEMS. COMMON EXHAUST
DUCT FOR MORE THAN ONE HOOD WOULD DEFINE A SINGLE
HAZARD AREA. EXCEPTION WOULD BE A SECONDARY FIRE
SUPRESSION SYSTEM CONTAINED IN THE COMMON EXHAUST
DUCT.
J
EXHAUST HOOD DUCTWORK
OFFSETS TO GREASE EXHAUST FANS FROM HOOD LOCATION
SHALL BE MADE WITH 2 - 45' ELBOWS. TRANSITION TO FULL
SIZE OF FAN CONNECTION AT CURB.
BILL OF MATERIAL
THE FOLLOWING CONTROLS TO BE FURNISHED BY TEMPERATURE CONTROL CONTRACTOR
NO. QUANTITY MAKE REMARKS
T1 1 (PER UNIT) HONEYWELL T730OA1005 NOTE: FOR MEET ROOM UNIT USE
MODEL 0730OAl018 T7300/0730OB1008 (SWITCHING BASE)
HONEYWELL T7047CIO25 REMOTE SENSOR
(NOTE: EXCEPT MEET ROOM UNIT)
T1 T /07aoo
S[JBBASE
O'
3
RC
TERMINAL EQUIPMENT TRANSFORMER
� c
I
I
I (IF NO 'C' TERMINAL)
LED2
Y2 Y2 cool
I 2
Yt Yt cool
Two (2) #IS AM SHIELDED, T7047
TWISTED PAIR WARES. SENSOR C
MOUNTED.
T7300/07300 (CONFIGURED FOR 2H -2C) USED IN SINGLE TRANSFORMER,
2 STAGE HEATING/ 2 STAGE COOLING SYSTEM WITHOUT ECONOMIZER.
REMOTE SENSOR NOTE:
REMOTE SENSOR (T7047C1025) IS TO BE MOUNTED ON COLUMN (OR WALL),
6' -0" UP. WITH THE SUBBASE (T/07300) LOCATED IN MANAGER'S OFFICE. CONNECT
REMOTE SENSOR TO T -T TERMINALS OF SUBBASE VIA TWO (2) 116 AWG SHIELDED.
TWISTED PAIR WIRES, BELDEN 8719. SEE CONTROL WIRING DIAGRAM.
EXHAUST FAN
Eu-
SEE EXHAUST
FAN SCHEDULE —
8 "0 UP TO
EXHAUST FAN
EE_2
X3/8" WATER B'0
7 "0
6 "0 --/
OVEN
(FAN TO BE CONTROLLED
BY SWITCH ON OVEN DOOR)
FAN MANUFACTURER.
PROGRAM
1 COOLING
76 R
OCCUPIED
HEAT
72 r
UNTIL SUBMITTAL APPROVED BY WINN -DIXIE STORE DESIGN
1 COOLING
85 f
NOT OCCUPIED
22 HEATING
60 OF
HOOD STATIC PRESSURE
2
8 AM OR AS DIRECTED BY OWNER
UNOCCUPIEDO
(OFF)
yyl
AMTEKCO 800 -336 -4677 GREENHECK
1/4
N/A
I
HEAT
z
115V/1e I
N/A
B ALL FANS SHALL BE COMPLETE WITH DISCONNECT SWITCH AND CURB.
EXHAUST FAN MFG OD I
C FAN FOR THE GREASE HOODS SHALL BE THE FAN PACKAGE TYPE WITH COMMON
DU30HFA
CURB FOR BOTH THE EXHAUST AND MAKE -UP AIR FANS AND INTAKE TRUNKUNE
SUPPLY FAN MFG/MOO 1
WITH RAIL AND FILTERS.
N/A
D SINGLE PHASE FANS SHALL INCLUDE BUILT -IN MOTOR OVERLOADS.
0
E COORDINATE EXACT DUCT CONNECTION SIZES AND LOCATIONS WITH
G
ACTUAL HOODS AND FANS SUPPLIED AND PROVIDE TRANSITIONS TO
FAN
DUCT SIZES SHOWN ON PLAN.
CAPTIVE AIRE
AUX
HOOD MODEL NO.
3624 VH -1
Al
�71mal
ES7DE
FIELD WIN
POWER FROM HVAC FEEDERS WITH FUSED PROTECTION
FACTORY WIRING
24 VAC SECONDARY. MUST BE ABLE TO CARRY ADDITIONAL 5 VA LOAD OF
O
THERMOSTAT AND SUBBASE.
O
FIELD INSTALLED JUMPER.
O
24 VAC ONLY.
T7300/07300 (CONFIGURED FOR 2H -2C) USED IN SINGLE TRANSFORMER,
2 STAGE HEATING/ 2 STAGE COOLING SYSTEM WITHOUT ECONOMIZER.
REMOTE SENSOR NOTE:
REMOTE SENSOR (T7047C1025) IS TO BE MOUNTED ON COLUMN (OR WALL),
6' -0" UP. WITH THE SUBBASE (T/07300) LOCATED IN MANAGER'S OFFICE. CONNECT
REMOTE SENSOR TO T -T TERMINALS OF SUBBASE VIA TWO (2) 116 AWG SHIELDED.
TWISTED PAIR WIRES, BELDEN 8719. SEE CONTROL WIRING DIAGRAM.
EXHAUST FAN
Eu-
SEE EXHAUST
FAN SCHEDULE —
8 "0 UP TO
EXHAUST FAN
EE_2
X3/8" WATER B'0
7 "0
6 "0 --/
OVEN
(FAN TO BE CONTROLLED
BY SWITCH ON OVEN DOOR)
HVAC CONTROL DIAGRAM (EACH UNIT)
NO SCALE
"0 7'0
7 "0
1/2 DIST
FROM OVEN
TO ROOF -
STEAM
HOOD 6'0
OVEN
OVEN: BAKER'S AID
BARO -1E, BARO -2E
36 ", OR 24" ABOVE
ANY PARAPET WITHIN
10'0
ROOF
- STOR COLLAR do ROOF
JACK, SEAL ALL SEAMS
WITH "PAR -BOND"
GUTTER SEAL
�•- HEAT AND STEAM
REMOVAL VENT-
SINGLE WALL, SEAL
LIQUID TIGHT WITH
MASTIC
4 "0
NOTE: VENT SHALL
BE INSTALLED STRAIGHT
UP IN THE VERTICAL
FLOOR
SIDE VIEW
OVEN FLUE DETAIL
NTS
EXHAUST HOOD NOTES
1. EXHAUST HOODS SHALL BE CONSTRUCTED OF 18 GAUGE 304 STAINLESS STEEL FOR
ALL SURFACES EXPOSED TO THE AIRSTREAM AND 18 GAUGE GALVANIZED STEEL
FOR OTHER SURFACES. ALL SEAMS AND JOINTS SHALL HAVE A LIQUID TIGHT
U.L APPROVED CONTINUOUS EXTERNAL WELD.
2. ENTIRE SYSTEM SHALL BE CONSTRUCTED IN ACCORDANCE WITH NATIONAL
SANITATION FOUNDATION STANDARDS, NFPA -96, NFPA -17 -A. AND ALL
GOVERNING CODES.
3. EXHAUST HOODS SHALL BE PROVIDED WITH A ANSUL R -102 AUTOMATIC FIRE
EXTINGUISHING SYSTEM FOR PROTECTION OF THE EXHAUST HOOD, PLENUM,
GREASE FILTERS, EXHAUST DUCT AND COOKING EQUIPMENT. THE SYSTEM SHALL
EMPLOY A LIQUID CHEMICAL EXTINGUISHMENT. THE SYSTEM SHALL BE ARRANGED
TO SHUT OFF THE SOURCE OF COOKING HEAT AUTOMATICALLY UPON SYSTEMS
OPERATION. THE SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH NFPA -96,
NFPA -17 -A AND ACCORDING TO MANUFACTURERS PRINTED INSTALLATION PROCEDURES.
EACH HOOD SHALL HAVE A SEPARATE FIRE EXTINGUISHING SYSTEM WHICH WILL
OPERATE EFFECTIVELY WITH OR WITHOUT FANS OPERATING.
4. THE INSTALLER OF THE EXHAUST HOOD AUTOMATIC FIRE EXTINGUISHING SYSTEM
SHALL BRIEF THE BAKERY AND DELICATESSEN PERSONNEL IN ITS OPERATION.
5. EXHAUST AND SUPPLY FANS OF EACH HOOD SHALL BE INTERLOCKED. PROVIDE ONE
LIGHT SWITCH AND ONE FAN SWITCH ON THE FACE OF EACH GREASE HOOD.
6. GREASE FILTERS TO BE FLAME GARD, INC., STAINLESS STEEL U.L CLASSIFIED
FILE i R6593.
EXHAUST HOOD SCHEDULE
FAN MANUFACTURER.
PROGRAM
1 COOLING
76 R
OCCUPIED
2� HEATING
72 r
UNTIL SUBMITTAL APPROVED BY WINN -DIXIE STORE DESIGN
1 COOLING
85 f
NOT OCCUPIED
22 HEATING
60 OF
HOOD STATIC PRESSURE
OCCUPIED
8 AM OR AS DIRECTED BY OWNER
UNOCCUPIEDO
(OFF)
10 PM OR AS DIRECTED BY OWNER
HVAC CONTROL DIAGRAM (EACH UNIT)
NO SCALE
"0 7'0
7 "0
1/2 DIST
FROM OVEN
TO ROOF -
STEAM
HOOD 6'0
OVEN
OVEN: BAKER'S AID
BARO -1E, BARO -2E
36 ", OR 24" ABOVE
ANY PARAPET WITHIN
10'0
ROOF
- STOR COLLAR do ROOF
JACK, SEAL ALL SEAMS
WITH "PAR -BOND"
GUTTER SEAL
�•- HEAT AND STEAM
REMOVAL VENT-
SINGLE WALL, SEAL
LIQUID TIGHT WITH
MASTIC
4 "0
NOTE: VENT SHALL
BE INSTALLED STRAIGHT
UP IN THE VERTICAL
FLOOR
SIDE VIEW
OVEN FLUE DETAIL
NTS
EXHAUST HOOD NOTES
1. EXHAUST HOODS SHALL BE CONSTRUCTED OF 18 GAUGE 304 STAINLESS STEEL FOR
ALL SURFACES EXPOSED TO THE AIRSTREAM AND 18 GAUGE GALVANIZED STEEL
FOR OTHER SURFACES. ALL SEAMS AND JOINTS SHALL HAVE A LIQUID TIGHT
U.L APPROVED CONTINUOUS EXTERNAL WELD.
2. ENTIRE SYSTEM SHALL BE CONSTRUCTED IN ACCORDANCE WITH NATIONAL
SANITATION FOUNDATION STANDARDS, NFPA -96, NFPA -17 -A. AND ALL
GOVERNING CODES.
3. EXHAUST HOODS SHALL BE PROVIDED WITH A ANSUL R -102 AUTOMATIC FIRE
EXTINGUISHING SYSTEM FOR PROTECTION OF THE EXHAUST HOOD, PLENUM,
GREASE FILTERS, EXHAUST DUCT AND COOKING EQUIPMENT. THE SYSTEM SHALL
EMPLOY A LIQUID CHEMICAL EXTINGUISHMENT. THE SYSTEM SHALL BE ARRANGED
TO SHUT OFF THE SOURCE OF COOKING HEAT AUTOMATICALLY UPON SYSTEMS
OPERATION. THE SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH NFPA -96,
NFPA -17 -A AND ACCORDING TO MANUFACTURERS PRINTED INSTALLATION PROCEDURES.
EACH HOOD SHALL HAVE A SEPARATE FIRE EXTINGUISHING SYSTEM WHICH WILL
OPERATE EFFECTIVELY WITH OR WITHOUT FANS OPERATING.
4. THE INSTALLER OF THE EXHAUST HOOD AUTOMATIC FIRE EXTINGUISHING SYSTEM
SHALL BRIEF THE BAKERY AND DELICATESSEN PERSONNEL IN ITS OPERATION.
5. EXHAUST AND SUPPLY FANS OF EACH HOOD SHALL BE INTERLOCKED. PROVIDE ONE
LIGHT SWITCH AND ONE FAN SWITCH ON THE FACE OF EACH GREASE HOOD.
6. GREASE FILTERS TO BE FLAME GARD, INC., STAINLESS STEEL U.L CLASSIFIED
FILE i R6593.
EXHAUST HOOD SCHEDULE
FAN MANUFACTURER.
HOOD !I
DaU-BAKE iY
HOOD N J
(SEAFOOD)
AIR SYSTEMS (800) 722 -3474
SEE SHT. M -501A
EXHAUST
SUPPLY
UNTIL SUBMITTAL APPROVED BY WINN -DIXIE STORE DESIGN
CFM
AEROLATOR SYSTEMS, INC. 704- 821 -7605 LARKIN INDUSTRIES
450
N/A
904 -731 -4711
HOOD STATIC PRESSURE
608 - 845 -6411
.02
N/A
FAB -X METALS, INC. 800- 677 -3229 LOREN COOK CO.
FAN H.P.
AMTEKCO 800 -336 -4677 GREENHECK
1/4
N/A
ELECTRICAL
z
115V/1e I
N/A
B ALL FANS SHALL BE COMPLETE WITH DISCONNECT SWITCH AND CURB.
EXHAUST FAN MFG OD I
C FAN FOR THE GREASE HOODS SHALL BE THE FAN PACKAGE TYPE WITH COMMON
DU30HFA
CURB FOR BOTH THE EXHAUST AND MAKE -UP AIR FANS AND INTAKE TRUNKUNE
SUPPLY FAN MFG/MOO 1
WITH RAIL AND FILTERS.
N/A
D SINGLE PHASE FANS SHALL INCLUDE BUILT -IN MOTOR OVERLOADS.
HOOD SIZE
E COORDINATE EXACT DUCT CONNECTION SIZES AND LOCATIONS WITH
3' -0" X 4' -0"
ACTUAL HOODS AND FANS SUPPLIED AND PROVIDE TRANSITIONS TO
HOOD MFG'R
DUCT SIZES SHOWN ON PLAN.
CAPTIVE AIRE
HOOD MODEL NO.
3624 VH -1
* VERIFY FAN OPENING WITH
FAN MANUFACTURER.
I
DESIGN CRITERIA BASED ON MARSHALL
AIR SYSTEMS (800) 722 -3474
�
THE FOLLOWING ALTERNATE EXHAUST HOOD MANUFACTURERS ARE NOT
APPROVED
UNTIL SUBMITTAL APPROVED BY WINN -DIXIE STORE DESIGN
-4
AEROLATOR SYSTEMS, INC. 704- 821 -7605 LARKIN INDUSTRIES
800- 322 -4036
CAPTIVE -AIRE SYSTEMS, INC. 800- 882 -6626 STANLEY INDUSTRIAL CORP.
904 -731 -4711
SUN -AIR HOODS 800- 633 -4373 CARNES COMPANY
608 - 845 -6411
GREASEMASTER, INC. 704- 821 -9211 PENN VENTILATOR CO.
215 - 464 -8900
FAB -X METALS, INC. 800- 677 -3229 LOREN COOK CO.
417- 869 -6474
AMTEKCO 800 -336 -4677 GREENHECK
715 -355 -2367
Ilm
A) FANS FOR GREASE HOODS SHALL BE UL LISTED FOR OPERATION AT 300 'F AND
z
SHALL CARRY BOTH THE UL762 AND UL705 LABELS.
U
B ALL FANS SHALL BE COMPLETE WITH DISCONNECT SWITCH AND CURB.
L0
C FAN FOR THE GREASE HOODS SHALL BE THE FAN PACKAGE TYPE WITH COMMON
Lli
CURB FOR BOTH THE EXHAUST AND MAKE -UP AIR FANS AND INTAKE TRUNKUNE
�c
WITH RAIL AND FILTERS.
G
D SINGLE PHASE FANS SHALL INCLUDE BUILT -IN MOTOR OVERLOADS.
a
E COORDINATE EXACT DUCT CONNECTION SIZES AND LOCATIONS WITH
ACTUAL HOODS AND FANS SUPPLIED AND PROVIDE TRANSITIONS TO
DUCT SIZES SHOWN ON PLAN.
r
CN
!� W
rl F_
t\ �
U�
Ir^\`
(o I— M
W
W
O
o It °
I V)
Hly-
Q DO
• In
o W
Y 0
U �
• O Z n
O %1
U 0)
I r- Q J
— W
- , SEAL .
re
A,
ENGINEERS
. CO
w "
o_
_ M I
I N
^ cis v
OLjNMn
Z
o_
x
o
W'L Li
Li w f- O
MEM
o
om
;2
REVISIONS:
REVISIONS:
v�
N
cq
yl
o�z
I
d
�} o
�
H~
r-i O
to
I
-4
W M
CO
A �
v
0
rn
III
W
E
Am
Q
I n
z
U
cc
L0
:D
Lli
_Z
�c
O
G
a
v�
N
cq
yl
o�z
I
V
�} o
�
A
r-i O
to
I
-4
W M
CO
A �
v
0
rn
III
W
V
X
Q
W
00
0
V
W
A
0
cy-
0
0
0
J
LL
�
W
V
X
Q
W
00
o
L0
:D
_Z
0
/
DATE:
JUNE 17, 2002
DRAWN BY:
CHECKED BY:
f
K Y PROJECT NO.
WD #0704
DRAWING NO.
M -501 OF -
SHEET NO.
OF _
W
W
0
cy-
0
W
�
vj
0
J
LL
�
W
X
Q
00
L0
:D
_Z
0
/
DATE:
JUNE 17, 2002
DRAWN BY:
CHECKED BY:
f
K Y PROJECT NO.
WD #0704
DRAWING NO.
M -501 OF -
SHEET NO.
OF _