Loading...
05-1059-0220 d 0 0 O O N O " 0 a E a N N N O 0 N O 7 o N v N J a 0 O N w C U �x Y] 0 0 0 a° - N . •o a ' U i N E z° 0 0 r GAS PIPING NOTES: 1. GAS PIPE SIZES BASED ON PRESSURE DROP OF 0.5, WATER COL. GAS SPECIFIC GRAVITY OF 0.6 AND SCHEDULE 40 BLACK STEEL PIPE 4.00 W.C. MINIMUM PRESSURE AND 14.00 W.C. MAXIMUM PRESSURE. 2. GAS PIPING SHALL BE INSTALLED IN ACCORDANCE WITH NFPA -54 AND THE STANDARD GAS CODE. (1991) 3. THE INSTALLATION SHALL BE FOR PROPANE GAS AND BE INSTALLED BY A LICENSED SUB - CONTRACTOR. (VERIFY SUPPLIER) 4. A NEW GAS METER AND PRESSURE REGULATOR SHALL BE PROVIDED BY THE UTILITY COMPANY. 5. GAS PIPING SHALL BE SCHEDULE 40 SEAMLESS BLACK STEEL PIPE AND BLACK IRON FITTINGS. GAS PIPING OUTSIDE THE BUILDING SHALL BE PAINTED WITH BLACK 'RUSTOLEUM' PAINT. 6. GAS PIPING SHALL BE PROVIDED WITH DRIP POCKETS AND DIRT LEGS IN ACCORDANCE WITH CODE REQUIREMENTS. 7. A GAS COCK AND QUICK- RELEASE FITTING SHALL BE PROVIDED AT ALL GAS APPLIANCES W/ CHAIN RESTRAINTS. 8. PROVIDE AN ACCESSIBLE MECHANICALLY OPERATED UL APPROVED GAS VALVE BELOW CEILING FOR EMERGENCY SHUT -OFF. COORDINATE WITH FIRE PROJECT SYSTEM. GAS VALVE SHALL BE MANUALLY RE -SET. 9. SEE SEPARATE HOOD DRAWINGS AND HOOD DETAILS FROM HOOD MANUFACTURER. 10. ALL GAS VALVES WILL BE INSTALLED IN ACCESSIBLE LOCATION. GAS METER & PRESSURE SET BY LOCAL GAS COMPANY GAS PLAN 1/4" = 1' -0" PROVIDE MECHANICAL SHOCK ABSORBER FOR SOLENOID VALVE FOR ALL WATER PROOF CONNECTIONS AS PER FBC 604.9 LONGEST RUN OF GAS LINE TO METER IS 73.66' TOTAL BTU = 414,600 1 1/2" GAS LINE Q,s q N 8) S S• \ cq s G7 \ N C 1 1/2" �S` / I IMF 2" BALL VALVE, MAIN SHUT —OFF G7 D N GAS P. R. 10.00' D N EXIST. GAS M ETER �� C34�3 / / 3" LINE DOWN D Sd� 'MANUAL SOV W 1 10.00' DRIP LEG c� SHUT OFF VALVE D 0 D U) 1/2" GAS BALL TO GAS WTR. HTR. 75,100 BTU's 1/2" GAS BALL FOR A HOT FOOD /STEAM TABLE 17.5K > BTU'S DRIP DRIP LEG 1 1/2" LINE LE Sb� BELOW CEILING MASTER GAS SHUT OFF VALVE INTERLOCKED WITH HOOD SUPPRESION SYSTEM TO SHUT OFF UPON ACTIVATION 3/4" GAS BALL \ S FOR A 6— BURNER S, 60• RANGE /GRIDDLE 110 W /OVEN 202K \ BTU'S Sb� 3/4" GAS BALL TO FRYER 120K BTU's GAS RISER N.T.S. NOTE: CONTRACTOR SHALL VERIFY MOUNTING HEIGHTS OF GAS EQUIPMENT FOR STUB —UP's PRIOR TO GAS PIPING ROUGH —IN. SEE ADDITIONAL GAS NOTES, THIS SHEET. NOTE: GAS METER SHOWN IS FOR DIAGRAMATIC PURPOSES ONLY AND IS NOT THE ACTUAL LOCATION OF METER AT SITE. SEE SITE PLAN FOR A MORE ACURATE DESCRIPTION OF METER LOCATION. CONTRACTOR SHALL FIELD VERIFY PRECISE LOCATION PRIOR TO PERFORMING HIS /HER WORK. PROVIDE BELOW CEILING MASTER GAS SHUT OFF VALVE INTERLOCKED WITH HOOD SUPPRESION SYSTEM TO SHUT OFF UPON ACTIVATION PROVIDE SHUT —OFF VALVE ® EACH GAS LINE DOWN cis \ 1" s Q, "�H 10.00' 2 GPS' GPS G. "J .�� GPS GPS GPS D G7 D U) G) D U) 1/2" GAS BALL TO GAS WTR. HTR. 75,100 BTU's DRIP LEG William hamilton arthur architect Inc. 800 douglas entrance suite 303 coral gables, florida, 33134 (305)443 -3100 fax (305)441 -7960 license no. 2282 DRAWN BY: M.M.H. SEAL: h y.. REVISION DATE(S) 0 PROJ. NO: F— 05 -25 04.23.05 z �N P 9 D F- U) U) w Q CD z z L,L Q ~ I— W 0 O UQ �z �o w J Qz ~ 0 Q rw\ W N REVISION DATE(S) 0 PROJ. NO: F— 05 -25 04.23.05 z NO.: P 9 D F- U) w z o% U) I— W 0 UQ W M rw\ _ / Q O Ld z > a Z _ U) W Li _ Q Z Ld O F- F- Z0(r J LLI Wm U U Ld o 0 ^ _ 00W ¢o L L� � REVISION DATE(S) 0 PROJ. NO: DATE: 05 -25 04.23.05 SHEET NO.: P 3 12 OF 13 .c J ,1