ELECTRICAL PREWIRE PACKAGE JOB NAME
DRAWING NUMBER 21111002 JOB NUMBER •
CONTROL INPUT 120VAC H1 =LINE, N1= NEUTRAL 15A BKR
LIGHT INPUT 120VAC H2 -H5 =LINE, N2- N5= NEUTRAL 15A BKR
15 LS -01
H2 B L W N2
16
17
1 P C SE 208V
18 INPUT L1 L1 T1 21 EXH -1 GR
1 PHASE L2 L2 T2 22
A
19 0
20 1 PHASE 208V
L1 T1 23 GR
2 WIC L3 L2 T2 24 SUP -2 -
21 1 PHASE L4 3
22
23
24
DATE
DRAWN BY
Electrical Package Description
220V /1Ph, W/ 1 Exhaust Fan, 1 Supply
Fan, Exhaust in Fire
Label DescriRtlon
ST Starter
FS Fan Switch (Lighted)
MS MlcroSwltch (Ansul or PyroChem)
R1 Relay DPDT
LS Light Switch
L Hood Light(s)
GP General Purpose Relay DPDT
TX Transformer
C Contactor
G Ground
AF Air Flow Switch
Spare Relay MS -1 MS -2 MicroSwitcl
Contacts Ansul Pyrochem
C -RD C -RD C -RD
NO -BL NO-8K NO -BK
NC -PR NC -BR NC -BR
1 NC 3 SPARE RELAY CONTACTS
4 NO 6 CAN BE USED TO CONTROL
ITEMS REQUIRING SHUT
7 CON 9 DOWN WHEN THE FIRE
A COIL B SYSTEM DISCHARGES,
SUCH AS SHUNT TRIP,
R1 -R5 RELAY SIGNALS, ETC -
TERMINATIONS
,Spare Relay Contacts
R2 -1 TERMINAL FOR FIEL:
NO3 NC C IIRENPANEL, DRY
NC3 CONTACTS FOR
NO SIGNAL ONLY
C3
R2 -2 MS -2
N04 NC C MNO C
NC4
C4 NO
Motor
Type
IPHIVolt
SUPPLY FAN
IHP
I FLA
I BREAKER
Exh -1
Exh
11
12081
VOLT
FLA
BLOWER
Sup-2
Su
1
208
RPM
H.P.
0
DENOTES FIELD WIRING
DENOTES INTERNAL WIRING
WIRE COLOR
BK - BLACK YW - YELLOW
BL - BLUE GY - GRAY
BR - BROWN PR - PURPLE
OR - ORANGE OR /BL - ORANGE /BLUE
RD - RED (STRIPE)
WH - WHITE BL /RD - BLUE /RED
(STRIPE)
RD /GN - RED /GREEN
(STRIPE)
DRAWING SHOWN DE- ENERGIZED
NOTEr IF WALL MOUNT PREWIRE, OR
FIELD INSTALLED FIRE SYSTEM
MICROSWITCH, THE TERMINALS SHOWING
FACTORY WIRING MUST BE FIELD WIRED.
12 x 18 x 6 Box Size
FAN TWMRMATinx
FAN
UNIT
NO,
FAN UNIT MODEL 0
EXHAUST FAN
SUPPLY FAN
MODEL
TAG
CFM
S.P.
RPM
H.P.
0
VOLT
FLA
BLOWER
HOUSING
TAG
CFM
S.P.
RPM
H.P.
0
VOLT
FLA
EF -1
NCAI6FA
KEF -I
NCAI6FA
2125
-1.000
925
0.750
1
208
5.2
STOP SUPPLY FAN.
- HIGH HEAT OPERATION 300•F 049'()
BUILDINGS, PROPERTY LINES, AIR INTAKES
OR 3 FT. VERTICAL CLEARANCE PER NFPA96
C. HOOD EXHAUST FANS SHALL OPERATE WHENEVER THE EXTINGUISHING
- GREASE CLASSIFICATION TESTING
SF -1
NSAU.1 -GIC
KSF -1
8. HORIZONTAL EXHAUST DUCT TO SLOPE BACK TO
NORMAL TEMPERATURE TEST
EXHAUST FAN MUST OPERATE CONTINUOUSLY
HOOD, CHECK LOCAL CODE FOR REQUIRED PITCH.
A FIXED PIPE EXTINGUISHING SYSTEMS IN A SINGLE HAZARD AREA -
GIO
NSAU 1
F WHILE EXHAUSTING AIR AT 3007 (149'0
1700
0.500'
743
0.750
1
208
52
SECTION VIEW OF FAN #KEF 1
MIN. 40'
MIN. 26'
EXHAUST DUCT
16 GA. GALVANIZED
WELDED LIQUID TIGHT
EXISTING 35' SQ.
SUPPLY FAN CURB
EXISTING ROOF
HINGED BASE
GREASE DRAIN
�-- #10 TEK SCREW - EVERY 12' MIN.
•-16 GA. FLAT ROOF CURB
1/4' X 6' SELF TAPPING SCREW)
TOGGLE BOLT OR THREADED ROD EXISTING WOOD TRUSSES
AT CORNERS AND 12 ON CENTER
MAX FOR ALL FAN CURBS AND
PLATFORMS ABOVE WILL PROVIDE
A CONNECTION OF FAN CURB
TO ROOF THAT WILL WITHSTAND
WIND LOADS OF 140 MPH WITH
SAFETY FACTOR OF AT LEAST (4)
SECTION VIEW OF FAN #KSF 1
EXISTING ROOF
INSULATION
TOGGLE BOLT OR THREADED ROD
AT CORNERS AND 12' ON CENTER
MAX FOR ALL FAN CURBS AND
PLATFORMS ABOVE WILL PROVIDE
A CONNECTION OF FAN CURB
TO ROOF THAT WILL WITHSTAND
WIND LOADS OF 140 MPH WITH
SAFETY FACTOR OF AT LEAST (4)
NCAFA SERIES UPBLAST EXHAUST FAN (UL762) jKEF
-1
FEATURES;
- ROOF MOUNTED FANS
W
SERVICE
DISCONNECT
SWITCH
BLOWER /MOTOR
ACCESS DOOR
C
- RESTAURANT MODEL
TOGGLE BOLT OR THREADED ROD
AT CORNERS AND 12' ON CENTER
MAX FOR ALL FAN CURBS AND
PLATFORMS ABOVE WILL PROVIDE
A CONNECTION OF FAN CURB
TO ROOF THAT WILL WITHSTAND
WIND LOADS OF 140 MPH WITH
SAFETY FACTOR OF AT LEAST (4)
NCAFA SERIES UPBLAST EXHAUST FAN (UL762) jKEF
-1
FEATURES;
- ROOF MOUNTED FANS
W
B
C
- RESTAURANT MODEL
R
I RO
I WEIGHT
LB
- UL762
33 3/4
38
1 2
1 es
- AMCA SOUND AND AIR CERTIFIED
1 16 1/2
24 1/2
190
1 20
I 20
1 26
- WIRING FROM MOTOR TO DISCONECT SWITCH
16' X 20'
175 LBS
OVER SCALE.
7. FAN TO HAVE A MINIMUM OF 10 FT. OF
- WEATHERPROOF DISCONNECT
•:
ti -
CLEARANCE FROM THE OUTLET TO ADJACENT
STOP SUPPLY FAN.
- HIGH HEAT OPERATION 300•F 049'()
BUILDINGS, PROPERTY LINES, AIR INTAKES
OR 3 FT. VERTICAL CLEARANCE PER NFPA96
C. HOOD EXHAUST FANS SHALL OPERATE WHENEVER THE EXTINGUISHING
- GREASE CLASSIFICATION TESTING
HT
8. HORIZONTAL EXHAUST DUCT TO SLOPE BACK TO
NORMAL TEMPERATURE TEST
EXHAUST FAN MUST OPERATE CONTINUOUSLY
HOOD, CHECK LOCAL CODE FOR REQUIRED PITCH.
A FIXED PIPE EXTINGUISHING SYSTEMS IN A SINGLE HAZARD AREA -
F WHILE EXHAUSTING AIR AT 3007 (149'0
SHALL BE ARRANGED FOR SIMULTANEOUS AUTOMATIC OPERATION
ON ALL OPEN SIDES.
UPON ACTIVATION OF ANYONE OF THE SYSTEMS.
UNTIL ALL FAN PARTS HAVE REACHED
E. GAS AND ELECTRICAL EQUIPMENT AND OUTLETS SERVED BY THE
COMBUSTIBLES PER NFPA96 AND LOCAL CODE.
HOOD SHALL BE DEACTIVATED IN THE EVENT OF A FIRE SYSTEM
THERMAL EQUILIBRIUM, AND WITHOUT ANY
ACTUATION PER NFPA 96 7 -3.
WATER COLUMN AT EXTERIOR DOORS.
F. ACTUATION OF THE FIRE SYSTEM SHALL SIGNAL THE ALARM SYSTEM
12. KITCHEN SHALL BE BALANCED TO BE NEGATIVE
DETERIORATING EFFECTS TO THE FAN WHICH
SERVING THE AREA OCCUPIED BY THE HOOD PER NFPA96 7 -3.
WITH RESPECT TO THE DINING ROOM.
GREASE
DRAIN
WOULD CAUSE UNSAFE OPERATION.
L
B
ABNORMAL FLARE -UP TEST
EXHAUST FAN MUST OPERATE CONTINUOUSLY
WHILE EXHAUSTING BURNING GREASE VAPORS
/
R
\
AT 600'F (316'0 FOR A PERIOD OF
15 MINUTES WITHOUT THE FAN BECOMING
WR *3'
DAMAGED TO ANY EXTENT THAT COULD CAUSE
\\
2G AN UNSAFE CONDITION.
RO
OPTIONS:
\\
GREASE
/
C
FANX
F•- - ^ - - - - - - - - - "-
PITCHED CURB
INSULATED CURB
DUCTWORK BETWEEN
NCAFA BELT DRIVE
EXHAUST RISER ON HOOD
CENTRIFUGAL UP-BLAST EXHAUST FANS DIMENSIONAL DATA
AND FAN (BY OTHERS)
FAN MODEL
HT
I W
B
C
F
R
I RO
I WEIGHT
LB
NCAI6FA
33 3/4
38
1 2
1 es
23 I/2
1 16 1/2
24 1/2
190
NSAU -1 SERIES DOWN DISCHARGE SUPPLY FAN #KSF -1
�1
EXTERNAL SERVICE DISCONNECT
A
SUPPLY FAN
ELECTRICAL DROP
H
L
.�j
D
D
r VENTED
CURB
E
20 GAUGE
STEEL
CONSTRUCTION
/ 3' FLANGE
\- ROOF OPENING
RO r/ DIMENSIONS
SUPPLY AIR UNIT DIMENSIONAL DATA
PITCHED CURBS ARE AVAILABLE 7
FOR PITCHED ROOFS.
30•
SPECIFY PITC14 12
EXAMPLE] 7/12 PITCH - 300 SLOPE
CURB DIMENSIONAL DATA
FAN MODEL
D
E
NCAI6FA
26 1/2
20
MODEL
BLOWER
HP
I RANGE
A
B
C
D
E
F
FILTER
QTY.
FILTER SIZE
WEIGHT
NSAU -1
G -10
.33 - 2
1 26
1 32
1 28
1 20
I 20
1 26
1 2
16' X 20'
175 LBS
GALVANIZED SUPPLY FAN
FILTER
r � AIR INTAKE THROUGH FILTER
E
CURB WITH 20 GA. CONSTRUCTION
3' CONTINUOUS FLASHING
U
,,�- BLOWER OUTLET SIZE
ROOF OPENING
CURB /ROOFTOP DIMENSIONAL DATA
MODEL
BLOWER
G
H
J
K
NSAU -1
G -10
23
14
U -3/4
1 13 -1/2
PITCHED CURBS ARE AVAILABLE
FOR PITCHED ROOFS
SPECIFY P�TCHl �.
EXAMPLES /12 PITCH - 30• SLOPE
CAPTIV[- JNIIC�f� N[SL'RVCS M RIG1T i0 ICY M % INTnW" cam
PFAMO KT MTM rFM OHIO ALf[AFCM M& siVVJr 0R.
CAPTIVE -AIRE HODS ARE
BUILT IN C ❑MPLIANCE WITH
BUILT NSF ACS
NFPA
No. 96 0%
NFPA #96
NSF
UL 710 & ULC710 STANDARDS
E,T,L, LISTED 3054804 -001
GENERAL N ❑TES ,
1. ELECTRICAL HOOK -UP TO MOTOR CONTROLS
(MOTOR STARTERS, FAN SWITCHES,
r
FAN DISCONNECTS, RELAYS, ETC.) BY OTHERS.
ALL SEAMS AND JOINTS TO HAVE A LIQUID
2. FIRE CHASE BY OTHERS, IF REQUIRED.
c•,
s �,
3. ALL PHASES OF INSTALLATION SHALL COMPLY
IN KITCHEN AREA.
WITH 2001 VERSION OF NFPA 96.
4. WRITTEN MEASUREMENTS HAVE PRECEDENCE
TIGHT CONTINUOUS EXTERNAL WELD.
OVER SCALE.
7. FAN TO HAVE A MINIMUM OF 10 FT. OF
5. PROVIDE CLEANOUTS IN EXHAUST AIR
•:
ti -
CAPTIVE -AIRE HODS ARE
BUILT IN C ❑MPLIANCE WITH
BUILT NSF ACS
NFPA
No. 96 0%
NFPA #96
NSF
UL 710 & ULC710 STANDARDS
E,T,L, LISTED 3054804 -001
FOR QUESTIONS, PLEASE CALL JOB POBLANO MEXICAN RESTAURANT
CAPTIVE AIRE SYSTEMS, INC. — _ LOCATION SOUTH MIAMI
PHONES (954) 579 -8595 ^ _ AV - DATE 07/30/2005 JOB jf
FAXt (954) 578 -8596 �i
rvg630cnpt1ven1r.con • , -� DWG 1 2 OF 2 DRAWN BY CAS
REY. I SCALE
DUCTS AS INDICATED TO ALLOW CLEANING
AT ALL BENDS AND HORIZONTAL RUNS.
6. EXHAUST DUCT TO BE 16 GA. CARBON STEEL
�
ALL SEAMS AND JOINTS TO HAVE A LIQUID
A. SUPPLY AND EXHAUST FANS ARE INTERLOCKED WITH PILOT LIGHT
IN KITCHEN AREA.
TIGHT CONTINUOUS EXTERNAL WELD.
7. FAN TO HAVE A MINIMUM OF 10 FT. OF
B. FIRE MODE REQUIRES EXHAUST FAN TO OPERATE CONTINUALLY AND,
CLEARANCE FROM THE OUTLET TO ADJACENT
STOP SUPPLY FAN.
BUILDINGS, PROPERTY LINES, AIR INTAKES
OR 3 FT. VERTICAL CLEARANCE PER NFPA96
C. HOOD EXHAUST FANS SHALL OPERATE WHENEVER THE EXTINGUISHING
SYSTEM IS ACTIVATED.
8. HORIZONTAL EXHAUST DUCT TO SLOPE BACK TO
HOOD, CHECK LOCAL CODE FOR REQUIRED PITCH.
A FIXED PIPE EXTINGUISHING SYSTEMS IN A SINGLE HAZARD AREA -
9. HOOD TO OVERHANG COOKING EQUIPMENT 6'
SHALL BE ARRANGED FOR SIMULTANEOUS AUTOMATIC OPERATION
ON ALL OPEN SIDES.
UPON ACTIVATION OF ANYONE OF THE SYSTEMS.
10. EXHAUST DUCT TO BE PROTECTED FROM
E. GAS AND ELECTRICAL EQUIPMENT AND OUTLETS SERVED BY THE
COMBUSTIBLES PER NFPA96 AND LOCAL CODE.
HOOD SHALL BE DEACTIVATED IN THE EVENT OF A FIRE SYSTEM
11. BUILDING PRESSURE SHALL NOT EXCEED 0. 02'
ACTUATION PER NFPA 96 7 -3.
WATER COLUMN AT EXTERIOR DOORS.
F. ACTUATION OF THE FIRE SYSTEM SHALL SIGNAL THE ALARM SYSTEM
12. KITCHEN SHALL BE BALANCED TO BE NEGATIVE
SERVING THE AREA OCCUPIED BY THE HOOD PER NFPA96 7 -3.
WITH RESPECT TO THE DINING ROOM.
FOR QUESTIONS, PLEASE CALL JOB POBLANO MEXICAN RESTAURANT
CAPTIVE AIRE SYSTEMS, INC. — _ LOCATION SOUTH MIAMI
PHONES (954) 579 -8595 ^ _ AV - DATE 07/30/2005 JOB jf
FAXt (954) 578 -8596 �i
rvg630cnpt1ven1r.con • , -� DWG 1 2 OF 2 DRAWN BY CAS
REY. I SCALE