44.34 KVA
67.20 KW / 360 = 190.00 AMPS
2 2.8 6 KVA
EXISTING COMPRESSORS.
ELECTRICAL SCHEDULE PANEL "A"
TYP. DUPLEX RECEPTACLE
TYPE SQ. D / 10,000 A.I.C. MAINS MLO/ 225 AMP
MOUNT SURFACE BUS 225 AMP
LOC. SEE PLAN VOLTS: 120/208
CIRC.
POLE
KVA
DESCRIPTION
WIRE COND.
CIRC.
POLE
KVA
DESCRIPTION
WIRE COND.
1
1/20
1.50
REACH IN FREEZER
2-#12 1/2-
2
1/20
1.30
WORKTOP REFRIGERATOR
2-#12 1/2"
3
1/20
1.20
COUNTERTOP WARMER
2 - #12 1/2"
4
1/20
1.30
REACH -IN REFRIGERATOR
2 - #12 1/2 r'
5
1/20
1.50
SL. DOOR REFRIG.
2-#12 1/2-
6
1/20
1.50
REACH IN REFRIGERATOR
2-#12 1/2"
7
1/20
1,20
HOT FOOD WELL
2 - #12 1/2"
8
2/30
2.20
HI -TEMP SANITIZER
2 - #12 1/2"
2-#12 1/21p
9
1/20
.40
SOUP WELL
2-#12 1/2-1
10
11
3/100
26.30
SUB -PANEL "B"
#3 2"
12
1/20
1.50
ICE MACHINE
2 - #12 1/2"
13
14
1/20
1.50
SANDWICH UNIT (MEGA)
2 - #12 1/2 Is
15
16
1/20
1,20
INFRARED FOOD WARME
2 -# 12 1/2"
17
1/20
.75
SODA DISPENSERS
2 - #12 1/2"
18
1/20
1.50
ELECTRIC CHEESEMELTE
2 -# 12 1/2"
19
1/20
1.50
SMALL APPLIANCE
2-#12 1/2"
20
1/20
1.50
SMALL APPLIANCE
2 - #12 1/2's
21
1/20
1.50
SMALL APPLIANCE
2-#12 1/2"
22
1/20
1.50
SMALL APPLIANCE
2-#12 1/2"
23
1/20
.25
P.O.S.
2-#12 1/219
24
1/20
,54
WINDOW OUTLET
2-#12 1/20'
25
1/20
.50
GENERAL USE
2-#12 1/299
26
1/20
1.20
EXTERIOR SIGN
2-#12 1/2"
27
1/20
.20
PHONE SYSTEM
2-#12 1/2"
28
1/20
1.20
WATER FEATURE
2-#12 1/2's
29
1/20
.50
MUSIC SYSTEM
2-#12 1/2"
30
1/20
.86
BATHROOM LIGHTS
2-#12 1/211
31
1/20
1.28
LIGHTING
2 - #12 1/2"
32
1/20
1.12
KITCHEN LIGHTS
2 - #12 1/2"
33
1/20
1.28
LIGHTING
2 - #12 1/2"
34
1/20
.36
NIGHT LIGHTING
2 - #12 1/2"
35
1/20
1.44
LIGHTING
2-#12 1/2"
36
1/20
.50
HOOD LIGHTS
2-#12 1/2"
37
1/20
1.44
LIGHTING
2-#12 1/2-
38
1/20
.80
LIGHTING
2-#12 1/2"
39
1/20
1.60
LIGHTING
2 - #12 1/2"
40
1/20
1.28
LIGHTING
2 - #12 1/2"
41
-
-
BLANK
- -
42
-
-
BLANK
_ -
44.34 KVA
67.20 KW / 360 = 190.00 AMPS
2 2.8 6 KVA
EXISTING COMPRESSORS.
13.80 KVA
12.50 KVA
26.30 KVA / 360 = 70.00 AMPS
THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL NECESSARY
CONNECTIONS & METHODOLOGY FROM METER TO NEW PANEL AS INDICATED.
IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE
EXISTING AVAILABLE VOLTAGE VERSUS WHAT IS PROPOSED PRIOR TO
FINALIZED BID TO FRANCHISEE.
SEE FRANCHISEE PROVIDED CUT - SHEETS FOR ALL EQUIPMENT AND
HOOD SYSTEM PRIOR TO SUBMITTING BID.
/-- /,-I N
WTR. HTR.
B -14,16
+18"
ELEC. FLOOR PLAN
1/4" = 1 P -01'
ELECTRICAL LEGEND
ELECTRICAL SCHEDULE PANEL "B" (SUB - PANEL)
TYP. DUPLEX RECEPTACLE
TYPE SQ. D / 10,000 A.I.C. MAINS M.C.B.
MOUNT SURFACE MOUNTED BUS 150 AMP
LOC. SEE PLAN VOLTS: 120/208
CIRC.
POLE
KVA
DESCRIPTION
WIRE COND.
CIRC.
POLE
KVA
DESCRIPTION
WIRE COND.
1
3/60
7.50
H.V.A.C. SYSTEM #1
4 TONS
(NEW SYSTEM /REPLACEMENT)
W/ 7.5 KW HT. STRIP
#6 1 vp
2
3/60
9.50
H.V.A.C. SYSTEM #2
6.0 TONS
(NEW SYSTEM /REPLACEMENT)
W/ 7.9 KW HT. STRIP
#6 110
3
4
5
6
7
3/20
2.50
HOOD SYSTEM
EF# 1
#12 1/2 to
8
1/20
1.00
ANSUL SYSTEM #1
2-#12 1/2"
9
10
1/20
1.00
SPARE
2-#12 1/219
11
12
1/20
1.00
SPARE
- #12 1/2"
13
3/30
3.80
HOOD SYSTEM
SF #1, 1.5 hp
#12 1/2"
14
2/20
3,80
ELEC. WTR. HTR. 120G.
#12 1/2"
15
16
17
18
--
--
BLANK
- -- --
19
--
--
--
--
--
--
BLANK
BLANK
BLANK
__
--
--
20
--
--
BLANK
- -- --
21
22
--
--
BLANK
- -- --
23
24
--
--
BLANK
- -- --
13.80 KVA
12.50 KVA
26.30 KVA / 360 = 70.00 AMPS
THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL NECESSARY
CONNECTIONS & METHODOLOGY FROM METER TO NEW PANEL AS INDICATED.
IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE
EXISTING AVAILABLE VOLTAGE VERSUS WHAT IS PROPOSED PRIOR TO
FINALIZED BID TO FRANCHISEE.
SEE FRANCHISEE PROVIDED CUT - SHEETS FOR ALL EQUIPMENT AND
HOOD SYSTEM PRIOR TO SUBMITTING BID.
/-- /,-I N
WTR. HTR.
B -14,16
+18"
ELEC. FLOOR PLAN
1/4" = 1 P -01'
ELECTRICAL LEGEND
DATE:
TYP. DUPLEX RECEPTACLE
04.23.05
TYP. QUADPLEX RECEPTACLE
NO.:
TYP. DUPLEX CEILING OUTLET
a
TYP. PHONE OUTLET
zry
TYP. PHONE /DATA OUTLET
OJUNCTION
BOX
GFI
DENOTES GROUND FAULT
INTERRUPTER.
WP
DENOTES WEATHERPROOF.
X 10' GROUND
RODSs
ELECTRICAL-- NOTES. � -
1. ALL WORK SHALL BE DC-NE IN ACCnF�DANc;E WI_TA __ME LATEST APPROVED EDITION OF THE
FLORIDA BUILDING CODE. THE- NATIONAL kL�C- TRICAC CODE, NFPA AND ANY APPLICABLE LOCAL
CODES AND ORDINANCES. -- -
2. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL ELECTRICAL CONNECTIONS UNLESS
OTHERWISE NOTED.
3. THE ELECTRICAL CONTRACTOR SHALL ESE RFSPONSIaE FOR COMMUNICATION WITH THE
OWNER'S PERSONNEL TO REVIEW CON RACr DOCJMEn i S PRIOR TO INSTALLATION.
4. THE OWNER WILL NOT BE HELD LIABLE FOR FIELD CHANGES THAT MAY ARISE FROM
CONTRACTOR ERROR OR OMISSION OF MATERIALS OR WORKMANSHIP IN TRADE PERFORMANCE.
5. IN GENERAL, PLANS AND DETAILS ARE DIAGRAMMATIC ONLY AND SHOULD NOT BE SCALED
COORDINATE ALL ELECTRICAL WORK WITH PLUMBING, HVAC AND FIRE SUPPRESSION WORK SO
AS NOT TO CONFLICT IN LOCATION OR PERFORMANCE OF OTHER SYSTEMS
6. NECESSARY, OBVIOUSLY REQUIRED ELECTRICAL ITEMS THAT ARE NOT SHOWN ON THE
DRAWINGS DOES NOT RELIEVE THE CONTRACTOR OF THEIR RESPONSIBILITY TO INSTALL A
COMPLETE OPERATING AND SAFE ELECTRICAL SYSTEM.
7. ELECTRICAL CONTRACTOR SHALL KEEP A MASTER SET OF BLUE LINES THAT ARE TO BE
MARKED UP TO REFLECT "AS BUILT" CONDITIONS ON A DAILY BASIS. THESE "AS BUILT"
MARK -UPS MAY BE REVIEWED BY THE ARCHITECT, ENGINEER, OR OWNER'S REPRESENTATIVE, AT
THEIR REQUEST AND WITHOUT PRIOR NOTIFICATION. THESE "AS BUILT" DRAWINGS WILL BE
TURNED OVER TO THE OWNER AT THE CONCLUSION OF THE PROJECT.
8. THE ELECTRICAL CONTRACTOR SHALL INCLUDE ALL NECESSARY FEES AND POWER COMPANY
CHARGES IN HIS BID.
9. CONTRACTOR TO VISIT THE SITE AND ALLOW FOR ALL EXISTING CONDITIONS IN HIS BID.
10. THOROUGHLY REVIEW FINAL LOCATION, TYPE, MOUNTING HEIGHT AND CONTROL OF ALL
DEVICES PRIOR TO ROUGH IN.
11. COORDINATE FINAL INSTALLATION REQUIREMENTS WITH PROPER AUTHORITIES.
12. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY AND ALL INSPECTIONS AND
CERTIFICATIONS THAT MAY BE REQUIRED, DURING AND UPON COMPLETION OF HIS WORK.
13. ALL ELECTRICAL DEVICES AND EQUIPMENT SHALL BE EFFECTIVELY GROUNDED IN
ACCORDANCE WITH NATIONAL ELECTRICAL CODE REQUIREMENTS. ALL BRANCH CIRCUITS
SHALL HAVE A SEPARATE GREEN INSULATED GROUND WIRE IN EACH CONDUIT RUN.
14, ALL BRANCH CIRCUIT CONDUCTORS SHALL BE MIN 75d c /THHW /THWN COPPER MINIMUM
SIZE SHALL BE No. 12 RUN IN APPROVED METAL RACEWAY.
15. FOR 20 AMP BRANCH CIRCUITS GREATER THAN 10OFT IN LENGTH ONE WAY, UP TO 200 FT.
USE No. 10 WIRE OVER 200 FT. USE No. 8 WIRE. INCREASE CONDUIT SIZE AS REQUIRED FOR
THE LARGER CONDUCTORS THIS SUPERSEDES WIRE SIZES CALLED FOR ON THE DRAWINGS.
16. RIGID CONDUIT SHALL BE GALVANIZED STEEL HOT DIPPED OR SHERADIZED STEEL ZINC
COATED AND SHALL BEAR THE UNDERWRITER'S LABORATORY LABEL. CUT THREADS SHALL
BE FULL DIE CUT AND PROTECTED FROM RUST,
17. RIGID CONDUIT SHALL BE USED WHERE INSTALLATION IS BELOW GRADE, IN CONCRETE,
SLABS, EXPOSED TO WEATHER IN DAMP LOCATIONS, IN EXTERIOR WALLS, IN CONCRETE
BLOCK WALLS INTERIOR OR EXTERIOR AND IN CONNECTION TO PANEL BOARDS AND
CABINETS.
18. RIGID CONDUIT ENTERING AND LEAVING PANEL BOARDS, CABINETS AND OUTLET BOXES,
SHALL BE PROVIDED WITH LOCKNUTS ON BOTH SIDES OF SUCH DEVICES AND DRIVEN TIGHT
TO MAINTAIN POSITIVE ELECTRICAL AND MECHANICAL CONTINUITY THROUGH THE CONDUIT
SYSTEM, INSULATED BUSHINGS SHALL BE INSTALLED INSIDE THE TERMINATIONS MINIMUM
TRADE SIZE OF RIGID CONDUIT SHALL BE HALF INCH.
19. INSTALLATION IN GENERAL, ALL RACEWAYS SHALL RUN CONCEALED WITHIN WALLS, CEILINGS,
OR FLOORS UNLESS OTHERWISE INDICATED OR SPECIFIED. WHERE IMPOSSIBLE TO RUN
CONCEALED, A SURFACE MOUNTED METAL RACEWAY ADEQUATELY PROTECTED AND
SUPPORTED MAY BE USED WITH WRITTEN AUTHORITY OF ARCHITECT AND OWNER.
20. ELECTRICAL METALLIC TUBING AS DEFINED IN THE N.E.C. MAYBE USED ABOVE CEILINGS AND
IN PARTITION WALLS. CHANGES FROM RIGID CONDUIT TO E.M.T. SHALL BE MADE AT A
JUNCTION BOX MINIMUM TRADE SIZE OF E.M.T. WHERE CONCEALED IN PARTITION WALLS OR
ABOVE PLASTERED CEILINGS OR OTHERWISE NOT ACCESSIBLE SHALL BE THREE HALF INCH
(1/2 ") ONLY COMPRESSION TYPE CONNECTORS OR COUPLINGS WILL BE USED.
21. TYPE MC CABLE MAY BE USED AS PER
CODE.
22. USE SEAL OFF'S FOR ALL PENETRATIONS OF COOLER.
23. ALL CIRCUITS SHALL HAVE GREEN BONDING GROUND PER CODE.
THE CIRCUITRY ON THESE PLANS ARE FOR THE SOLE PURPOSE OF BALANCING THE PANEL LOADS.
IT IS NOT INTENDED NOR EXPECTED OF THE ELECTRICIAN TO FOLLOW THIS SPECIFIC LAYOUT IN
THE PROCESS OF WIRING THIS PROJECT. IT IS HOWEVER, THE SOLE RESPONSIBILITY OF THE
ELECTRICAL CONTRACTOR OF RECORD, TO PROVIDE AND TO SUBMIT TO THE ARCHITECT AND
LANDLORD, A COMPLETE MARKED -UP SET OF 'AS- BUILT' PRINTS OF ANY CHANGES, MODIFICATIONS
OR DEVIATIONS FROM THIS PLAN IN ANY FORM.
THE CONDUIT FOR RECEPTACLES LOCATED AT THE COUNTER WILL BE RUN THROUGH THE
STUDS.
EXISTING LINE GUTTER
ONEW MTR. AND
DISC. FOR NEW
EQUIPMENT
225
225
s
1/0 GROUND
ELECTRICAL RISER DIA.
I �
(2) 5/8" DRIVEN
GROUND RODS
W/ rW RnNn
(4) 4/0 M IN 2
)�" CON.
William
hamilton
arthur
architect
Inc.
800 douglas entrance
suite 303
coral gables,
florida, 33134
(305)443 -3100
fax (3051441 -7960
license no. 2282
DRAWN BY:
U M. M., H.
1 i
�w c•
REVISION DATE(S)
A11.14.05
A
0
PROJ. NO:
DATE:
05 -25
04.23.05
W
NO.:
E-1
zry
Q
(.%)
�z
NW
L.L
0
Ld
O
w
w
0
U
Ld
Q
LJ_
--I
W
W
Q
W
L
U
�
�
O_
0
�oz
Z
Q
E2 ,
N
W
p
F-
W
NNZ
Of Of
Z 0 of
LL_I
0
w
U
z
-j
LLJ
V)
Q
w
V)
REVISION DATE(S)
A11.14.05
A
0
PROJ. NO:
DATE:
05 -25
04.23.05
z
NO.:
E-1
8OF13
U
NW
L.L
z
Q
w
0
U
Ld
Q
Xm
W
W
a
O_
in
<
Z
Q
E2 ,
N
W
p
F-
JU]
NNZ
Of Of
Z 0 of
U
LLI
N L� m
LLI
of
W
O -
00 Q
n
I.r)5LOU
REVISION DATE(S)
A11.14.05
A
0
PROJ. NO:
DATE:
05 -25
04.23.05
SHEET
NO.:
E-1
8OF13
ti "may.