07-638-093i �I r r System No. C -AJ -1226 F RATING = 3 -HR. T RATING = 0 -HR. L Rating At Ambient - Less than I CFM /Sq Ft L Rating At 400 F - 4 CFM /Sq Ft 1. Flog or Well Assembly — Min 4 -1/2 in. thick reinforced lightweight or normal weight (100 -150 pef) sonerete. Wall may also be constructed of any UL Classed Concrete Blocks *. Max diem of opening is 32 in. See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers. 2. Metallic Sleeve — (Optional) Nom 32 in. diam (or smaller) Schedule 40 (or heavier) steel sleeve cast or grouted into floor or wall assembly, flush with floor or wall surfaces. 3. Through Penetrant — One metallic pipe or conduit to be installed either concentrically or eccentrically within the frestop system. The annular space between pipe or conduit and periphery of opening shall be min 0 in. (point contact) to max 1 -7 /8 in. Pipe or conduit to be rigidly supporter on both sides of floor or wall assembly. The following types and sizes of metallic pipes or conduits may be user: A. Steel Pipe -- Nom 30 in. diem (or smaller) Schedule 10 (or heavier) steel pipe. f. Copper Pipe — Nom 6 in. dNm (or smaller) Regular (or heavier) copper pipe - C. Copper Tubing — Nom 6 in. diem (or smaller) Type L (or heavier) copper tubing. D. Conduit — Nom 6 in. diam (or smaller) steel conduit. E Conduit — Nom 4 in. diem (or smaller) steel electrical metallic tubing 4. Firestof System — The firestop system shall consist of the following: A. Packing Material — Min 4 in. thickness of min 4 pct mineral wool batt insulation firmly packer into opening as a permanent form. Packing material to be recessed from top surface of floor or from bath surfaces of wall as required to accommodate the required thickness of fib material. M. Fill, Void or Cavity Metered* — Sealant — Min 1/4 in. thickness of Al material applied within the annulus, flush with top surface of floor or with bath surfaces of wall. At the point contact location letween pipe and concrete, a min 1/4 in. diam bead of fill material shall be applied at the ooncrete /pipe interface on the top surface of floor end on both surfaces of wall. HILTI, Inc. — FS—ONE Sealant *fearing the UL Classification Marking Rert —1 My HILn, Inc. Courtesy of F1RESr0� SYSTEMS Underwriters talarstaries Inc. Revised 28, July 1819 C US ` &­'\ WF ZONE#5 EOL T"-1, v EOL ZONE ;4 77 N System Na, W -L -1054 F Rating - I and 2 Hr T Rating - 0 Hr L Rating At Ambient - Less Than I CFM /Sq Ft L Rating At 400 F - 4 CFM /Sq Ft SECTION A -A 1. Wall Assembly — The 1 or 2 hr fire —rated gypsum wallboard /stud wall assembly shall be constructed of the materials and in the manner specified in the individual 11300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following constriction features: A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min 2 -1/2 in, wide and spaced max 24 in. OC. When steel studs are used and the diem of opening exceeds the width of stud cavity, the opening shall be framed on all sides using lengths of steel stud installed between the vertical studs and screw — attached to the steel studs at each end. The framed opening in the well shall be 4 to S in. wider and 4 to 6 in. higher than the diem of the penetrating item such that, when the penetrating item is installed in the opening, a 2 to 3 in, clearance is present between the penetrating item and the framing on all four sides. f. Wallboard Gypsum* — 5/8 in. thick, 4 ft wide with square or tapered edges. The gypsum wallboard type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300 or 0400 Series Design in the UL Fire Resistance Directory. Max diom of opening is 32 -1/4 in. for steel stud walls. Max diem of opening is 14 -1/2 in. for wood stud walls. LO C] L;: ;Jo d` ��pssiF,�o Reproduced frr HIL11, Inc. Courtesy d ■ Unlen.dim tabiwwWries, Inc. C � US FlRESTOI* SYSTEMS Revisal 16. August 2000 hge: 1 of 2 System No. W -L -1054 F Rating - I and 2 Hr T Rating - 0 Hr L Rating At Ambient - Less Than 1 CFM /Sq .Ft L Rating At 400 F - 4 CFM /Sq Ft 2. Through -- Penetrants — One metallic pipe, conduit or tubing to be centered within the firestop system. An annular space of min 0 in. to max 2 -1/4 in. is required within firestop system. Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A. Steel ripe — Nom 30 in diem (or smaller) Schedule 10 (or heavier) steel pipe. f. Iron Pipe — Nom 30 in. diem (or smaller) cast or ductile iron pipe. C. Conduit — Nom 4 in diem (or smaller) steel electrical metallic tubing or 6 in. diem steel conduit. D. Copper Tubing — Nom 6 in. diem (or smaller) Type L (or heavier) copper tubing. E. Copper Pipe — Nom 6 in. diem (or smaller) regular (or heavier) copper pipe. 3. FIT, Void or Cavity Material* — Sealant — In 1 hr fire rated assemblies, min 5/8 im thickness of fill material applied within the annulus, flush with both surfaces of the wall. In 2 hr fire rated assemblies, min 1 -1/4 in. thickness of fill material applied within the annulus, flush with both surfaces of wall. HILTI, Inc. — FS —ONE Sealant *fearing the UL Clossi ication Marking �a�4�• Repduced by HILTI, Inc. Courtesy of FIRESTO� SYSTEMS Underwriters Labaratades, Inc. Revised 01, Oct 1999 FLOOR PLAN SCALE: 1/8" = 1 " -0" THIS IS A SPRINKLED 9UILDING Q J c�SSIF/�� C US 1,W2 . SCOPE OF WORK I PROVIDE, INSTALL, CONNECT & TEST FIRE ALARM EQUIPMENT INCLUDING CONTROL PANELS, VISUAL & AUDIBLE INDICATING APPLIANCES, MANUAL FIRE ALARM PULL STATIONS & SMOKE DETECTORS, 2 PR ❑VIDE DUCT - MOUNTED SMOKE DETECTORS & AHU SHUTDOWN RELAYS TO FIRE ALARM CONTROL PANEL, 3 PROVIDE & INSTALL ALL WIRE & CABLE NECESSARY FOR A COMPLETE FIRE ALARM SYSTEM, INCLUDING CONNECTION TO DEVICES PROVIDED BY OTHERS, a. SPRINKLER WATERFLOW SWITCH b, SPRINKLER VALUE TAMPER SWITCH, 4 PROVIDE & INSTALL, 42 DEVICES & I FIRE ALARM CONTROL PANEL USE PLENUM RATED CABLE WITH STUB -UPS r•• •rr u V U••UV VUV ••• U Y U - V w Y • VVVUV Y f V V u V U O ••• •i• r W v Vuuu V U u uuu FIRE—ALARM- 1. THIS IS A POWER LIMITED FIRE ALARM SYSTEM.'SLL OEM CPS YOR tJNIM8ft,LL BE INSTALLED USING APPROVED MATERIALS AND WIRING PRACTICES IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE #70 AND THE NATIONAL FIRE PROTECTION ASSOCIATION ARTICLE #760 POWER LIMITED SECTION AND ALL APPLICABLE LOCAi.Y*IRING'ORONAN_CES',, VVVY u r • w 2. CONDUCTORS AND CABLES FOR USE WITH TOS PbWER 6MITED'�FIRE, ALARM GH,�AcLL BE INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTF%ICAAL CbiYE V #760 POWER ` LIMITED JECTION AND SHALL BE LISTED FOR THIS USE. CONDUCTORS SHALL HAVE MINIMUM RATING OF 300V AND SHALL BE OF SOLID COPPER OR BUNCH — TINNED STRANDED COPPER CONDUCTORS. THESE CONDUCTORS OR CABLES SHALL BE FPLP OR FPLR IN ACCORDANCE WITH NEC ARTICLE 760 AND NEC ARTICLE 725 CLASS 2 OR 3 CIRCUITS. 3. CONDUCTORS OR CABLES USED IN DUCTS OR PLENUM TYPE CEILING FOR ENVIRONMENT AIR SHALL EMPLOY THE USE OF ELECTRICAL METAL TUBING OR PLENUM RATED INSULATED TYPE CABLE (FPLP). THE CABLE SHALL BE UL LISTED FOR SUCH USE AND MEET ALL THE REQUIREMENTS OF THE NATIONAL FIRE PROTECTION ASSOCIATION. 4. ALL INDICATING DEVICES SHALL BE MOUNTED AT 80" A.F.F. FROM THE FLOOR TO THE BOTTOM OF THE LENS UNLESS OTHERWISE NOTED, AND SHALL BE UL LISTED 1971 ADA 75 CANDELA MINIMUM. 5. ALL MANUAL — INITIATING DEVICES SHALL BE MOUNTED AT 48" TO CENTER A.F.F. UNLESS OTHERWISE NOTED. 6. CUSTOMER TO PROVIDE (2) PHONE LINES FOR CERTIFICATED CENTRAL STATION MONITORING WITH DIFFERENT LONG DISTANCE CARRIERS. 7. ELECTRICAL CONTRACTOR TO PROVIDE 110V DEDICATED CIRCUIT WITH 2OAMP CIRCUIT BREAKER, USING 12AWG THHN TYPE WIRE WITH 600V MINIMUM INSULATION. IN 1/2" MINIMUM CONDUIT. THE THE CIRCUIT BREAKER NUMBER AND PANEL SHALL BE NOTED AND MARKED IN ACCORDANCE TO NFPA 72, AND ANY LOCAL ORDINANCE. 8. ALL INITIATING AND INDICATING CIRCUITS SHALL BE STYLE Y (CLASS B) UNLESS OTHERWISE SPECIFIED. 9. DUCT DETECTOR SEQUENCE OF OPERATION UPON ALARM DUCT DETECTOR SHALL ACTIVATE ANY TROUBLE CONDITION WILL BE ANNUNCIATED AT THE MAIN PANEL, AND ANNUNCIATOR, ALSO SHUTDOWN A/C UNIT 10. ANY DUCT DETECTOR ALARM SHALL CAUSE THE AIR HANDLERS TO SHUT DOWN. 11. THIS SYSTEM WILL BE CERTIFICATED AS A CENTRAL STATION SERVICE FIRE ALARM SYSTEM. 12. ALLOWABLE AMPACITY ACCORDING TO CONDUCTOR SIZE. SIZE(AWG) ALLOWABLE AMPACITY 18 6 16 8 14 17 12 23 10 28 13. MAXIMUM NUMBER OF CONDUCTORS IN ELECTRICAL METAL TUBING. TYPE CONDUCTOR TRADE --SIZES IN INCHES LETTER SIZE (AWG) 1/2" 3/4" 1" 1- �-1/4" 1 -1/2" 2" 2 -1/2" TEN, TFFN 18AWG 22 3a 63 108 148 244 TFN, TFFN 16AWG 17 29 48 83 113 186 THHN 14AWG 12 22 35 61 84 138 241 THWN 12AWG 09 16 26 45 61 101 176 THWN -2 10AWG 05 10 16 28 38 63 111 WIRE LEGEND CHART TYPE CONDUCTORSfDESCRIPTION MARKINGS A 2 COND 18 AWG SOLID ADT493490 2C /18AWG TYPE FPLP /CMP(UL) B 4 COND 18 AWG SOLID ADT494449 4C /18AWG TYPE FPLP /CMP(UL) C 2 COND 14 AWG SOLID ADT493491 2C /14AWG TYPE FPLP /CMP(UL) D 2 COND 18 AWG SOLID SHLD 860830A 2C /18AWG TYPE FPLP /CMP(UL) E 4 COND 18 AWG SOLID SHLD 860836 4C /18AWG TYPE FPLP /CMP(UL) F 4 COND 22 AWG SOLID ADT494468 4C /22AWG TYPE FPLP /CMP(UL) G 12 COND 22 AWG SOLID ADT494469 12C /22AWG TYPE FPLP /CMP(UL) H 2 COND 18 AWG SOLID BLACK BURIAL 180010 2C /18AWG TYPE FPLP /1RR(UL) 14. ALL EQUIPMENT COMPATIBLE AND UL LISTED FOR FIRE SERVICE. 1/2" MIN EMC FOR STUBS 40% FILL FOR ALL CONDUIT. 15. THE DESIGN INSTALLATION COMPLIES WITH FBC 11- 4.28.3 SEQUENCE OF OPERATION ANY INITIATING DEVICE ACTIVATED SHALL CAUSE THE FIRE ALARM PANEL TO GO INTO ALARM CONDITION, ON INIIATING DEVICE SUPERVISORY SIGNAL SHALL CAUSE THE FIRE ALARM PANEL TO SHOW A SUPERVISORY CONDITION, ALSO ON ANY TROUBLE CONDITION, BOTH THESE SIGNALS WILL DISPLAY THE DEVICE OR ZONE ON THE FRONT PANEL. AS WELL AS ANY REMOTE ANNUNCIATORS CONNECTED TO SYSTEM. ACTIVATI INDICATING DEVICES, TRANSMIT SIGNAL TO OFFSITE LISTED CENTRAL STATION AND ACTIVATE OR OPERATE OPERATE ANY AUX. RELAYS OR FUNCTONS AS NOTED ON FLOOR PLAN. SEE SEQUENCE OF OPERATION MATRIX AS SHOWN ON PLANS. nw»� a CONTRACTOR SHALL COORDINATE ALL MOUNTING HEIGHTS AND FINAL LOCATIONS OF DEVICES WITH A REPRESENTATIVE (PRIOR TO ROUGH —IN). SYMBOL SW 40 S1FEEf MAMI, FLORDA , �y OWS �1 U H_ECinCAL LTC. 53M5*S TEL, 305 5510724 FIRE ALARM CABINET — INSTALLED 5-0" AFF UNIMODE 10 ADT A REMOTE POWER SUPPLY — CIRCUIT EXPANDER r•• •rr u V U••UV VUV ••• U Y U - V w Y • VVVUV Y f V V u V U O ••• •i• r W v Vuuu V U u uuu FIRE—ALARM- 1. THIS IS A POWER LIMITED FIRE ALARM SYSTEM.'SLL OEM CPS YOR tJNIM8ft,LL BE INSTALLED USING APPROVED MATERIALS AND WIRING PRACTICES IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE #70 AND THE NATIONAL FIRE PROTECTION ASSOCIATION ARTICLE #760 POWER LIMITED SECTION AND ALL APPLICABLE LOCAi.Y*IRING'ORONAN_CES',, VVVY u r • w 2. CONDUCTORS AND CABLES FOR USE WITH TOS PbWER 6MITED'�FIRE, ALARM GH,�AcLL BE INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTF%ICAAL CbiYE V #760 POWER ` LIMITED JECTION AND SHALL BE LISTED FOR THIS USE. CONDUCTORS SHALL HAVE MINIMUM RATING OF 300V AND SHALL BE OF SOLID COPPER OR BUNCH — TINNED STRANDED COPPER CONDUCTORS. THESE CONDUCTORS OR CABLES SHALL BE FPLP OR FPLR IN ACCORDANCE WITH NEC ARTICLE 760 AND NEC ARTICLE 725 CLASS 2 OR 3 CIRCUITS. 3. CONDUCTORS OR CABLES USED IN DUCTS OR PLENUM TYPE CEILING FOR ENVIRONMENT AIR SHALL EMPLOY THE USE OF ELECTRICAL METAL TUBING OR PLENUM RATED INSULATED TYPE CABLE (FPLP). THE CABLE SHALL BE UL LISTED FOR SUCH USE AND MEET ALL THE REQUIREMENTS OF THE NATIONAL FIRE PROTECTION ASSOCIATION. 4. ALL INDICATING DEVICES SHALL BE MOUNTED AT 80" A.F.F. FROM THE FLOOR TO THE BOTTOM OF THE LENS UNLESS OTHERWISE NOTED, AND SHALL BE UL LISTED 1971 ADA 75 CANDELA MINIMUM. 5. ALL MANUAL — INITIATING DEVICES SHALL BE MOUNTED AT 48" TO CENTER A.F.F. UNLESS OTHERWISE NOTED. 6. CUSTOMER TO PROVIDE (2) PHONE LINES FOR CERTIFICATED CENTRAL STATION MONITORING WITH DIFFERENT LONG DISTANCE CARRIERS. 7. ELECTRICAL CONTRACTOR TO PROVIDE 110V DEDICATED CIRCUIT WITH 2OAMP CIRCUIT BREAKER, USING 12AWG THHN TYPE WIRE WITH 600V MINIMUM INSULATION. IN 1/2" MINIMUM CONDUIT. THE THE CIRCUIT BREAKER NUMBER AND PANEL SHALL BE NOTED AND MARKED IN ACCORDANCE TO NFPA 72, AND ANY LOCAL ORDINANCE. 8. ALL INITIATING AND INDICATING CIRCUITS SHALL BE STYLE Y (CLASS B) UNLESS OTHERWISE SPECIFIED. 9. DUCT DETECTOR SEQUENCE OF OPERATION UPON ALARM DUCT DETECTOR SHALL ACTIVATE ANY TROUBLE CONDITION WILL BE ANNUNCIATED AT THE MAIN PANEL, AND ANNUNCIATOR, ALSO SHUTDOWN A/C UNIT 10. ANY DUCT DETECTOR ALARM SHALL CAUSE THE AIR HANDLERS TO SHUT DOWN. 11. THIS SYSTEM WILL BE CERTIFICATED AS A CENTRAL STATION SERVICE FIRE ALARM SYSTEM. 12. ALLOWABLE AMPACITY ACCORDING TO CONDUCTOR SIZE. SIZE(AWG) ALLOWABLE AMPACITY 18 6 16 8 14 17 12 23 10 28 13. MAXIMUM NUMBER OF CONDUCTORS IN ELECTRICAL METAL TUBING. TYPE CONDUCTOR TRADE --SIZES IN INCHES LETTER SIZE (AWG) 1/2" 3/4" 1" 1- �-1/4" 1 -1/2" 2" 2 -1/2" TEN, TFFN 18AWG 22 3a 63 108 148 244 TFN, TFFN 16AWG 17 29 48 83 113 186 THHN 14AWG 12 22 35 61 84 138 241 THWN 12AWG 09 16 26 45 61 101 176 THWN -2 10AWG 05 10 16 28 38 63 111 WIRE LEGEND CHART TYPE CONDUCTORSfDESCRIPTION MARKINGS A 2 COND 18 AWG SOLID ADT493490 2C /18AWG TYPE FPLP /CMP(UL) B 4 COND 18 AWG SOLID ADT494449 4C /18AWG TYPE FPLP /CMP(UL) C 2 COND 14 AWG SOLID ADT493491 2C /14AWG TYPE FPLP /CMP(UL) D 2 COND 18 AWG SOLID SHLD 860830A 2C /18AWG TYPE FPLP /CMP(UL) E 4 COND 18 AWG SOLID SHLD 860836 4C /18AWG TYPE FPLP /CMP(UL) F 4 COND 22 AWG SOLID ADT494468 4C /22AWG TYPE FPLP /CMP(UL) G 12 COND 22 AWG SOLID ADT494469 12C /22AWG TYPE FPLP /CMP(UL) H 2 COND 18 AWG SOLID BLACK BURIAL 180010 2C /18AWG TYPE FPLP /1RR(UL) 14. ALL EQUIPMENT COMPATIBLE AND UL LISTED FOR FIRE SERVICE. 1/2" MIN EMC FOR STUBS 40% FILL FOR ALL CONDUIT. 15. THE DESIGN INSTALLATION COMPLIES WITH FBC 11- 4.28.3 SEQUENCE OF OPERATION ANY INITIATING DEVICE ACTIVATED SHALL CAUSE THE FIRE ALARM PANEL TO GO INTO ALARM CONDITION, ON INIIATING DEVICE SUPERVISORY SIGNAL SHALL CAUSE THE FIRE ALARM PANEL TO SHOW A SUPERVISORY CONDITION, ALSO ON ANY TROUBLE CONDITION, BOTH THESE SIGNALS WILL DISPLAY THE DEVICE OR ZONE ON THE FRONT PANEL. AS WELL AS ANY REMOTE ANNUNCIATORS CONNECTED TO SYSTEM. ACTIVATI INDICATING DEVICES, TRANSMIT SIGNAL TO OFFSITE LISTED CENTRAL STATION AND ACTIVATE OR OPERATE OPERATE ANY AUX. RELAYS OR FUNCTONS AS NOTED ON FLOOR PLAN. SEE SEQUENCE OF OPERATION MATRIX AS SHOWN ON PLANS. REVISIONS +,. SECURITY SERVICES, INC. . 7747 NW 48 ST SUITE #160 MIAMI FLORIDA 33166 NO.: DATES: BY; (786) 331 -3940 FAX (786) 331 -3952 ISRAEL GARCIA EF 0001194 1 2 CARRABBA'S ITALIAN GRILL 3 5829 SW 73 STREET SUITE 102 4 SOUTH MIAMI, FLORIDA 33143 5 DESIGNED MY: DWG DY: ADT FIRE ALARM PLAN R.0 6 DATE: SCALE: SHEET NO.: DWG. NO.: 7 6/13/07 1/81" = 1 "--Q" 1 OF 2 00341 FIRE ALARM LEGEND CONTRACTOR SHALL COORDINATE ALL MOUNTING HEIGHTS AND FINAL LOCATIONS OF DEVICES WITH A REPRESENTATIVE (PRIOR TO ROUGH —IN). SYMBOL DESCRIPTION PART # CATALOG # MANUFACTURER — FIRE ALARM CABINET — INSTALLED 5-0" AFF UNIMODE 10 ADT REMOTE POWER SUPPLY — CIRCUIT EXPANDER FCPS -24FS8 ADT FIRE ALARM MANUAL PULL STATION ADT— BG -12L ADT WEATHERPROOF FIRE ALARM MANUAL PULL STATION - BG- 1 2L0It (`tM_t- L_% r E 75 CEILING HORN— STROBE — "RED" CANDELLA _75 _ PC2R SYSTEM SENSOR 75 WEATHERPROOF HORN— STROBE— "RED" CANDELLA P2RK SYSTEM SENSOR 75 FIRE ALARM STROBE — "RED" CANDELLA 75 SR SYSTEM SENSOR RC CEILING STROBE -- "RED" CANDELLA _ 75 SCR SYSTEM SENSOR 75 WP WEATHERPROOF STROBE — "RED" CANDELLA _75 SCRK SYSTEM SENSOR CR CONTROL RELAY MR -101 /C ADT OD DUCT SMOKE DETECTOR P.O.C. BY OTHERS OP PHOTO ELECTRIC SMOKE DETECTOR 2151 ADT Q ANSUL SYSTEM P.O.C. BY OTHERS FSA LED ANNUNCIATOR LED -10 ADT CR REMOTE TEST SWITCH RTS -451 SYSTEM SENSOR REVISIONS +,. SECURITY SERVICES, INC. . 7747 NW 48 ST SUITE #160 MIAMI FLORIDA 33166 NO.: DATES: BY; (786) 331 -3940 FAX (786) 331 -3952 ISRAEL GARCIA EF 0001194 1 2 CARRABBA'S ITALIAN GRILL 3 5829 SW 73 STREET SUITE 102 4 SOUTH MIAMI, FLORIDA 33143 5 DESIGNED MY: DWG DY: ADT FIRE ALARM PLAN R.0 6 DATE: SCALE: SHEET NO.: DWG. NO.: 7 6/13/07 1/81" = 1 "--Q" 1 OF 2 00341