07-638-0751. MATERIALS AND INSTALLATION, AS A MINIMUM, ARE TO CONFORM WITH THE LATEST EDITION
24. THE ELECTRICAL CONTRACTOR SHALL MEET AND COORDINATE WITH THE LOCAL POWER COMPANY
OF THE NATIONAL ELECTRIC CODE, THE LATEST EDITION OF N.F.P.A., AND THE LATEST EDITIONS
AT THE SITE PRIOR TO CONSTRUCTION. AT THAT TIME, THE CONTRACTOR SHALL COORDINATE
OF THE LOCAL CODES AND ORDINANCES, INCLUDING ALL AMENDMENTS TO THE N.E.C. EQUIPMENT,
ALL RELATED WORK WITH THE UTILITY COMPANY'S RESPONSIBILITIES TO MEET THE OWNER'S
WHERE APPLICABLE, WILL BE LISTED WITH THE UNDERWRITERS LABORATORIES, INC. QUALITY AND
SCHEDULE.
WORKMANSHIP ESTABLISHED BY DRAWINGS AND SPECIFICATIONS ARE NOT TO BE REDUCED BY THE
V t3
ABOVE MENTIONED CODES.
25. ALL ELECTRICAL CONDUCTORS SHALL BE INSTALLED IN AN APPROVED RACEWAY. MAXIMUM
V
NUMBER OF 120 VOLT CIRCUITS ALLOWED IN A COMMON CONDUIT SHALL BE SIX (6). THE
2. BIDDERS ARE TO VISIT THE SITE AND FAMILIARIZE THEMSELVES WITH EXISTING CONDITIONS AND
CONTRACTOR SHALL STRICTLY CONFORM TO THE N.E.C. REQUIREMENTS OF DERATING FOR
SATISFY THEMSELVES AS TO THE NATURE AND SCOPE OF WORK. THE SUBMISSION OF A BID WILL
CONDUCTOR AMPACITY AND CONDUIT FILL
BE EVIDENCE THAT SUCH AN EXAMINATION HAS BEEN MADE. LATER CLAIMS FOR LABOR, EQUIPMENT,
G
OR MATERIALS REQUIRED, OR FOR DIFFICULTIES ENCOUNTERED WHICH COULD HAVE BEEN FORESEEN
25.1. CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS:
HAD AN EXAMINATION BEEN MADE, WILL NOT BE ALLOWED.
20 2V SYSTEM PHASE SEQUENCE
VVVV
NEUTRAL - WHITE ABC, TOP TO BOTTOM
3. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST -CLASS
PHASE A - BLACK LEFT TO RIGHT, FRONT
WORKMANLIKE MANNER. THE COMPLETED SYSTEM IS TO BE FULLY OPERABLE AND ACCEPTANCE OF
PHASE B - RED TO BACK
THIS SYSTEM BY THE ENGINEER /ARCHITECT MUST BE A CONDITION OF THE SUM CONTRACT.
PHASE C - BLUE
VuUV
GRD.CON -• GREEN
4. ALL WORK TO BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH THE
• i V V
PROGRESS OF CONSTRUCTION.
26. CONTRACTOR SHALL BE RESPONSIBLE FOR SEALING ALL CONDUIT PENETRATIONS MADE THROUGH
V v V
FIRE RATED WALLS, CEILINGS, SLABS, ETC. PENETRATION SEALS SHALL BE PER U.L ASSEMBLY
5. CONTRACTOR TO GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS FOR PERIOD
STANDARDS.
OF NOT LESS THAN ONE (1) YEAR FROM DATE OF ACCEPTANCE.
i
27. CONTRACTOR SHALL MAINTAIN A COMPLETE SET OF CONTRACT DRAWINGS AT JOB SITE WITH
S. CORRECTION OF ANY DEFECTS TO BE COMPLETED WITHOUT ADDITIONAL CHARGE AND TO INCLUDE
COLORED MARKINGS INDICATING PROGRESS OF WORK. THIS SET OF CONTRACT DRAWINGS IS TO
REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN
BE SEPARATE FROM AND IN ADDITION TO CONTRACTOR'S CONSTRUCTION SET. EVERY UNIT OF
DAMAGED THEREBY.
EQUIPMENT, DEVICE, CONDUIT AND WIRE IS TO MARKED WHEN INSTALLED. USE GREEN TO
INDICATE INSTALLATION AS SHOWN ON DRAWINGS AND USE RM TO INDICATE FIELD CHANGES.
7. ALL REQUIRED INSURANCE TO BE PROVIDED FOR PROTECTION AGAINST PUBLIC LIABILITY OF
UPON COMPLETION OF WORK, THIS SET OF CONTRACT DRAWINGS IS TO BE TURNED OVER TO,
PROPERTY DAMAGE FOR THE DURATION OF THE WORK.
AND BECOME PROPERTY OF THE ARCHITECT.
I. CONTRACTOR TO PAY FOR ALL PERMITS, FEES INSPECTIONS AND TESTINGS.
28. THE OWNER RESERVES THE RIGHT TO REVISE THE DRAWING FROM TIME TO TIME TO INDICATE
S. ELECTRICAL INSTALLATION TO MEET ALL STANDARD REQUIREMENTS OF LOCAL POWER AND
CHANGES IN THE WORK. WHEN REVISED DRAWING ARE ISSUED, THE CONTRACTOR SHALL
EVALUATE THE CHANGES PROMPTLY. BEFORE INSTALLATION OF ANY ITEM OR PERFORMANCE OF
TELEPHONE COMPANIES. ELECTRICAL CONTRACTOR SHALL CONTACT LOCAL POWER AND
THE WORK INDICATED BY THE REVISED DRAWINGS, THE CONTRACTOR SHALL NOTIFY THE OWNER
TELEPHONE COMPANIES PRIOR TO START OF CONSTRUCTION.
IN WRITING THAT THE REVISED DRAWINGS INVOLVE AN ADDITION OR DEDUCTION OF A SPECIFIC
10. ALL WIRING SHALL BE IN CONDUIT UNLESS OTHERWISE NOTED, MINIMUM WIRE SIZE SHALL
AMOUNT OF MONEY TO THE CONTRACT PRICE THE CONTRACTOR SHALL NOT PROCEED WITH THE
BE #12 AWG, EXCLUDING CONTROL WIRING. ALL CONDUCTORS SHALL BE COPPER WITH
REVISED WORK WITHOUT PRIOR WRITTEN APPROVAL BY THE OWNER OF THE COST OF THE REVISED
THWN /THHN INSULATION. CONDUCTORS #10 AND SMALLER MAY BE SOLID; ALL THOSE #i
WORK.
AND LARGER TO BE STRANDED.
29. IF ELECTRICAL CONTRACTOR HAS QUESTIONS, OR IN THEIR OPINION FINDS OMISSIONS OR
11. ALL UNDERGROUND RACEWAYS SHALL BE MINIMUM 314 ", GALVANIZED RIGID STEEL CONDUIT OR
ERRORS ON ELECTRICAL DOCUMENTS, IT IS THERE RESPONSIBILITY TO BRING THIS TO THE
SCHEDULE 40 PVC. ALL OTHER RACEWAYS TO COMPLY WITH GOVERNING CODES. WHERE RIGID STEEL
ATTENTION OF THE ELECTRICAL ENGINEER /ARCHITECT /OWNER IMMEDIATELY.
IS USED, IT SHALL BE COMPLETELY COATED WITH AN ALKALI AND RUST RESISTANT BITUMASTIC
PAINT, KOPPER NO. 50, AND THREADS SHALL BE COATED WITH ZINC CHROMATE. RIGID STEEL
30. ELECTRICAL CONTRACTOR SHALL PROVIDE SEPARATE DEDUCT PRICE FOR BRANCH CIRCUITS IN
SHALL ALSO BE USED WHEN CONDUIT IS EXPOSED TO EXTERIOR ENVIRONMENT SUCH AS EXTERIOR
'AC' AND 'MC' TYPE WIRING, ONLY WHEN ALLOWED BY LOCAL CODE AND AUTHORITY HAVING
OF BUILDING OR WHERE IT IS EXPOSED AND SUBJECT TO DAMAGE, INSIDE OF BUILDING.
JURISDICTION. THE BASE BID WILL ONLY REFLECT CONDUIT AND WIRE AS_SPECIFIED.
11.1 ALL UNDERGROUND SERVICE CONDSI,IUZRACF•WAYS ENTERING BUILDING OR STRUCTURE FROM
V
OUTSIDE TO INSIDE SHALL BE SEALED, INCLUDING SPARE CONDUIT'S. SEALANT SHALL BE SUITABLE
W*.i
FOR THIS USE.
WWU
12. OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS, CAST ALLOY WITH THREADED HUBS
uWW� o
IN WET OR DAMP LOCATIONS, AND BE OF SPECIAL CONSTRUCTION FOR OTHER CLASSIFIED AREAS.
ALL BOXES SHALL BE RECESSED (FLUSH) IN WALLS OR CEILINGS WHENEVER POSSIBLE.
13. DISCONNECT SWITCHES SHALL BE H.P. RATED, GENERAL DUTY, QUICK -MAKE, QUICK -BREAK TYPE.
ENCLOSURES SHALL BE AS REQUIRED BY N.E.C. AND LOCATION (WEATHERPROOF, EXPLOSION
PROOF, ETC.). ENGRAVED LAMINATED PLASTIC IDENTIFICATION PLATES SHALL BE FURNISHED AND
INSTALLED ON ALL DISCONNECT SWITCHES, CONTACTORS AND STARTERS.
111. ALL FUSES FOR SAFETY SWITCHES SHALL BE DUAL ELEMENT, CARTRIDGE TYPE. FUSES SHALL BE
THOSE MANUFACTURED BY EITHER BUSSMAN OR LITTLEFUSE. THE CONTRACTOR SHALL FURNISH
TO THE OWNER ONE SPARE FUSE FOR EACH SIZE AND TYPE OF FUSE INSTALLED. FUSES 600 AMPS
OR LESS SHALL BE CLASS RK1, TYPICAL UNLESS OTHERWISE NOTED. FUSES OVER 600 AMPS SHALL
BE CLASS L
14. ALL GENERAL PURPOSE SWITCHES AND RECEPTACLES SHALL BE THE PRODUCT OF A SINGLE
MANUFACTURER. CATALOG NUMBERS LISTED ARE LEVITON: HOWEVER, COMPARABLE DEVICES BY
PASS k SEYMOUR, BRYANT, OR ARROW HART WILL BE ACCEPTED. COLOR OF DEVICES AND
PLATES SHALL BE DICTATED BY ARCHITECT /OWNER.
SWITCHES: SINGLE POLE - LEVITON #5521 -I* / THREE WAY - LEVITON #'5523 -I*
RECEPTACLES: DUPLEX OUTLET - LEVITON #5896 -SI*
COVER PLATES: SATIN FINISH STAINLESS STEEL - KITCHEN AREA, DARK BROWN- DINING AREA.
* IVORY-KITCHEN /DARK BROWN - DINING AREA TELEPHONE OUTLET, PROVIDE WITH PULL STUB-UP 1/2' TR STRING N WALL UP NOTE: ALL L OTHER REQUIRED DEVICES SHALL MATCH IN COLOR AND STYLE.
I -G BOX WITH RJ -11 PLATE. INTO CEILING SPACE. TERMINATE
15. ALL RACEWAYS AND PIPES, SPACED IN OR THROUGH ANY CONCRETE SLAB, SHALL BE SPACED A (TYPICAL) WITH INSULATING BUSHING.
MINIMUM OF THREE TIMES THE DIAMETER OF THE LARGEST RACEWAY. (TYPICAL)
16. IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. THE J
CONTRACTOR IS EXPECTED TO FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL % 4" SQ. x 2 1/8" JUNCTION
SYSTEM, AND PROVIDE ALL NECESSARY DEVICES AND COMPONENTS FOR EQUIPMENT BE PLACED IN TELEPHONE AT 40" A.F.F. J BOX WITH 2 GANG PLASTER
PROPER WORKING ORDER. RING. (TYPICAL)
QUAD. OUTLET AT ti" A.F.F.��
17. A SEPARATE, GREEN ME THW COPPER GROUND CONDUCTOR SHALL BE RUN FROM GROUND LUG OF
EACH GROUNDED RECEPTACLE TO AN APPROVED CONNECTION INSIDE THE ENCLOSING STEEL OUTLET
BOX. DEVICE MOUNTING SCREWS SHALL NOT BE CONSIDERED AN APPROVED GROUND. AUDIO SYSTEM. AT CASH REGISTER
A SEPARATE GROUND CONDUCTOR SHALL BE INSTALLED IN EVERY CONDUIT AND RACEWAY AND NOT TO SCALE
SECURELY BONDED IN AN APPROVED GROUNDING TERMINAL AT BOTH ENDS OF THE RUN. THE NOTE:
GROUNDING CONDUCTOR SHALL BE SIZED IN ACCORDANCE WITH TABLE 250 -95 OF THE N.E.C. 1. THE OWNER'S AUDIO SYSTEM VENDOR IS TO PROVIDE WIRING COMPONENTS AND
CONTRACTOR SHALL SIZE CONDUIT TO ACCOMMODATE ADDITIONAL CONDUCTOR. CONNECTIONS FOR AUDIO EQUIPMENT AND SPEAKERS (TYPICAL)
18. LOAD DATA IS BASED ON INFORMATION GIVEN ENGINEER AT THE TIME OF DESIGN. VERIFY ALL 2. SEE ARCHITECTURAL DETAIL FOR ADDITIONAL INFORMATION.
EQUIPMENT NAMEPLATE RATINGS BEFORE ORDERING.
IS. CIRCUITS SHOWN ON PLANS ARE TO DETERMINE LOAD DATA AND PANEL SIZES. THE CONTRACTOR
IS TO PROVIDE CIRCUITS AND ROUTING OF CONDUITS TO SUIT JOB CONDITIONS.
20. FURNISH AND INSTALL DISCONNECT SWITCHES, WIRING, AND CONNECTIONS ON AIR CONDITIONING
SYSTEM AS SHOWN ON PLANS. ELECTRICAL CONTRACTOR SHALL VERIFY AND COORDINATE WITH
MECHANICAL CONTRACTOR REGARDING SUPPLY AND INSTALLATION OF ALL REQUIRED CONTROLS.
21. ALL FLUORESCENT AND H.I.D. LIGHTING FIXTURES SHALL BE FUSED, AS REQUIRED BY LOCAL
CODE ONLY.
22. ALL SWITCHGEAR, PANELS, STARTERS, CONTACTORS ETC., SHALL DE THE PRODUCT OF A SINGLE
MANUFACTURER, THE SYSTEM DESIGN IS BASED ON SIEMENS; HOWEVER, COMPARABLE EQUIPMENT
BY G.E., SQUARE D, AND CUTLER HAMMER ONLY WILL BE ACCEPTABLE. TANDEM AND HALF -SPACE
CIRCUIT BREAKERS SHALL NOT BE USED.
22.1. TYPEWRITTEN CIRCUIT INDEX SHALL BE AFFIXED TO INSIDE SURFACE OF EACH PANELBOARD
DOOR, CLEARLY INDICATING AREA AND TYPE OF LOAD SERVED BY EACH BRANCH CIRCUIT
PROTECTIVE DEVICE, INCLUDING SPARES. HAND PRINTED WILL NOT DE ACCEPTED.
22.2. ENGRAVED, LAMINATED PLASTIC IDENTIFICATION PLATES SHALL BE FURNISHED AND INSTALLED
ON ALL PANELS AND SWITCHGEAR. PLATES SHALL BE AFFIXED TO FRONT OF PANELS.
23. ALL UNDERGROUND PVC CONDUIT RUNS SHALL HAVE RIGID STEEL ELBOWS AND RIGID STEEL
SECTIONS AT SLAB PENETRATIONS WHERE SUBJECT TO POSSIBLE DAMAGE. WHERE RIGID STEEL
IS USED, IT SHALL BE COMPLETELY COATED WITH AN ALKALI AND RUST - RESISTANT BITUMASTIC
PAINT, KOPPER NO. 50, AND THREADS SHALL BE COATED WITH ZINC CHROMATE.
FRAME WALL SCHEDULE 40 STEEL
PIPE SLEEVE
LOOSE CERAMIC
FIBER PACKING
tY
3M CAULK
JUL LISTED
#CP25 WB
CONDUIT
(EXCEEDS (EXCEEDS U.L. SYSTEM NO. CAJ1003, CAJ1011, WL2002.)
WALL AND FLOOR FIRESTOP SYSTEM
NOT TO SCALE
DRY TYPE TRANSFORMER
r -- - -- --- - - - - --
L1
� I
L1 I L2
I
I
480V. i N 120/208V.
L2 I
I
I
L3 I L3
G I
TERMINAL I G
I) GROUND BAR
L- - - - - - - - - - - - -J
BONDING JUMPER TO
TRANSFORMER ENCLOSURE.
BUILDING STEEL GROUNDING CONDUCTOR
480 VOLTA TO 208/120 VOLT Y
DRY TYPE TRANSFORMER GROUND -M DETAL
NO SCALE
�4' -0" O.C.
EXISTING
CONCRETE
JOISTS
1/2" 0 ROD DRY TYPE
TRANSFORMER
NEOPRENE PAD -
UNISTRUT
EQ. EQ.
TRANSFORMER MOUNTING DETAL
NO SCALE
WWWW
k'^
South Miami,
FL`,'.•'
VVU V
VuuWV
WVV
V t3
U V V
V W
V
i
G
W
C
V
VVUUV
VVVV
Project Number
06165
uVi
i V
W
VuUV
u V V
V
• i V V
V
W
V v V
Y i
G i
i
G • V
V V
V V
V
W
V
Vi
W
V
V
4, CVV
GG
V
V
1
*YM4
iiiV•
two
WiVU
a
V
V
V V
Vi00
i
V
W
V V
•
W
V
,.
W*.i
s 91Vm W
WWU
W
uWW� o
TRANSFORMER- DELIVERY
PUSH BUTTON
L._....,._.-- - - - - --I
H I I •
I I
I I
120 VAC I I #VAC B BELL IN
KITCHEN
I I
I I
I I
N
I I
I----- - - - - -J
DELIVERY DOOR
ANNUNCIATOR WIRING DIAGRAM'!
NOT TO SCALE
NOTE:
DELIVERY DOOR ANNUNCIATOR SYSTEM SHALL CONSIST OF A WEATHERPROOF
PUSH BUTTON INUAL FR AT THE EXTERIOR GATE OF TRASH_ ENCLOSURE, AN
ADJUSTABLE VOLUME BELL RATED AT 82 4b AT 3 FEET, AN i VOLT, A/C
TRANSFORMER WITH 10 VA MINIMUM CAPACITY AND 120 VOLT PRIMARY AND
WIRED AS SHOWN ABOVE. EQUIPMENT SHALL BE EDWARDS CAT. #156G -4AM IV
AC BELL; EDWARDS CAT. #852 FLUSH MOUNTED WEATHERPROOF PUSH BUTTON;
EDWARDS CAT. #5 92 TRANSFORMER; OR APPROVED EQUAL.
TRANSFORMER FRONT DOOR
r PUSH BUTTON
H I I •
I I
I I
I I
120 VAC I I i VAC cts BELL AT
AREA OFFICE
I I
I I
I I
N
I I
� ----- - - - - - J
FRONT DOOR ANNUNCIATOR
NOT M.
WIRING DIAGRA
NOTE:
FRONT DOOR ANNUNCIATOR SYSTEM SHALL CONSIST OF A WEATHERPROOF
PUSH BUTTON INSTALLED AT FRONT ENTRANCE DOOR, AN ADJUSTABLE VOLUME
BELL RATED AT 82 db AT 3 FEET, AN i VOLT, A/C TRANSFORMER WITH 10 VA
MINIMUM CAPACITY AND 120 VOLT PRIMARY AND WIRED AS SHOWN ABOVE.
EQUIPMENT SHALL BE EDWARDS #55 -6AM IV AC DELL; EDWARDS #852 FLUSH
MOUNTED WEATHERPROOF PUSH BUTTON; EDWARDS CAT. #596 TRANSFORMER
OR APPROVED EQUAL.
�-- THROUGH CONTACT IN DISHWASHER
•. " 'TFY WITH
20 AMP, 1 POLE
Y FUNCTION.
i MINUTES
TURNED OFF.
'00" STARTER, VERIFY COIL
TH DISHWASHER.
EXHAUST FAN
(DWEF -1)
�--► B -1
DISHWASHER EXHAUST FAN
WIRING DIAGRAM
NOT TO SCALE
NOTE:
VERIFY CONNECTION WITH MANUFACTURER PRIOR TO ROUGH -IN.
Harold Hart do Associates, Inc.
CONSULTING ENGINE=ERS
4201 West Gray Street : Time, Fferiali 33609
Telephone: (913) 287 -2719 Fix: (813) 287 -5704
E9 #0004221 : PE #17296
Seal
Mark S. Egg
ARCHITECT
211 F*t B!rv4W ftim Gr"nvft, $0 2B#01
T.064MMI200 F. 864"L7587
Project
�G ir�eue�� Ate'
1Q LIFE SAFETY COMMENTS 5/23/07
AND OWNER CHANGES
Drawing
ELECTRICAL DETAILS,
DIAGRAMS AND
SPECIFICATIONS
E -6
k'^
South Miami,
FL`,'.•'
Y
••
•
�, •I1,r�• . • . r ,
Project Number
06165
Drawn By
Checked By
Date
23 Mar 07
/
1Q LIFE SAFETY COMMENTS 5/23/07
AND OWNER CHANGES
Drawing
ELECTRICAL DETAILS,
DIAGRAMS AND
SPECIFICATIONS
E -6