05-66-016I
ONE LAYER OF 5/8" TYPE 'X' GYPSUM
WALLBOARD ON EACH SIDE OF 3 -5/8"
METAL STUDS, ,o 24" O.C.
I HR FIRE RATED CONSTRUCTION
TEST "WP -1200 (AS PER FIRE RESISTANCE
DESIGN MANUAL)
PLASTIC PIPE - NOM. 6" DIAM. ( OR
SMALLER) SCH. 40 PVC PIPE FOR USE
IN OPEN OR CLOSED PIPING SYSTEMS.
THE ANNULAR SPACE SHALL BE 0" MIN.
TO MAX. 3/8"
TREMSTOP WBM —/-�
TREMSTOP WS - TWO STACKS OF
INTUSCEMENT WRAP STRIPS,
CONTINUOUSLY WRAPPED AROUND THE
OUTER CIRCUMFERENCE OF THE PIPE,
EIGHT TIMES ON BOTH SIDES OF THE
WALL
TREMSTOP WBM - MIN. 1/4" THICKNESS OF
SEALANT APPLIED AT THE INTEFZFACE
OF THE WALL AND COLLAR, AND THE
INTERFACE OF THE COLLAR AND PIPE.
SEALANT APPLIED ON BOTH SIDES OF
WALL.
1 HOUR FIRE RATED THROUGH PENETRATION
FIRESTOP FOR SINGLE PLASTIC THROUGH
GYPSUM WALLS USING TREMSTOP WS AND
TREMSTOP MGR
R -i1 INSULATION
BETWEEN STUDS
TREMSTOP MGR - PREFABRICATED STEEL —,
COLLAR WRAPPED OVER THE WRAP STRIPS
AND MECHANICALLY FASTENED TO BOTH
SIDES OF THE WALL ASSEMBLY
1= OUfR 455 115L `' F N TEAT i ON
WL 2083
1 OR 2 HOUR FIRE RATED THROUGH
PENETRATION FIRE STOP FOR SINGLE
METAL PIPE THROUGH GYPSUM WALLS
USING TREMstop WBM.
F- RATING = 1 and 2 Hr.
ONE LAYER OF 5/8" TYPE 'X' GYPSUM T- RATING -0 and 1/2 Hr.
WALLBOARD ON EACH SIDE OF 3 -5/8"
METAL STUDS, a 24" O.C.
1 HR FIRE RATED CONSTRUCTION
TEST "WP -1200 (AS PER FIRE RESISTANCE
DESIGN MANUAL)
R -11 INSULATION
BETWEEN STUDS
A) METAL PIPE - NOM. 6" DIAM, l OR WHEN REQUIRED
SMALLER) SCH. 40 for heavier) STEEL
B) CONDUIT - 4" DIA. (or smaller) EMT
OR RIGID STEEL
TREMSTOP WBM WL 151
TREMSTOP WBM - MIN. THICKNESS A5T 1 E814
OF SEALANT FROM TABLE BELOW
APPLIED WiTHIN OPENING. FLUSH
WiTH BOTH SIDES OF WALL ASSEMBLY.
Pipe Annular Min. Sealant F T
or Space, Thickness, Rating, Rating,
Conduit In. in. Hr. Hr.
Pipe 3/4 1 -1/4 2 1/2
Conduit 3/4 3/4 1 0
1= HCU1� 4�5 �5L � FEN TFRAT i CN
WL -1051
1 OR 2 HOUR FIRE RATED THROUGH
PENETRATION FIRE STOP FOR SINGLE
VENT DUCT THROUGH GYPSUM WALLS
USING TREMCO 'FYRE- SHIELD'
NOTE: DRYER VENT SHALL BE 4" DIA. (MIN.) F- RATING - I and 2 Hr.
T- RATING -0
CLOTHES DRYER EXHAUST VENT, SHALL BE 26
GAUGE GALV. STEEL SHALL NOT BE SCREENED,
AND SHALL HAVE A SMOOTH INTERIOR SURFACE
WITH JOINTS RUNNING IN THE DIRECTION OF THE
AIR FLOW. DUCT JOINTS SHALL NOT BE ASSEMBLED LINE DENOTES ALT.
WITH SHEET METAL SCREWS OR OTHER FASTENERS j DIRECTION OF VENT
WHICH EXTEND INTO THE DUCT. THRU -ROOF TRUSS
DUCT TO BE RIGIDLY SUPPORTED ON BOTH SIDES
OF THE WALL ASSMEBLY. THE ANNULAR SPACE i
SHALL BE MIN. 1/4" TO MAX. 5/8" WITHIN THE
FIRESTOP SYSTEM.
/ \ / \ /I� � `. I\
�TREMCO 'FYRE- SHIELD' - MIN. 1/2" THICKNESS OF
SEALANT APPLIED WITHIN THE OPENING, FLUSH
WITH ADDITIONAL SEALANT TO BE INSTALLED SUCH
THAT A MIN. 114" CROWN IS FORMED AROUND
THE PENETRATING ITEM.
ONE LAYER OF 5/8" TYPE 'X' GYPSUM
WALLBOARD ON EACH SIDE OF 3 -5/8"
METAL STUDS, is 24" O.G.
i HR FIRE RATED CONSTRUCTION
TEST "WP -1200 (AS PER FIRE RESISTANCE
DESIGN MANUAL)
ID 1�� 1R \/ENT WAS
WL-1011
UJL 1011
R -11 INSULATION
BETWEEN STUDS
WHERE REQUIRED
PENEfiATION
L
TURN HEAD PIPE DOWN INTO STACic
LEAD COVER
CEMENT TILE (REFER TO TYP. WALL
SECTION)
SOLDERED LAP SEAM
MEMBER FLASHING —,
LEAD BASE
19/32" PLYWOOD SHEATHING,
REER TO TYP. WALL SECTION 4"
FOR METHOD OF ATTACHMENT
NOTE:
ANY FIRE VENT WITHIN 10' -0" OF
ANY DOOR WINDOW OR EXHAUST
OPNGS. SHALL EXTEND NOT LESS
THAN 3' -0" ABOVE SUCH
ROOF VENT FL ASS f NG [DETAIL NTT.
F- Rating = 1 and 2 Hr.
T- Rating = 0 Hr.
COLD WA7ti -
GATE VALVE
ELECTRIC WATER HEATER
WITH 5 -YEAR WARRANTY,
GLASS LINED TANK, DOUBLE
ELEMENT NON - CONCURRENT
ENERGY EFFICIENT INSULATION 66GAL.
MEETING ASHRAE 90A -1980
MIN. INSULATION R -16
0B8 EF.
WHEN THE WATER HEATER
IS INSTALLED ABOVE THE
GROUND FLOOR SLAB, PROVIDE
A MIN. 2" DEEP APPROVED DRAIN
PAN. IF THE PAN IS CIRCULAR
THE PAN SHALL HAVE A DIA.
4" LARGER THAN THE W.H.
IF THE PAN IS SQUARE THE SIDES
SHALL BE 2" LONGER THAN THE W.H.
i i i I A =P= "-- *-==,% i If-- h =P= t====:—% *—a 4==== =P= n I I
ASME PREP
RELIEF VALVE.;..
1
DRAIN VALVE SHALL BE POS!
TO FACE CORNER OF DRAiN PAt-,,.
1" DRAIN OUTLET, LOCATED
1/2" ABOVE BOTT. OF DRAIN
PAN.
•2" DRAIN PIPE (BELOW SLAB ONLY)
TO OUTSIDE OF BLDG. EXTERIOR
NOT MORE THAN 6" ABOVE GRADE.
1 OR 2 HOUR FIRE RATED
ONE LAYER OF 5/8" TYPE 'X' GYPSUM PENETRATION FIRE STOP FOR MULTIPLE
WALLBOARD ON EACH SIDE OF 3 -5/8" CABLES THROUGH GYPSUM WALLS
METAL STUDS, 6 24" O.C.
USING TREMstop IA
MAX.DIAMATER OF OPENING =3 -1/2" F- RATING = 1 and 2 Hr.
1 HR FIRE RATED CONSTRUCTION T- RATING =
TEST "WP -1200 (AS SISTANC I/4 and 1/2 Hr
DESIGN MANUAL)
CABLES -A- MAX. FOUR ALUMINUM OR ROME _
CONDUCTOR No 2/0 AWG (OR SMALLER)
ALUMINUM METAL CLAD
CABLE. MAX. ONE CABLE WITHIN FIRE STOP =
SYSTEM. ANNULAR SPACE SHALL BE MIN.I /4" _
TO MAX. 1" —
CABLES -B- MAX. FOUR ALUMINUM OR ROMEX =
CONDUCTOR No 2/0 AWG (OR SMALLER)
TYPE SER CABLE WITH PVC. INSULATION. _
MAX. TWO CABLES BUNDLED TOGETHER =
WITHIN FIRE STOP SYSTEM ANNULAR SPACE _
O SHALL BE FROM MiN. 1/2" TOM AX. 1 -1/2 ". —
1 Pre -Rated Gypsum Wallboard /Stud Wall Assembly
2Q Metallic Pipe - A) Steel Pipe - 8" diem. (or smaller) Sch. 40 (or heavier) steel pipe.
B) Iron Pipe - 8" diem. (or smaller) cast or ductile iron pipe.
C) Conduit - 4" diem. (or smaller) EMT or rigid steel conduit.
D) Copper Tubing - 4" diem. (or smaller) Type L for heavier) copper tubing.
E) Copper Pipe - 4" diam. (or smaller) Regular (or heavier) copper pipe.
TREMSTOP 1A
The annular space shall be min. 1/4" to max. 5/8" within the firestop system.
3 FYRE- SHIELD - Min. 1/2" thickness of sealant applied within opening. Additional sealant TREMSTOP T I NOM. i/2" THICKNESS OF SEALANT
0 pp p g• APPLIED WITHIN THE ANNULUS FLUSH
to be installed such that a min. 1/4" crown is formed around the WITH BOTH SURFACES OF WALL
T- RATINGO /4 Hr. FOR F- RATING OF 1 Hr.
penetrating item. T- RATING -1/2 Hr. FOR F- RATING OF 2 Hr.2
1�2�k4OUF--,, A5&Et"-15L"� FENETFRATION 2 k4CUR
WL 109-1
1 OR 2 HOUR FIRE RATED
ONE LAYER OF 5/8" TYPE 'X' GYPSUM PENETRATION FIRE STOP FOR MULTIPLE
CABLES THROUGH GYPSUM WALLS
WALLBOARD ON EACH SIDE OF 3 -5/8°
USING TREMstop IA
METAL STUDS, 6 24" O.C.
MAX.DIAMATER OF OPENING- 3 -1/2" F- RATING - 1 and 2 Hr.
1 HR FIRE RATED CONSTRUCTION T- RATING =114 and 1/2 Hr
TEST "WP -1200 (AS PER FIRE RESISTA
DESIGN MANUAL)
CABLES -A- MAX. FOUR ALUMINUM OR ROME
CONDUCTOR No 2/0 AWG (OR SMALLER) R -11 INSULATION
BETWEEN STUDS
ALUMINUM METAL CLAD WHERE REQUIRED
GABLE. MAX. ONE CABLE WITHIN FIRE STOP
SYSTEM. ANNULAR SPACE SHALL BE MIN.1 /4"
TO MAX. 1"
GABLES -B- MAX. FOUR ALUMINUM OR ROMEX
CONDUCTOR No 2/0 AWG (OR SMALLER)
TYPE SER CABLE WITH PVC. INSULATION.
MAX. TWO CABLES BUNDLED TOGETHER
SHALL BE FROM MIN. 11/2" fANNULAR . 1- 1 /2PACE
TREMSTOP 1A
TREMSTOP IA -NOM. 1/2" THICKNESS OF SEALANT
APPLIED WITHIN THE ANNULUS FLUSH
WITH BOTH SURFACES OF WALL
T- RATING =1 /4 Hr. FOR F- RATING OF 1 Hr.
T- RATING =1 /2 Hr. FOR F- RATING OF 2 Hr.
1=2 HCUFR 455 11 ""r F N TFRAT i ON
WL 3131
WL 3131
I T5,
8 "X 8 "X 16"
CONC. BLOCK
J9
ENETF-,AT f ON
DETAILS PLUMBING PLAN
1/411 = 1' -0"
1
4�
r'
4
r
o
a
Cn CD
w
w C CD
01 o
C)
� n D1 •f�1 (") 7
o �,N o�
w o
a
Cn
U
(A
. 4/
N
N II
jf
e�
I
I
0
00
I
cn
00
rn
I
Cn
0
r�
AWN B
J J. M. - k
ATE;
S
�E T