05-66-016I ONE LAYER OF 5/8" TYPE 'X' GYPSUM WALLBOARD ON EACH SIDE OF 3 -5/8" METAL STUDS, ,o 24" O.C. I HR FIRE RATED CONSTRUCTION TEST "WP -1200 (AS PER FIRE RESISTANCE DESIGN MANUAL) PLASTIC PIPE - NOM. 6" DIAM. ( OR SMALLER) SCH. 40 PVC PIPE FOR USE IN OPEN OR CLOSED PIPING SYSTEMS. THE ANNULAR SPACE SHALL BE 0" MIN. TO MAX. 3/8" TREMSTOP WBM —/-� TREMSTOP WS - TWO STACKS OF INTUSCEMENT WRAP STRIPS, CONTINUOUSLY WRAPPED AROUND THE OUTER CIRCUMFERENCE OF THE PIPE, EIGHT TIMES ON BOTH SIDES OF THE WALL TREMSTOP WBM - MIN. 1/4" THICKNESS OF SEALANT APPLIED AT THE INTEFZFACE OF THE WALL AND COLLAR, AND THE INTERFACE OF THE COLLAR AND PIPE. SEALANT APPLIED ON BOTH SIDES OF WALL. 1 HOUR FIRE RATED THROUGH PENETRATION FIRESTOP FOR SINGLE PLASTIC THROUGH GYPSUM WALLS USING TREMSTOP WS AND TREMSTOP MGR R -i1 INSULATION BETWEEN STUDS TREMSTOP MGR - PREFABRICATED STEEL —, COLLAR WRAPPED OVER THE WRAP STRIPS AND MECHANICALLY FASTENED TO BOTH SIDES OF THE WALL ASSEMBLY 1= OUfR 455 115L `' F N TEAT i ON WL 2083 1 OR 2 HOUR FIRE RATED THROUGH PENETRATION FIRE STOP FOR SINGLE METAL PIPE THROUGH GYPSUM WALLS USING TREMstop WBM. F- RATING = 1 and 2 Hr. ONE LAYER OF 5/8" TYPE 'X' GYPSUM T- RATING -0 and 1/2 Hr. WALLBOARD ON EACH SIDE OF 3 -5/8" METAL STUDS, a 24" O.C. 1 HR FIRE RATED CONSTRUCTION TEST "WP -1200 (AS PER FIRE RESISTANCE DESIGN MANUAL) R -11 INSULATION BETWEEN STUDS A) METAL PIPE - NOM. 6" DIAM, l OR WHEN REQUIRED SMALLER) SCH. 40 for heavier) STEEL B) CONDUIT - 4" DIA. (or smaller) EMT OR RIGID STEEL TREMSTOP WBM WL 151 TREMSTOP WBM - MIN. THICKNESS A5T 1 E814 OF SEALANT FROM TABLE BELOW APPLIED WiTHIN OPENING. FLUSH WiTH BOTH SIDES OF WALL ASSEMBLY. Pipe Annular Min. Sealant F T or Space, Thickness, Rating, Rating, Conduit In. in. Hr. Hr. Pipe 3/4 1 -1/4 2 1/2 Conduit 3/4 3/4 1 0 1= HCU1� 4�5 �5L � FEN TFRAT i CN WL -1051 1 OR 2 HOUR FIRE RATED THROUGH PENETRATION FIRE STOP FOR SINGLE VENT DUCT THROUGH GYPSUM WALLS USING TREMCO 'FYRE- SHIELD' NOTE: DRYER VENT SHALL BE 4" DIA. (MIN.) F- RATING - I and 2 Hr. T- RATING -0 CLOTHES DRYER EXHAUST VENT, SHALL BE 26 GAUGE GALV. STEEL SHALL NOT BE SCREENED, AND SHALL HAVE A SMOOTH INTERIOR SURFACE WITH JOINTS RUNNING IN THE DIRECTION OF THE AIR FLOW. DUCT JOINTS SHALL NOT BE ASSEMBLED LINE DENOTES ALT. WITH SHEET METAL SCREWS OR OTHER FASTENERS j DIRECTION OF VENT WHICH EXTEND INTO THE DUCT. THRU -ROOF TRUSS DUCT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF THE WALL ASSMEBLY. THE ANNULAR SPACE i SHALL BE MIN. 1/4" TO MAX. 5/8" WITHIN THE FIRESTOP SYSTEM. / \ / \ /I� � `. I\ �TREMCO 'FYRE- SHIELD' - MIN. 1/2" THICKNESS OF SEALANT APPLIED WITHIN THE OPENING, FLUSH WITH ADDITIONAL SEALANT TO BE INSTALLED SUCH THAT A MIN. 114" CROWN IS FORMED AROUND THE PENETRATING ITEM. ONE LAYER OF 5/8" TYPE 'X' GYPSUM WALLBOARD ON EACH SIDE OF 3 -5/8" METAL STUDS, is 24" O.G. i HR FIRE RATED CONSTRUCTION TEST "WP -1200 (AS PER FIRE RESISTANCE DESIGN MANUAL) ID 1�� 1R \/ENT WAS WL-1011 UJL 1011 R -11 INSULATION BETWEEN STUDS WHERE REQUIRED PENEfiATION L TURN HEAD PIPE DOWN INTO STACic LEAD COVER CEMENT TILE (REFER TO TYP. WALL SECTION) SOLDERED LAP SEAM MEMBER FLASHING —, LEAD BASE 19/32" PLYWOOD SHEATHING, REER TO TYP. WALL SECTION 4" FOR METHOD OF ATTACHMENT NOTE: ANY FIRE VENT WITHIN 10' -0" OF ANY DOOR WINDOW OR EXHAUST OPNGS. SHALL EXTEND NOT LESS THAN 3' -0" ABOVE SUCH ROOF VENT FL ASS f NG [DETAIL NTT. F- Rating = 1 and 2 Hr. T- Rating = 0 Hr. COLD WA7ti - GATE VALVE ELECTRIC WATER HEATER WITH 5 -YEAR WARRANTY, GLASS LINED TANK, DOUBLE ELEMENT NON - CONCURRENT ENERGY EFFICIENT INSULATION 66GAL. MEETING ASHRAE 90A -1980 MIN. INSULATION R -16 0B8 EF. WHEN THE WATER HEATER IS INSTALLED ABOVE THE GROUND FLOOR SLAB, PROVIDE A MIN. 2" DEEP APPROVED DRAIN PAN. IF THE PAN IS CIRCULAR THE PAN SHALL HAVE A DIA. 4" LARGER THAN THE W.H. IF THE PAN IS SQUARE THE SIDES SHALL BE 2" LONGER THAN THE W.H. i i i I A =P= "-- *-==,% i If-- h =P= t====:—% *—a 4==== =P= n I I ASME PREP RELIEF VALVE.;.. 1 DRAIN VALVE SHALL BE POS! TO FACE CORNER OF DRAiN PAt-,,. 1" DRAIN OUTLET, LOCATED 1/2" ABOVE BOTT. OF DRAIN PAN. •2" DRAIN PIPE (BELOW SLAB ONLY) TO OUTSIDE OF BLDG. EXTERIOR NOT MORE THAN 6" ABOVE GRADE. 1 OR 2 HOUR FIRE RATED ONE LAYER OF 5/8" TYPE 'X' GYPSUM PENETRATION FIRE STOP FOR MULTIPLE WALLBOARD ON EACH SIDE OF 3 -5/8" CABLES THROUGH GYPSUM WALLS METAL STUDS, 6 24" O.C. USING TREMstop IA MAX.DIAMATER OF OPENING =3 -1/2" F- RATING = 1 and 2 Hr. 1 HR FIRE RATED CONSTRUCTION T- RATING = TEST "WP -1200 (AS SISTANC I/4 and 1/2 Hr DESIGN MANUAL) CABLES -A- MAX. FOUR ALUMINUM OR ROME _ CONDUCTOR No 2/0 AWG (OR SMALLER) ALUMINUM METAL CLAD CABLE. MAX. ONE CABLE WITHIN FIRE STOP = SYSTEM. ANNULAR SPACE SHALL BE MIN.I /4" _ TO MAX. 1" — CABLES -B- MAX. FOUR ALUMINUM OR ROMEX = CONDUCTOR No 2/0 AWG (OR SMALLER) TYPE SER CABLE WITH PVC. INSULATION. _ MAX. TWO CABLES BUNDLED TOGETHER = WITHIN FIRE STOP SYSTEM ANNULAR SPACE _ O SHALL BE FROM MiN. 1/2" TOM AX. 1 -1/2 ". — 1 Pre -Rated Gypsum Wallboard /Stud Wall Assembly 2Q Metallic Pipe - A) Steel Pipe - 8" diem. (or smaller) Sch. 40 (or heavier) steel pipe. B) Iron Pipe - 8" diem. (or smaller) cast or ductile iron pipe. C) Conduit - 4" diem. (or smaller) EMT or rigid steel conduit. D) Copper Tubing - 4" diem. (or smaller) Type L for heavier) copper tubing. E) Copper Pipe - 4" diam. (or smaller) Regular (or heavier) copper pipe. TREMSTOP 1A The annular space shall be min. 1/4" to max. 5/8" within the firestop system. 3 FYRE- SHIELD - Min. 1/2" thickness of sealant applied within opening. Additional sealant TREMSTOP T I NOM. i/2" THICKNESS OF SEALANT 0 pp p g• APPLIED WITHIN THE ANNULUS FLUSH to be installed such that a min. 1/4" crown is formed around the WITH BOTH SURFACES OF WALL T- RATINGO /4 Hr. FOR F- RATING OF 1 Hr. penetrating item. T- RATING -1/2 Hr. FOR F- RATING OF 2 Hr.2 1�2�k4OUF--,, A5&Et"-15L"� FENETFRATION 2 k4CUR WL 109-1 1 OR 2 HOUR FIRE RATED ONE LAYER OF 5/8" TYPE 'X' GYPSUM PENETRATION FIRE STOP FOR MULTIPLE CABLES THROUGH GYPSUM WALLS WALLBOARD ON EACH SIDE OF 3 -5/8° USING TREMstop IA METAL STUDS, 6 24" O.C. MAX.DIAMATER OF OPENING- 3 -1/2" F- RATING - 1 and 2 Hr. 1 HR FIRE RATED CONSTRUCTION T- RATING =114 and 1/2 Hr TEST "WP -1200 (AS PER FIRE RESISTA DESIGN MANUAL) CABLES -A- MAX. FOUR ALUMINUM OR ROME CONDUCTOR No 2/0 AWG (OR SMALLER) R -11 INSULATION BETWEEN STUDS ALUMINUM METAL CLAD WHERE REQUIRED GABLE. MAX. ONE CABLE WITHIN FIRE STOP SYSTEM. ANNULAR SPACE SHALL BE MIN.1 /4" TO MAX. 1" GABLES -B- MAX. FOUR ALUMINUM OR ROMEX CONDUCTOR No 2/0 AWG (OR SMALLER) TYPE SER CABLE WITH PVC. INSULATION. MAX. TWO CABLES BUNDLED TOGETHER SHALL BE FROM MIN. 11/2" fANNULAR . 1- 1 /2PACE TREMSTOP 1A TREMSTOP IA -NOM. 1/2" THICKNESS OF SEALANT APPLIED WITHIN THE ANNULUS FLUSH WITH BOTH SURFACES OF WALL T- RATING =1 /4 Hr. FOR F- RATING OF 1 Hr. T- RATING =1 /2 Hr. FOR F- RATING OF 2 Hr. 1=2 HCUFR 455 11 ""r F N TFRAT i ON WL 3131 WL 3131 I T5, 8 "X 8 "X 16" CONC. BLOCK J9 ENETF-,AT f ON DETAILS PLUMBING PLAN 1/411 = 1' -0" 1 4� r' 4 r o a Cn CD w w C CD 01 o C) � n D1 •f�1 (") 7 o �,N o� w o a Cn U (A . 4/ N N II jf e� I I 0 00 I cn 00 rn I Cn 0 r� AWN B J J. M. - k ATE; S �E T