05-1333(2)-026GENERAL HVAC NOTES 1. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIAL AND EQUIPMENT FOR A COMPLETE HVAC SYSTEM INACCORDANCE WITH THESE DRAWINGS. THE FLORIDA BUILDING CODE 2002 AND THE LATEST EDITION OF THE FOLLOWING PUBLICATIONS: (A) ANS 89.1 MECHANICAL REFRIGERATION (8) NFPA PAMPHLETS 90A & 91 (C) SMACNA (D) ASHRAE. 2 ALL AIR CONDITIONING DUCTWORK SHALL BE V 1/2 "STANDARD DUTY FOIL REINFORCED FIBERGLASS (R 6) MANUFACTURED LOGO PRINTED ON THE VAPOR BARRIER WHEN IN UNCONDITIONED SPACE, AND 3/4 "STANDARD DUTY FOIL REINFORCED FI8ERGLASS (R -4) MANUFACTURED LOGO PRINTED ON THE VAPOR BARRIER IN CONDITIONED SPACE OR RETURN PLENUM SPACE 3. ALL EXHAUST DUCTWORK SHALL BE CODE GAGE GALVANIZED SHEET METAL. 4. DUCT SIZE SHOWN ARE NET FREE AREA INSIDE. 5. ALL AIR DEVICES (DIFFUSERS, REGISTERS AND GRILLES) SHALL BEALL ALUMINUM CONSTRUCTION, WITH EXPOSED SURFACE CHEMICALLY TREATED TO RECEIVE PAINT TO MATCH COLOR OR AIR GUIDE OR APPROVED EQUAL. J. PROVIDE OPPOSED BLADE DAMPERS ATALL DIFFUSERS AND REGISTERS. Z THERMOSTATS SHALL BE COMBINATION COOLING / HEATING PROGRAMMABLE /AUTO / HEAT/ OFFAND FAN ON /AUTO SELECTOR SWITCHES. & REFRIGERANT PIPING SHALL BE COPPER TYPE'l" WITH 112 'ARMAFLEX. INSULATION SHALL BE PROVIDED FOR SUCTION LINES. 9. PROVIDE NEW FILTERS FOR FAN COIL BEFORE STARTING. THESE FILTERS MUST ALSO BE REPLACED PRIOR TO FINAL ACCEPTANCE BY OWNER. 10. GENERAL CONTRACTOR IS TO HIRE AN INDEPENDENT TEST AND BALANCE COMPANY WHICH SHALL PROVIDE 3 SET OF THE REPORT SIGN AND SEALED BY THE PROFESSIONAL ENGINEER FROM THE COMPANY PRIOR OF ACCEPTANCE OF WORK 11. MECHANICAL CONTRACTOR ITS TO PROVIDE TURNING VANEAT ALL CHANGE OF DIRECTIONS OR TO PROVIDE TURNING RADIO, ALL OUTLETS SHALL HAVE EXTRACTORS OR SCUPPERS. AND SHALL BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE REGULATIONS. LEGEND EF - T SHALL BE.' 2024 CD (SEE SCHEDULE) MANUF: NUTONE DUCT TO MATCH NECK SIZE TYP. ® CEILING GRILLE SEE SIZE SCHEDULE SO CFM DUCT TO MATCH NECK SIZE TYP. © RETURN AIR GRILL ELECTRICAL SERVIC:115 /1/60 VOLUME DAMPER OT PROGRAMMABLE THERMOSTAT D DUCT MOUNTED SMOKE DETECTOR D SEE FA RISER FOR SPECS. 16" DEPTH OR LESS AIR FLOW DIRECTION [ARROWS DENOTE —� I WAY, 2 WAY, ETC., SEE PLANS -,✓`�- RETURN OR EXHAUST, SEE PLANS. 18.0 1 67 1 80 230 i 1 1 7.5 1.7 61.0 — TRANE TWE0421`13F6 WALL MOUNTED SIDE REGISTER. i f i EXHAUST FAN 12.00 SHOWN OAL OUISIDEAIR INTAKE 6R SIDE REGISTER co CEILING DIFFUSER CG CEILING GRILL NP. HEAT PUMP UNIT dox UNLESS OTHERWISE NOTED. RN ROOF TOP UNIT ANTI AIR HANDLER UNIT GU CONDENSING UNIT EF EXHAUST FAN CHI CU81C FEET PER MINUTE TF, THERMOFIN LLG UNDERCUT app BACKDRAFT DAMPER. EF - T SHALL BE.' EF- 2 ON MASTER BATHROOM MANUF: NUTONE SHALL BE: MODEL: 696 N MANUF: NUTONE SO CFM MODEL: 672 R F. L.A : 0.75 110 CFM ELECTRICAL SERVIC:115 /1/60 FL.A:0.70 25 SONES REMARK: WATER & VAPOR PROFF 61.0 WITH GH BRANCH CIRCUIT 80 i 230 i 1 1 10 4.0 SONES f �'� 0o GLR CONDENSING UNIT -� 4" THICK CONCRETE BASE NOTE.• PROVIDEANCHOR BOLT WITH A MINIMUM OF 500 POUND PULL -OUT RESISTANCE. SHALL SECURE THE AIR CONDITIONING CONDENSER UNIT FROM WITHIN THE UNIT TO THE CONCRETE SLAB ON WHICH THE UNIT RESTS TO WITHSTAND 150 MPH HURRICANE FORCE. CU MOUNTING DETAIL N.T.S. 4"0 EXHAUST DUCT TEEL HANGER WIRE CEILING CABINET EXHAUST H BACK DRAFT DAMPER, LOW EVEL AND NO VIBRATION POWER & CONTROL LOCATION NULONE W/O INSULATION LIQUID \_ SUCTION LINE W/ 1/Z'ARMAFLEX INSULATION & VAPOR BARRIER FROM FACE GRILLE WITH FASTENING SCREENS - EXHAUST FAN HANGING BRACKET (ADJUSTABLE) CEILING MOUNTED CABINET EXHAUST FAN DETAIL N.I.S. SUPPLY _ AIR DUCT 1 AITK: SPACE PROVIDER MIN. OF 4 "SPACE OFAHU SIDE TO ASSURE ADEQUATEACCESS FOR CONSTRUCTION & CLEANING COIL /HEAT SECTION L FAN SECTION - FILTER ACCESS - DISCHARGED SHALL BE MECHANICAL ATTACHED TO AHU �- CEILING WALLS r REF. LINES lPROVIDE CAP -OFF W/ 1 /4" PERFORATED FOR VENT —� 12"MIN. PROVIDE E.I. TRAP FLOW SWITCH COMBUSTIBLE MATERIALS ON SECONDARY C.D. DRAIN TO NO ALLOWED S PLENUM ��� \� SHUT DOWN THE UNIT IN CASE OF OVER FLOW. PREFAB MTL. FRAME F.F. A/C CLOSET INSTALLATION N.T.S. NOTE: THE A/C CONTRACTOR SHALL COORDINATE W/ TRUSS MANUFACTURER' SHOP DRAWINGS TO GUARANTEEALL NECESSARY TRUSS OPENING FOR DUCT WORK INSTALLATION. NO CHANGE OF THIS DESIGN ALLOWED. FAN-0011- i DESIGNATON CFM MBTUH ENTERING F 1 ELECTRICAL DATA ; MANUFAC. REF. UNIT I OBS TOTAL SENSIBLEi WS D8 i VOLTS PHASES !HTNGKW AHUFAN FL.A. FUSES L/Q. ! _SUC. COND. I AHU -2 2000 61.0 45.7 i 67 80 i 230 i 1 1 10 3.9 16" DEPTH OR LESS TRANS j TWE063P 13FB 318 i 1-118 1 1 AHU -1 800 25.0 18.0 1 67 1 80 230 i 1 1 7.5 1.7 61.0 — TRANE TWE0421`13F6 5116 ! 314 i 314" 1 1 37 50 I TRANE 2TTR206081000A 12.00 SHOWN CU -1 i 25.0 95 230 l 11 AHU�3 & 4 - -- -- 600 - 18.8 13.8 67 -- - - 80 230 ; 1 I 5 - -- -- j-- - - 1.4 - -- TRANE ! TWE018P 13FB 174 518 314" + LOAD AT 125% AS PER MANUFACTER SPECS. NOTE 1. FLEXIBLE DUE SHALL BE ONE PIECE & SHALLBE SPLICED TOGETHER. Z -MAX. SAG 117PER FOOT BETWEN SUPPORT POINTS. AND 5'O" MAX. OF SUPPORT SPACING. HANGERS AND SUPPORTS DETAIL N.T.S. STANDARD 311 WIDE HANGERS HANGER EXTENSION IS DEFINED AS THE SUM OF THE DISTANCES BETWEEN THE HANGING WIRES AND THE DUCT WALLS (BOTH SIDES) TABLE 4 -1 MAXIMUN HANGER TABLE 4-2 CHANNEL SELECTION SPACING BY DUCT SIZE, ID. DUCT SIZE, INCHES CONDENSING UNIT DESIGNATION! MBTUN TEMP. ENT. _ ELECTRICAL DATA 1 MANUFAC. REF UNIT OBS OR SEER AREA SERVED ! CONDENSER VOLTS PHASES !WIRE AMPS FUSES ; LESS THAN 28" WIDE AND ? 8 FT 16" DEPTH OR LESS 2 -7716 - - - -- 6, Z 8, 9, 10, 12 i MP-39 2 -1 i/Id 4 -7%16 6%16 17-15116 CU -2 ! 61.0 95 230 1 1 37 50 I TRANE 2TTR206081000A 12.00 SHOWN CU -1 i 25.0 95 230 l 11 15 ; TRANE 2TTR2024A IOOOA 12.75 SHOWN 1 CU-3&4 91.0 95 230 1 i 10 15 1 TRANE 2TTR2018AI000A 12.75 SHOWN NOTE 1. FLEXIBLE DUE SHALL BE ONE PIECE & SHALLBE SPLICED TOGETHER. Z -MAX. SAG 117PER FOOT BETWEN SUPPORT POINTS. AND 5'O" MAX. OF SUPPORT SPACING. HANGERS AND SUPPORTS DETAIL N.T.S. STANDARD 311 WIDE HANGERS HANGER EXTENSION IS DEFINED AS THE SUM OF THE DISTANCES BETWEEN THE HANGING WIRES AND THE DUCT WALLS (BOTH SIDES) TABLE 4 -1 MAXIMUN HANGER TABLE 4-2 CHANNEL SELECTION SPACING BY DUCT SIZE, ID. DUCT SIZE, INCHES .... .....................-• ........... MAXIMUN HANG..• ER NOMINAL LENGTH SPACING ---------- ------------------------- ------ i 48" WIDE OR GREATER --•----------------------- ....... ............. < 4 FT LESS THAN 48" WIDEAND -^ 6 FT —^ LESS THAN 48" DEEP 1 _ .. .................................. ..................... .........� -- --- ----------< WIDTH BETWEEN 28 "& 48" �--------- AND GREATER THAN 16" DEEP ; LESS THAN 28" WIDE AND ? 8 FT 16" DEPTH OR LESS 2 -7716 - - - -- IF TOTAL EXTENSION IS MAXIMUN CHANNEL MINIMUM CHANNEL NOT GREAT TITAN: j GAUGE PROFILE 6" i 24 3 "X 1.5" i 18" i 22 3 "X 2" -------------- ---- I ------------------ -------_- ................. ........................ --............... ..............................3j 30" 18 3'X 2" 1 USE OF 2 HANGERS 22 GAUGE, Z' X 1.5" HANGERS MAY BE SUBSTITUTED FOR 3" HANGERS INIW i 1.5 2 3 6 16 18 24 28 30 I 48 = 80 FOR DUCTS WITH WIDTHS NOT OVER 48 "AND DEPTHS NOT OVER 24' 1 ° ..................4'1 1 ........... { ' PROVIDED THAN ONE JOINT OCCURS BTWEEN HANGERS AND THE iii 51 i 76 152 _41 M . 46 M. ;61 M _; .71 M J6 M T.22 M 2.0.3 M MAXIMUN HANGER SPACING IS 4 FT. EXCEPTION: WHEN DUCT PERIMETER IS 80' OR LESS AND DOES NOT REQUIRE REINFORCEMENT TWO PERMITTED FT ? 4 6 ;' 8 18 GA 22 GA ! 24 GA ; BETWEEN HANGERS. 4.......1 .......:....... °f ° I M 38 FT ? 76 152 .7534 .6010 3 14 "DEEPx 1/8'POWEREO _ ACTUATED PINS ��II FLEX DUCT UP TO 29 'WITH ORIG" DEEP LOCKING QUADRANT TO BE EXPOSED GALV. STEEL ROD OR STRAP SUPPORTS PER SMACNA STANDARDS (SEE NOTE #2) - - - IL V 1/2" WIDE x 26 GA STRAP @ 8" O/C PINS RIGID DUCT UP TO 29" WITH OR 16" DEEP _ 3A-WIDE 26 GA G.M. STRIP AT SUPPORT DUCT HANG DETAIL 1 1/2" (R -6') STANDARD OR SHEET METAL SUPPLY DUTY FOIL REINFORCED DUCT W12" THK. WRAP FIBERGLASS W/VAPOR INSULATION (R -6) �\ BARRIER SUPPLY DUCT SPIN IN TAP FITTING WITH AIR SCOOP & DAMPER U 112"X V 112"X 1/8" GALV. ANGLE OR STRAP PER SMACNA - - - - NYLON DRAWBAND AND MASTIC AT EACH CONNECTION N.T.S. ML/ LM R IN WIDTH (IN) NOMINAL LENGTH AVAILABLE - - -_ -- NUMBEROFSLOTS L IN INLETS /COLLAR IN TYPE 1 _ 2 _ 13 14 24 4, 5, 6, 7, 8, 9, 10 MP -37 2- 3716 3-7716 4-1111615-15116 36 4, 5, 6, 7, 8, 9, 10 MP,38 2 -7716 3- 15116 5- 7116 6 15116 48 6, Z 8, 9, 10, 12 i MP-39 2 -1 i/Id 4 -7%16 6%16 17-15116 _ 60 _ 6, 7, 8, 9, 10, 12 FLEXIBLE DUCT W71 "THK (R 6) INSULATION & VAPOR BARRIER MAX DUCT COLLAR RUN TO BE 8'0" ____] % VPPERATTACHMENl / W PER SMACNA 1 (SEE NOTE #2) I ' MIN. 2" WIDE 22 \ GALV. STRAP HANGER W /HEMMED EDGES PER SMACNA FIG. 3.10 - -- - -- - SUSPENDED CEILING TITUS ML-37,38 OR 39 LINEAR DIFFUSER OR EQUIVALENT TITUS INSUL RECTANGL PLENUM TYPICAL LINEAR DIFFUSER W /FLEXIBLE DUCT CONNECTION N.T.S FXHAUST VENT GAS WH VENT. DETAIL (DIRECT VENT AND SIDE WALL) N.r.s. )MBUSTION PVC VENT TERMINAL 7TH MESH PROTECTIVE ;BEEN INSIDE EXHAUST ENT TERMINAL PVC 450 ELBOW 7TH DRIVER PLATE ND ADAPTER SCREEN 'TAKE VENT TERMINAL i 4" - �o i 3" WALL CAP FOR DRYER AND BATHROOM EXHAUST N. T.S. !I ROOF STRUCTURE - SEEARCHITECTURAL ` PROVIDE W/P CAP LOW PROFILE B.D.D. ` AT TOP, FOR DRYER. NO SCREEN, FOR ! BATHROOM PROVIDE INSECT SCREEN 4-160 NAILS \ ' THRU PLYWOOD V 6 "CLEAR FROM FINISH ROOF DUCT FROM UNIT (SEE J PLAN FOR SIZE &TYPE) TYPICAL ROOF CAP DETAIL DRYER AND /O R TOILET EXH . - DUCT DOUBLE THICKNESS TURNING VANES ELBOW WITH TURNING VANES DETAIL N.T.S., N.T.S. I�,, • ► A 1 • ELECTRICAL • MECHANICAL • PLUMBING CARLOS M. Quo BARRENECHEA PRESIDENT lW< 2740 S.W. 97 AVE. ` WQ SUITE #1 OS o MIAMI, FLA. 1Za 33165 i It 1 u ❑EPICS !� (3051 552 -853S ,!Zz FAx (305) 91 7-451 7 `W E -MAIL CME3 @CM©EN13.COM URL WWW.CMSENU.COM L.C. No. E60007150 P.E. No. 1113613225 ORLANDO RANGEL MECHANICAL ENGINEER a •. - • � PROJECT NUMBER: OS 0033 • BY i r r I 0 8 A b 9 DATE JUL 0 12005 SCALE A5 SHOWN DRAWN PGB JOB 05_0035 SHEET I 1